![Carrier 48HC D17 Series Скачать руководство пользователя страница 74](http://html1.mh-extra.com/html/carrier/48hc-d17-series/48hc-d17-series_service-and-maintenance-instructions_2561010074.webp)
74
APPENDIX III. FAN PERFORMANCE (cont.)
TABLE 31 – PULLEY ADJUSTMENT VERTICAL
MODEL
SIZE
MOTOR/DRIVE COMBO
MOTOR PULLEY TURNS OPEN
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
17
3 phase
Standard Static
680
663
647
630
614
597
580
564
547
531
514
Medium Static
863
845
826
808
789
771
753
734
716
697
679
High Static
1009
991
972
954
936
918
899
881
863
844
826
20
3 phase
Standard Static
822
802
782
762
742
722
702
682
662
642
622
Medium Static
879
862
846
829
813
796
779
763
746
730
713
High Static
1078
1058
1039
1019
1000
980
960
941
921
902
882
24
3 phase
Standard Static
863
846
828
811
794
777
759
742
725
707
690
Medium Static
1021
1002
984
965
947
928
909
891
872
854
835
High Static
1176
1153
1129
1106
1082
1059
1035
1012
988
965
941
28
3 phase
Standard Static
911
892
872
853
833
814
795
775
756
736
717
Medium Static
1116
1096
1075
1055
1035
1015
994
974
954
933
913
High Static
1176
1153
1129
1106
1082
1059
1035
1012
988
965
941
NOTE
: Do not adjust pulley further than 5 turns open.
--- Factory settings
TABLE 32 – PULLEY ADJUSTMENT HORIZONTAL
MODEL
SIZE
MOTOR/DRIVE COMBO
Motor Pulley turns open
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
17
3 phase
Standard Static
680
663
647
630
614
597
580
564
547
531
514
Medium Static
780
763
747
730
714
697
680
664
647
631
614
High Static
912
895
879
862
846
829
812
796
779
763
746
20
3 phase
Standard Static
822
802
782
762
742
722
702
682
662
642
622
Medium Static
879
862
846
829
813
796
779
763
746
730
713
High Static
1078
1058
1039
1019
1000
980
960
941
921
902
882
24
3 phase
Standard Static
863
846
828
811
794
777
759
742
725
707
690
Medium Static
1021
1002
984
965
947
928
909
891
872
854
835
High Static
1176
1153
1129
1106
1082
1059
1035
1012
988
965
941
28
3 phase
Standard Static
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Medium Static
923
906
889
873
856
839
822
805
789
772
755
High Static
1010
992
973
955
937
919
900
882
864
845
827
NOTE
: Do not adjust pulley further than 5 turns open.
--- Factory settings
48H
C
Содержание 48HC D17 Series
Страница 76: ...76 APPENDIX IV WIRING DIAGRAMS C12615 Fig 76 48HC D17 D28 Control Diagram 208 230 3060 460 575 3 60 48HC...
Страница 77: ...77 APPENDIX IV WIRING DIAGRAMS C12616 Fig 77 48HC D17 D28 Power Diagram 208 230 3 60 48HC...
Страница 78: ...78 APPENDIX IV WIRING DIAGRAMS C12617 Fig 78 48HC D17 D28 Power Diagram 460 3 60 48HC...
Страница 79: ...79 APPENDIX IV WIRING DIAGRAMS C12618 Fig 79 48HC D17 D28 Power Diagram 575 3 60 48HC...
Страница 80: ...80 APPENDIX IV WIRING DIAGRAMS C14061 Fig 80 48HC D17 D28 Control Diagram with Humidi MiZer 48HC...
Страница 81: ...81 APPENDIX IV WIRING DIAGRAMS C12620 Fig 81 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer 48HC...
Страница 82: ...82 APPENDIX IV WIRING DIAGRAMS C12621 Fig 82 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer 48HC...
Страница 83: ...83 APPENDIX IV WIRING DIAGRAMS C12622 Fig 83 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer 48HC...
Страница 85: ...85 APPENDIX IV WIRING DIAGRAMS C13766 Fig 85 PremierLinkt System Control Wiring Diagram with Humidi MiZer 48HC...
Страница 86: ...86 APPENDIX IV WIRING DIAGRAMS C13767 Fig 86 RTU OPEN Wiring Diagram 48HC...
Страница 87: ...87 APPENDIX IV WIRING DIAGRAMS C13768 Fig 87 RTU OPEN Wiring Diagram with Humidi MiZer 48HC...