background image

The evaporator-fan OFF delay can also be modified. Once

the call for heating has ended, there is a 10-minute period
during which the modification can occur. If the limit switch
trips during this period, the evaporator-fan OFF delay will
increase by 15 seconds. A maximum of 9 trips can occur,
extending the evaporator-fan OFF delay to 180 seconds.

To restore the original default value, reset the power to

the unit.

TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting heating selector lever below room tem-
perature will temporarily shut unit off until space tempera-
ture falls below thermostat setting.

Safety Relief —

A soft solder joint at the suction service

Schrader port provides pressure relief under abnormal tem-
perature and pressure conditions (i.e., fire in building).

Ventilation (Continuous Fan) —

Set fan and sys-

tem selector switches at ON and OFF positions, respec-
tively. Evaporator fan operates continuously to provide
constant air circulation. When the evaporator-fan selector switch
is turned to the OFF position, there is a 30-second delay be-
fore the fan turns off.

Operating Sequence

COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are ener-
gized, and the indoor (evaporator) fan motor (IFM), com-
pressor, and outdoor (condenser) fan motor (OFM) start. The
OFM runs continuously while the unit is in cooling. When
the thermostat is satisfied, compressor contactor (C) is de-
energized and the compressor and OFM shut off. After a
30-second delay, the IFM shuts off. If the thermostat fan
selector switch is in the ON position, the evaporator motor
will run continuously.
HEATING, UNITS WITHOUT ECONOMIZER — When
the thermostat calls for heating, terminal W1 is energized.
To prevent thermostat short-cycling, the unit is locked into
the Heating mode for at least 1 minute when W1 is ener-
gized. The induced-draft motor is energized and the burner
ignition sequence begins. The indoor (evaporator) fan motor
(IFM) is energized 45 seconds after a flame is ignited. On
units equipped for two stages of heat, when additional heat
is needed, W2 is energized and the high-fire solenoid on
the main gas valve (MGV) is energized. When the thermo-
stat is satisfied and W1 is deenergized, the IFM stops after
a 45-second time-off delay.
COOLING, UNITS WITH VARISLIDE™ ECONOMIZER
— When the outdoor-air temperature is above the outdoor-
air thermostat (OAT) setting and the room thermostat calls
for cooling, compressor contactor is energized to start com-
pressor and the outdoor (condenser) fan motor (OFM). The
indoor (evaporator) fan motor (IFM) is energized and the
economizer damper moves to the minimum position. After
the thermostat is satisfied, there is a 30-second delay before
the evaporator fan turns off. The damper then moves to the
fully closed position. When using continuous fan, the damper
moves to the minimum position.

When the outdoor-air temperature is below the OAT set-

ting and the thermostat calls for cooling, the economizer damper
moves to the minimum position. If the supply-air tempera-
ture is above 57 F, the damper continue to open until it reaches
the fully open position or until the supply-air temperature
drops below 52 F.

When the supply-air temperature falls between 57 F and

52 F, the damper will remain at an intermediate open posi-
tion. If the supply-air temperature falls below 52 F, the damper
will modulate closed until it reaches the minimum position
or until the supply air temperature is above 52 F. When the
thermostat is satisfied, the damper moves to the fully closed
position when using AUTO. fan or to the minimum position
when using continuous fan.

If the outdoor air alone cannot satisfy the cooling require-

ments of the conditioned space, economizer cooling is in-
tegrated with mechanical cooling, providing, two stages of
cooling. Compressor and the condenser fan will be ener-
gized and the position of the economizer damper will be de-
termined by the supply-air temperature. When the second
stage of cooling is satisfied, the compressor and OFM will
be deenergized. The damper position will be determined by
the supply-air temperature. When the first stage of cooling is
satisfied, there is a 30-second delay before the evaporator
fan shuts off. The damper then moves to the fully closed po-
sition. When using a continuous fan, the damper moves to
the minimum position.

COOLING, UNITS WITH PARABLADE ECONOMIZER
− When the outdoor-air is above the enthalpy control setting
and the room thermostat calls for cooling, the compressor
contactor is energized to start the compressor and the out-
door (condenser) fan motor. The indoor (evaporator) fan mo-
tor is energized and the economizer damper moves to the
minimum position. After the room thermostat is satisfied, the
damper will spring return to the fully closed position.

When the outdoor-air is below the enthalpy control set-

ting and the thermostat calls for cooling, the economizer
outdoor-air damper is opened proportionally to maintain be-
tween 50 and 56 F at the mixed-air sensor. If outside air along
cannot satisfy the cooling requirements, economizer cooling
is integrated with mechanical cooling. When the room ther-
mostat is satisfied, the damper will spring return to the fully
closed position.
HEATING, UNITS WITH ECONOMIZER — When the ther-
mostat calls for heating, terminal W1 is energized. To pre-
vent thermostat short-cycling, the unit is locked into the Heating
mode for at least 1 minute when W1 is energized. The induced-
draft motor is energized and the burner ignition sequence
begins. The indoor (evaporator) fan motor (IFM) is ener-
gized 45 seconds after a flame is ignited and the damper moves
to the minimum position. On units equipped for two stages
of heat, when additional heat is needed, W2 energized
and the high-fire solenoid on the main gas valve (MGV) is
energized. When the thermostat is satisfied and W1 is de-
energized, the IFM stops after a 45-second time-off delay.
The economizer damper then moves to the fully closed po-
sition. When using continuous fan, the damper will remain
in the minimum position.

28

Содержание 48TJD Series

Страница 1: ...o pres sure greater than 1 2 psig it must be re placed before use When pressure testing field supplied gas piping at pressures of 1 2 psig or less a unit connected to such piping must be isolated by m...

Страница 2: ...e of 50 F dry bulb or an intermittent opera tion down to 45 F dry bulb such as when used with a night set back thermostat Step 3 Install External Trap for Condensate Drain The unit s 3 4 in condensate...

Страница 3: ...u the Bottom ROOF CURB ACCESSORY A UNIT SIZE 48TJ CRRFCURB001A00 18 29 356 004 007 CRRFCURB002A00 28 09 610 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in...

Страница 4: ...e in accordance with the CAN1 B149 1 and CAN1 B149 2 installation codes for gas burning appliances For natural gas applications gas pressure at unit gas con nection must not be less than 4 in wg or gr...

Страница 5: ...in the legend for Table 2 Note 2 to determine the percent of voltage imbalance Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical com...

Страница 6: ...ging to prevent rigging straps from damaging unit UNIT MAX WEIGHT A B C Lb Kg in mm in mm in mm 48TJE TJF004 510 231 73 69 1872 37 50 953 33 35 847 48TJD TJE TJF005 520 236 48TJD TJE TJF006 540 245 48...

Страница 7: ...600 2000 2400 Alt 1200 1600 2000 Maximum Continuous Bhp Std 34 75 1 20 2 40 Alt 1 00 1 00 1 80 Motor Frame Size Std 48 48 48 56 Alt 48 48 56 Nominal Rpm High Low Std 860 800 1075 970 1075 970 Alt Fan...

Страница 8: ...80 25 55 35 65 50 80 25 55 35 65 50 80 Manifold Pressure in wg Natural Gas 3 5 3 5 3 5 3 5 Liquid Propane 3 5 3 5 3 5 3 5 Gas Valve Quantity 1 1 1 1 Field Gas Connection Size in 1 2 1 2 1 2 1 2 HIGH...

Страница 9: ...jurisdiction may prevail a Between unit flue side and combustible surfaces 36 inches b Bottom of unit to combustible surfaces when not using curb 1 inch Bot tom of base rail to combustible surfaces wh...

Страница 10: ...E Follow all local codes SPACING OF SUPPORTS STEEL PIPE X DIMENSIONS feet NOMINAL DIAMETER in 1 2 6 3 4 or 1 8 11 4 or larger 10 Fig 8 Gas Piping Guide With Accessory Thru the Curb Service Connections...

Страница 11: ...A Adjustable Heat Anticipator TH Thermostat Heating CC Cooling Compensator Field Wiring TC Thermostat Cooling Factory Wiring NOTES 1 Connect Y2 when unit is equipped with an economizer 2 Connect W2 wh...

Страница 12: ...6 20 15 94 575 3 60 Std 518 632 7 9 58 0 0 6 2 6 30 14 4 15 12 76 IMPORTANT Optional alternate evaporator fan motor and drive are not available for 48TJ007 units Contact your local Carrier representat...

Страница 13: ...he 4 screws removed in Step 3 See Fig 15 6 Remove and save 6 screws 3 on each side from sides of the manual outdoor air damper 7 Align screw holes on hood with screw holes on side of manual outdoor ai...

Страница 14: ...g hood assembly See Fig 20 5 Insert economizer plug into economizer harness Re move tape from barometric relief damper See Fig 21 6 If ventilation air is not required proceed to Step 8 If ventilation...

Страница 15: ...fm Determine Setting 5 in Fig 22 Varislide Economizer Minimum Position Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 6...

Страница 16: ...ired perform the following a Make sure the factory installed jumper is in place across terminals P and P1 on the economizer logic module T and T1 should be disconnected during adjustment b The 2 poten...

Страница 17: ...y en gaged See Fig 28 8 Fasten hood top and side plate assembly Fig 29 to outdoor air opening panel with screws provided 9 Slide outdoor air inlet screen into screen track on hood side plate While hol...

Страница 18: ...n speed make sure the new fan speed will provide an air temperature rise range as shown in Table 1 To change fan speed 1 Shut off unit power supply 2 Loosen belt by loosening fan motor mounting nuts S...

Страница 19: ...10 1070 Approximate fan rpm shown Indicates alternate motor and drive package Indicates standard motor and drive package Table 4 Motor Data UNIT 48TJ EVAPORATOR FAN MOTOR MAXIMUM CONTINUOUS BHP MAXIMU...

Страница 20: ...487 1100 687 219 746 259 806 298 867 348 929 398 964 398 1013 487 1068 547 1200 733 259 785 318 843 348 903 408 960 467 994 497 1045 557 1090 637 1300 754 288 826 378 891 428 942 477 991 527 1047 597...

Страница 21: ...1072 950 1107 998 1700 791 515 873 599 907 678 941 757 1024 889 1064 976 1103 1063 1137 1128 1800 831 609 881 693 929 772 976 851 1057 991 1095 1078 1132 1165 1167 1239 1900 872 704 919 788 965 877 1...

Страница 22: ...70 869 1144 1032 1226 1216 1301 1492 1380 1757 1600 770 429 826 501 930 654 1015 797 1098 961 1173 1134 1242 1308 1318 1523 1392 1800 1700 811 511 864 582 964 736 1051 899 1124 1053 1203 1237 1270 142...

Страница 23: ...or and drive are required 3 Maximum usable watts input is 2120 Extensive motor and elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using you...

Страница 24: ...your fan motors up to the wattage ratings shown will not result in nuisance tripping or pre mature motor failure Unit warranty will not be affected For ad ditional information on motor performance re...

Страница 25: ...d elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using your fan motors up to the wattage ratings shown will not result in nuisance tripping...

Страница 26: ...ll other rpms require field supplied drive 7 To convert watts to bhp watts input x motor efficiency bhp 746 Motor efficiency 74 Table 18 Fan Performance 48TJD TJE TJF007 Horizontal Discharge Units Sta...

Страница 27: ...Natural Gas Orifice Size Liquid Propane Orifice Size Natural Gas Orifice Size Liquid Propane Orifice Size 0 2 000 33 45 30 38 2 000 34 46 30 39 3 000 35 47 31 40 4 000 36 47 32 41 5 000 36 47 33 42 6...

Страница 28: ...thermostat calls for cooling the economizer damper moves to the minimum position If the supply air tempera ture is above 57 F the damper continue to open until it reaches the fully open position or u...

Страница 29: ...top cover as shown in Fig 36 and 37 It is not necessary to remove the top cover 2 Remove 3 screws on right side of compressor access panel Remove one screw securing condenser coil top cover to compres...

Страница 30: ...harging charts are different from type normally used Charts are based on charg ing the units to the correct superheat for the various oper ating conditions Accurate pressure gage and temperature sensi...

Страница 31: ...Fig 40 Cooling Charging Chart 48TJ004 Fig 41 Cooling Charging Chart 48TJ005 Fig 42 Cooling Charging Chart 48TJ006 Fig 43 Cooling Charging Chart 48TJ007 31...

Страница 32: ...aporator Fan On Off Delay Modified 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced Draft Motor F...

Страница 33: ...Fig 45 Burner Tray Details Fig 46 Spark Adjustment LOW HEAT 48TJE004 48TJD005 007 74 000 BTUH INPUT MEDIUM AND HIGH HEAT 48TJE005 007 48TJF004 115 000 BTUH INPUT 48TJF005 007 150 000 BTUH INPUT 33...

Страница 34: ...trode spacing gaps etc Ensure that flame sense and ignition wires are prop erly terminated Verify that unit is obtaining proper amount of gas Induced draft motor fault LED 6 flashes IGC does not sense...

Страница 35: ...pressure at manifold Clock gas meter for input If too low increase manifold pressure or replace with correct orifices Unit undersized for application Replace with proper unit or add additional unit Re...

Страница 36: ...ace Restriction in refrigerant system Locate restriction and remove Compressor operates con tinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Therm...

Страница 37: ...l board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are function ing and wired properly and no 24 vac exists check wiring s...

Страница 38: ...ed If these actions do not occur replace module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to economizer 1 Disconnect power at TR and TR1 Disconne...

Страница 39: ...inal wire furnished must be replaced it must be replaced with type 90 C wire or its equivalent 2 Three phase motors are protected under primary single phasing conditions 3 Thermostat HH07AT170 172 174...

Страница 40: ...Fig 47 Typical Wiring Diagram and Component Arrangement 40...

Страница 41: ......

Страница 42: ...turer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 6a PC 111 Catalog No 534 852 Printed in U S A F...

Страница 43: ......

Страница 44: ...M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMPER...

Отзывы: