TO SHUT UNIT OFF

See Fig. 1 for location of gas valve(s). Refer to Fig. 3 while

proceeding with the following steps.
1. Turn off the unit demand for cooling or heating by using

the scrolling marquee. The scrolling marquee is located in
the control box at the compressor end of the unit.

 a. Push the 

 key until a blank display screen is

shown.

 b. Push the 

 key until the SERVICE TEST LED is lit.

 c. Push the 

 key. The display will show STOP.

 d. Push the 

 key again. The NO/YES display

will flash.

 e. Push  the 

 or 

 key to toggle the display to YES

and then push 

. The unit will be locked off

from heating, cooling or any operation. The controls

will still function and the display will still operate.

2. Close the field-installed manual gas shutoff valve.
3. Turn off the electrical power to the unit using the optional

disconnect or the field-installed disconnect and lock off

using proper lockout and tag-out procedures.

4. Open the burner section hinged access door.

5. Move the switch on the gas valves to the OFF position and

wait 5 minutes before doing any service in the section or
on the piping.

6. Close the burner section hinged access door.

7. If unit is being shut down because of a malfunction, call

your dealer as soon as possible.

If unit is being shut down because the heating season has

ended, restore electrical power to the unit and reset the
scrolling marquee to Run mode to ensure operation of the

cooling system during the cooling season.

Do not use this unit if any part has been under water. Immedi-

ately call a qualified service technician to inspect the unit and

to replace any part of the control system and gas control that

has been under water.

Fig. 3 — To Shut Unit Off

WARNING

1. Do not turn off the electrical power to unit without first

turning off the gas supply.

2. Never attempt to manually light the main burners on unit

with a match, lighter, or any other flame. If the electric

sparking device fails to light the main burners, refer to

the following shutdown procedures. Call your dealer as

soon as possible.

Failure to follow these procedures can result in serious fire

or personal injury.

ESCAPE

ENTER

ENTER

IMPORTANT: Should overheating occur or the gas supply

fail to shut off, shut off the manual gas valve to the unit before

shutting off the electrical supply.

ENTER

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

STEP 1

STEP 2

STEP 3

STEP 4

STEP 5

STEP 6

STEP 7

ON

MAIN

OFF

LOCK-OUT

TAG

ON

MAIN

OFF

Содержание 48P 030

Страница 1: ...diatement Appeler imm diatement le fournisseur de gaz en utilisant le t l phone d un voisin Suivre les instructions du fournisseur de gaz Si le fournisseur de gaz n est pas accessible appeler le servi...

Страница 2: ...gas valve to the unit before shutting off the electrical supply AVERTISSEMENT En cas de temp rature excessive ou s il est impossible de couper l alimentation en gaz fermer le robinet manuel d ali ment...

Страница 3: ...ection hinged access door 5 Move the switch on the gas valves to the OFF position and wait 5 minutes NOTE If this is the first installation of the unit the gas flue hoods must be installed before oper...

Страница 4: ...t units with a conven tional thermostat are set to heating control temperature On VAV variable air volume and constant volume units with a space temperature sensor make sure that the set points are at...

Страница 5: ...ecause of a malfunction call your dealer as soon as possible If unit is being shut down because the heating season has ended restore electrical power to the unit and reset the scrolling marquee to Run...

Страница 6: ...rication is not recommended Bearings will not require lu brication for at least 5 years of normal operation After 5 years motor life can be extended by having the motors serviced at an authorized moto...

Страница 7: ...in the burners firing out of normal time sequence This delayed ignition is characterized by an especially loud sound See Fig 1 and 4 and proceed as follows to inspect the combus tion area and power ve...

Страница 8: ...tions Repair or adjustment should be made at this time 14 Your servicing dealer may offer an economical service contract that covers seasonal inspections Ask for further details Complete Service Instr...

Отзывы: