TO USE COOLING CHARGING CHARTS, STANDARD
UNITS — Take the outdoor ambient temperature and read the
suction pressure gage. Refer to appropriate chart to determine
what the suction temperature should be. If suction temperature
is high, add refrigerant. If suction temperature is low, carefully
recover some of the charge. Recheck the suction pressure as
charge is adjusted.
EXAMPLE (Fig. 56):
Circuit 1
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 F
Suction Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig
Suction Temperature should be. . . . . . . . . . . . . . . . . . . . .46 F
(Suction Temperature may vary ±5° F.)
TO USE COOLING CHARGING CHARTS, UNITS
WITH HUMIDI-MIZER™ ADAPTIVE DEHUMIDIFICA-
TION SYSTEM — Refer to the charts (Fig. 60-62) to deter-
mine the proper leaving condenser pressure and temperature.
EXAMPLE: (Fig. 60)
Circuit 1
Leaving Condenser Pressure. . . . . . . . . . . . . . . . . . . . . 300 psig
Leaving Condenser Temperature . . . . . . . . . . . . . . . . . . . .117 F
NOTE: When using the charging charts, it is important that
only the subcooling/reheat dehumidification coil liquid line
solenoid valve be energized. The subcooling/reheat dehumidi-
fication coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller
jumpered to run the fan at full speed.
Replacement Parts —
A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.