51
NOTE: When using the charging charts, it is important that only the
subcooling/reheat dehumidification coil liquid line solenoid valve be
energized. The subcooling/reheat dehumidification coil liquid line
solenoid valve MUST be energized to use the charging charts and
the outdoor motor speed controller jumpered to run the fan at full
speed.
Fig. 61 — Cooling Charging Chart, 50HJ009,012
With Optional Humidi-MiZer Adaptive
Dehumidification System
NOTE: When using the charging charts, it is important that only the
subcooling/reheat dehumidification coil liquid line solenoid valve be
energized. The subcooling/reheat dehumidification coil liquid line
solenoid valve MUST be energized to use the charging charts and
the outdoor motor speed controller jumpered to run the fan at full
speed.
Fig. 60 — Cooling Charging Chart, 50HJ008
With Optional Humidi-MiZer™ Adaptive
Dehumidification System
NOTE: When using the charging charts, it is important that only the
subcooling/reheat dehumidification coil liquid line solenoid valve be
energized. The subcooling/reheat dehumidification coil liquid line
solenoid valve MUST be energized to use the charging charts and
the outdoor motor speed controller jumpered to run the fan at full
speed.
Fig. 62 — Cooling Charging Chart, 50HJ014
With Optional Humidi-MiZer Adaptive
Dehumidification System