*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Table 18 — Dry Bulb Operation with DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
Above CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
VENTMIN to
Full-Open
Closed to Full-Open
Table 19 — Enthalpy Operation without DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NO CO
2
SENSOR
NO
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
YES
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
0v/Off
0v/Off
MIN POS to Full Open
Closed to Full-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
MIN POS to Full Open
Closed to Full-Open
Содержание 48FC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont...
Страница 6: ...6 Fig 2 Unit Dimensional Drawing cont...
Страница 22: ...22 Fig 40 Typical Control Wiring Diagram Electro Mechanical with W7212 48FC 04 06 208 230 3 60 Unit Shown...
Страница 23: ...23 Fig 41 Typical Electro Mechanical with W7220 Control Wiring Diagram 48FC 07 208 230 3 60 Unit Shown...
Страница 24: ...24 T Fig 42 Typical 48FC 04 07 Power Wiring Diagram 208 230V Unit Shown...
Страница 45: ......