Filter fouling is measured by a pressure sensor located in the electrics box.
It is set to 1.5 times the value for the filter when clean (pressure ports upstream and downstream of the filter).
11.1.5 - Standard control elements:
(Factory cables)
-
An intake temperature sensor.
-
A differential pressure sensor: attached to the electrics box, this allows the difference in pressure upstream and downstream of
the filter to be measured, so as to determine whether the filter is fouled.
-
A water leak sensor: this is found at the end of a wound cable located at the bottom of the unit so that it is long enough to extend
downwards into a raised floor, if required, and to be positioned in the area to be monitored. It can be added on request.
It can be added on request.
11.2 - Optional Components
11.2.1 - Heating coil
Moderately tighten the "coil supply" connections to avoid damaging the manifolds.
The coil is adjusted by a two-way or four-way valve equipped with a 0-10V servomotor (mounted and connected).
Coil specifications:
HOT WATER
W40
W53
W78
W100
Coil (1 row)
Number of coils
1
1
1
1
Capacity (l)
3,82
4,92
6,29
6,29
HEATING COIL
W40
W53
W78
W100
W115
Air flow (m3/h)
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
Nominal
Maximum
10 000
13 300
13 300
13 300
18 800
20 500
24 500
27 000
27 000
27 500
Heating capacity (kW)*
36
40
44
44
63
66
71
73
-
-
Heating capacity (kW)**
18
21
23
23
33
34
37
38
-
-
* Conditions: return air 17 °C - 50 %, water temperature 80/60 °C
** Conditions: return air 17 °C - 50 %, water temperature 45/40 °C
Heating coil pressure drop*:
HOT WATER
W40
W53
W78
W100
Nominal water flow (m³/h)
0,9
1,1
1,68
1,9
KV valve
4
4
4
4
∆P Valve only (mWC)
0,6
0,8
1,8
2,3
∆P (Pa) Valve + Coil (mWC)
1,5
1,8
3
3,8
Nominal flow rate
: water ∆T: 20 °C
W40
W53
W78
W100
KV
4
4
4
4
∆P max.¹ Four-way valve
240
240
240
240
∆P max.² Two-way valve
400
400
400
400
11 - TECHNICAL SPECIFICATIONS
51