background image

4

10. Using the scrolling marquee, enable the unit to run using

the following procedure:
 a. Push the 

 key until a blank display screen is

shown.

 b. Push the 

 key until the SERVICE TEST LED is lit.

 c. Push the 

 key. The display will show STOP.

 d. Push the 

 key again. The NO/YES display

will flash.

 e. Push the 

 or 

 key to toggle the display to NO and

then push 

. The unit will return to     normal

operation and exit SERVICE TEST mode.

11. To test the operation of the gas section, use the scrolling

marquee Service Test routine to energize the gas outputs

and to turn on the gas. Refer to the unit Controls, Start-Up,

Operation, Service and Troubleshooting literature for

more information.

12. For normal operation, make sure that units with a conven-

tional thermostat are set to heating control temperature.

On VAV (variable air volume) and constant volume units
with a space temperature sensor, make sure that the set

points are at the normal heat set points.

Fig. 2 — To Light Unit

ESCAPE

ENTER

ENTER

ENTER

WARNING

If the main burners fail to light or the blower fails to start, shut

down gas heating section and call your dealer for service. Fail-

ure to follow these requirements could result in serious per-

sonal injury.

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

LOCK-OUT

TAG

ON

MAIN

OFF

STEP 1

STEP 2

STEP 3

STEP 4

STEP 10

STEP 5

STEP 6

STEP 7

ON

MAIN

OFF

STEP 8

STEP 9

Содержание 48P 030

Страница 1: ...diatement Appeler imm diatement le fournisseur de gaz en utilisant le t l phone d un voisin Suivre les instructions du fournisseur de gaz Si le fournisseur de gaz n est pas accessible appeler le servi...

Страница 2: ...gas valve to the unit before shutting off the electrical supply AVERTISSEMENT En cas de temp rature excessive ou s il est impossible de couper l alimentation en gaz fermer le robinet manuel d ali ment...

Страница 3: ...ection hinged access door 5 Move the switch on the gas valves to the OFF position and wait 5 minutes NOTE If this is the first installation of the unit the gas flue hoods must be installed before oper...

Страница 4: ...t units with a conven tional thermostat are set to heating control temperature On VAV variable air volume and constant volume units with a space temperature sensor make sure that the set points are at...

Страница 5: ...ecause of a malfunction call your dealer as soon as possible If unit is being shut down because the heating season has ended restore electrical power to the unit and reset the scrolling marquee to Run...

Страница 6: ...rication is not recommended Bearings will not require lu brication for at least 5 years of normal operation After 5 years motor life can be extended by having the motors serviced at an authorized moto...

Страница 7: ...in the burners firing out of normal time sequence This delayed ignition is characterized by an especially loud sound See Fig 1 and 4 and proceed as follows to inspect the combus tion area and power ve...

Страница 8: ...tions Repair or adjustment should be made at this time 14 Your servicing dealer may offer an economical service contract that covers seasonal inspections Ask for further details Complete Service Instr...

Отзывы: