Table 17 — Fan Performance, 48TJD/TJE/TJF006 Horizontal Discharge Units;
Alternate Motor (Belt)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
1500
730
357
789
420
896
557
990
704
1072
872
1153
1051
1600
770
420
826
483
931
641
1020
788
1101
956
1178
1145
1700
811
494
865
567
966
725
1051
883
1133
1061
1205
1240
1800
852
578
905
651
1002
820
1084
977
1163
1156
1235
1355
1900
894
567
945
757
1037
925
1119
1093
1194
1271
1266
1471
2000
936
778
984
862
1072
1030
1154
1219
1226
1397
1297
1608
2100
978
893
1024
977
1108
1156
1192
1355
1259
1545
1327
1744
2200
1021
1019
1064
1103
1145
1282
1225
1503
1294
1702
1359
1902
2300
1064
1156
1104
1240
1183
1429
1260
1650
1330
1870
1392
2070
2400
1107
1303
1145
1387
1222
1524
1296
1818
1365
2038
1426
2259
2500
1150
1460
1186
1555
1262
1765
1331
1986
1400
2227
1461
2459
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
Rpm
Watts
Rpm
Watts
Rpm
Watts
Rpm
Watts
1500
1221
1229
1256
1366
1283
1387
1303
1282
1600
1252
1334
1311
1524
1340
1660
1330
1692
1700
1278
1439
1345
1650
1397
1849
1424
1986
1800
1303
1555
1371
1776
1433
1996
1480
2196
1900
1330
1671
1396
1902
1460
2133
1517
2364
2000
1362
1818
1422
2038
1485
2270
1544
2522
2100
1393
1965
1452
2185
1510
2427
1570
2674
2200
1423
2122
1483
2354
1538
2585
1594
2821
2300
1454
2291
1515
2532
1571
2758
1623
2976
2400
1485
2480
1544
2721
1604
2947
1657
3152
2500
1518
2679
1574
2905
1633
3134
1692
3345
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2.
indicates field-supplied motor and drive are required.
3. Maximum usable watts input is 1921. Extensive motor and elec-
trical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Table 4.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Alternate motor drive range: 900 to 1300. All other rpms require
field-supplied drive.
7. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .74
Table 18 — Fan Performance, 48TJD/TJE/TJF007 Horizontal Discharge Units;
Standard Motor (Belt)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
1800
885
623
942
700
1047
835
1139
956
1193
1031
1276
1165
1341
1250
1413
1378
1474
1404
1900
928
700
982
779
1084
932
1160
1006
1223
1114
1301
1233
1374
1361
1437
1439
1490
1482
2000
971
787
1022
867
1121
1014
1188
1097
1254
1216
1329
1284
1396
1473
1460
1491
1509
1569
2100
1015
891
1063
998
1140
1064
1196
1140
1272
1292
1354
1404
1413
1552
1475
1534
1529
1700
2200
1060
998
1104
1081
1159
1106
1229
1258
1306
1361
1363
1508
1434
1604
1487
1639
1554
1831
2300
1104
1123
1130
1140
1196
1224
1264
1387
1340
1473
1397
1648
1459
1665
1520
1831
1576
1980
2400
1138
1165
1174
1224
1245
1396
1305
1447
1373
1630
1440
1726
1502
1823
1552
1980
1604
2136
2500
1183
1275
1201
1335
1284
1465
1338
1552
1402
1761
1469
1805
1524
1980
1585
2136
1638
2292
2600
1210
1404
1246
1482
1312
1560
1366
1735
1435
1858
1494
1936
1552
2119
1616
2317
1671
2462
2700
1254
1560
1285
1595
1354
1726
1403
1892
1474
1954
1536
2171
1584
2300
1646
2487
1706
2653
2800
1274
1613
1304
1639
1374
1875
1459
1989
1514
2136
1570
2343
1624
2504
1677
2661
—
—
2900
1318
1726
1345
1814
1412
2050
1496
2240
1529
2300
1603
2521
1671
2725
—
—
—
—
3000
1362
1945
1378
2032
1451
2119
1534
2343
1560
2470
1611
2648
1690
2886
—
—
—
—
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2.
indicates field-supplied motor and drive are required.
3. Maximum usable watts input is 2120. Extensive motor and elec-
trical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Table 4.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Standard motor drive range: 1070 to 1460. All other rpms require
field-supplied drive.
7. To convert watts to bhp:
watts input x motor efficiency
bhp =
746
Motor efficiency = .84
26