UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT
CORNER WT (Lb/Kg)
Lb
Kg
A
B
C
D
50HS048
208/230-1-60, 208/230-3-60, 460-3-60
359
163
89/40
81/37
113/51
76/35
50HS060
208/230-1-60, 208/230-3-60, 460-3-60
373
170
92/42
85/39
116/53
80/36
UNIT
CENTER OF GRAVITY (in./mm)
X
Y
Z
50HS048
19.7/500
20.5/522
15.0/381
50HS060
19.7/499
20.6/523
15.0/381
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side . . . . . . . . . . . . . . . . . 30 (762)
Control Box Access Side . . . . . . . . . . . . . . . . 30 (762)
(Except for NEC requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side Opposite Ducts
. . . . . . . . . . . . . . . . . . 30 (762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit
. . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge, First 12 in. (305) of Supply Duct
. . . 1 (25)
NEC REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side
. . . . . . . . . . . 42 (1067)
Unit and Ungrounded Surfaces, Control Box Side . . . .36 (914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . 42 (1067)
LEGEND
CG
— Center of Gravity
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTE: Clearances must be maintained to prevent
recirculation of air from outdoor-fan discharge.
Fig. 4 — Dimensions; Sizes 048,060; Without Base Rail
4