31

STATUS

(cont)

EXH2 OUT

OFF

ON/OFF

EXHAUST STAGE 2 RELAY OUTPUT

Output of AUX1 O terminal

Displays ON when damper position reaches programmed 

percentage set point.

ON = 24 vac output

OFF = No output

Displays only if AUX1 O = EXH2

ERV

OFF

ON/OFF

ENERGY RECOVERY VENTILATOR

Output of AUX1 O terminal; displays only if AUX1 O = ERV

ON = 24 vac output

OFF = No Output

MECH COOL ON

or

HEAT STAGES ON

0

0, 1, or 2

Displays stage of mechanical cooling that is active.

Displays the stage of heat pump heating that is active.

FAN SPEED

N/A

LOW or HIGH

SUPPLY FAN SPEED

Displays speed setting of fan on a 2-speed fan unit.

W (HEAT IN)

N/A

ON/OFF

HEAT DEMAND STATUS

Displays status of heat demand on a 2-speed fan unit.

SETPOINTS

MAT SET

53°F (12°C)

38°F to 70°F

(3°C to 21°C);

increment by 1 

degree

SUPPLY AIR SETPOINT

The economizer will modulate the OA damper to maintain the 

mixed air temperature at the set point

LOW T LOCK

32°F (0°C)

–45°F to 80°F

(–43°C to 27°C);

increment by 1 

degree

COMPRESSOR LOW TEMPERATURE LOCKOUT

Set point determines outdoor temperature when the mechanical 

cooling cannot be turned on. Commonly referred to as the 

Compressor lockout. At or below the set point, the Y1-O and Y2-

O will not be energized on the controller.

DRYBLB SET

63°F (17°C)

48°F to 80°F

(9°C to 27°C);

increment by 

1 degree

OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT

Dry bulb set point will only appear if using dry bulb changeover.

Set point determines where the economizer will assume outdoor 

air temperature is good for free cooling; e.g.; at 63°F unit will 

economize at 62°F and below and not economize at 64°F and 

above. There is a 2°F deadband.

ENTH CURVE

ES3

ES1,ES2,ES3,ES4, 

or ES5

ENTHALPY CHANGEOVER CURVE

ES curve will only appear if using enthalpy changeover.

Enthalpy boundary “curves” for economizing using single 

enthalpy. See page 38 for description of enthalpy curves.

DCV SET

1100ppm

500 to 2000 ppm; 

increment by 100

DEMAND CONTROLLED VENTILATION

Displays only if CO

2

 sensor is connected. Set point for Demand 

Controlled Ventilation of space. Above the set point, the OA 

dampers will modulate open to bring in additional OA to maintain 

a space ppm level below the set point.

MIN POS

2.8 V

2 to 10 vdc

VENTILATION MINIMUM POSITION

Displays ONLY if a CO

2

 sensor is NOT connected.

With 2-speed fan units, MIN POS L (low speed fan) and MIN 

POS H (high speed fan) settings are required. Default for MIN 

POS L is 3.2V and MIN POS H is 2.8V.

VENTMAX 2.8 

V

2 to 10 vdc

DCV MAXIMUM DAMPER POSITION

Displays only if a CO

2

 sensor is connected.

Used for Vbz (ventilation max cfm) set point. VENTMAX is the 

same setting as MIN POS would be if unit did not have CO

2

 

sensor.

100 to 9990 cfm; 

increment by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled 

by CFM and displays from 100 to 9990 CFM.

2 to 10 vdc

With 2-speed fan units, VENTMAX L (low speed fan) and 

VENTMAX H (high speed fan) settings are required. Default for 

VENTMAX L is 3.2V and VENTMAX H is 2.8V

VENTMIN 2.25 

V

2 to 10 vdc or 100 

to 9990 cfm 

increment by 10

DCV MINIMUM DAMPER POSITION

Displays only if a CO

sensor is connected. Used for Va 

(ventilation min cfm) set point. This is the ventilation for less than 

maximum occupancy of the space.

100 to 9990 cfm; 

increment by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled 

by CFM and displays from 100 to 9990 CFM.

2 to 10 vdc

With 2-speed fan units VENTMIN L (low speed fan) and 

VENTMIN H (high speed fan) settings are required. Default for 

VENTMIN L is 2.5V and VENTMIN H is 2.25V

ERV OAT SP

††

32°F (0°C)

0°F to 50°F

(–18°C to 10°C);

increment by 

1 degree

ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR 

TEMPERATURE SETPOINT

Only when AUX1 O = ERV

Table 11 — W7220 Menu Structure* (cont)

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

EXPANDED PARAMETER NAME

Notes

Содержание 48FC 04

Страница 1: ...troller Factory Option 40 SystemVu Controller Factory Option 40 Controller Options 40 LOW AMBIENT Smoke Detectors 40 Step 14 Adjust Factory Installed Options 41 SMOKE DETECTORS ECONOMI ER IV OCCUPANCY...

Страница 2: ...sult in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing air conditioning e...

Страница 3: ...Zer system2 Coil Options Outdoor Indoor Hail Guard A Al Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N...

Страница 4: ...4 Fig 2 Unit Dimensional Drawing...

Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont...

Страница 6: ...6 Fig 2 Unit Dimensional Drawing cont...

Страница 7: ...ll dictate different se quences for the steps of unit installation For example on curb mounted units some accessories must be installed on the unit before the unit is placed on the curb Review the fol...

Страница 8: ...NSULATED PANELS 25 4 1 THK POLYURETHANE FOAM 44 5 1 3 4 DENSITY 3 DIMENSIONS IN ARE IN MILLIMETERS 4 ROOFCURB 18 GAGE STEEL 5 ATTACH DUCTWORK TO CURB FLANGES OF DUCT REST ON CURB 6 SERVICE CLEARANCE 4...

Страница 9: ...is used on a vertical unit the return should be ducted through the roof deck to comply with applicable fire codes A minimum clearance is not required around ductwork Step 6 Rig and Place Unit Keep uni...

Страница 10: ...und duct openings must be tight Secure with screws as shown in Fig 8 Cover seams with foil duct tape Field supplied flanges should be attached to horizontal duct openings and all ductwork should be se...

Страница 11: ...to not damage any wiring or cut tie wraps securing any wiring Fig 10 Economizer and Two Position Damper Hood Parts Location 3 Carefully lift the hood assembly with metal tray through the filter access...

Страница 12: ...g must be accordance with local building codes and with applicable national codes In U S A re fer to NFPA 54 ANSI Z223 1 National Fuel Gas Code NFGC In Canada installation must be accordance with the...

Страница 13: ...s of connector lock nuts before connecting gas piping Install a 1 2 in NPT street elbow on the thru base gas fitting Attach a 1 2 in pipe nipple with minimum length of 16 in 406 mm field supplied to t...

Страница 14: ...s supply line observe local codes per taining to gas pipe installations Refer to the NFPA 54 ANSI Z223 1 NFGC latest edition in Canada CAN CSA B149 1 In the absence of local building codes adhere to t...

Страница 15: ...protect against freeze up If drain line is installed downstream from the exter nal trap pitch the line away from the unit at 1 in per 10 ft 25 mm per 3 m of run Do not use a pipe size smaller than the...

Страница 16: ...g 25 Connect field power supply conductors to LINE side terminals when the switch enclosure cover is removed to attach the handle Field Install the NFD Shaft and Handle 1 Remove the Control Box access...

Страница 17: ...pressure lugs on the power terminal block or at factory installed option non fused disconnect Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate...

Страница 18: ...screw heads is exposed Press the gasket over the screw heads 3 Slip the backing plate over the screw heads at the keyhole slots and align with the gasket tighten the two screws until snug do not over...

Страница 19: ...and conduit may be attached to the connectors on the base pan Pull correctly rated high voltage and low voltage through appropriate conduits Connect the power conduit to the internal disconnect if uni...

Страница 20: ...able for single phase 3 voltage code models The Humidi MiZer dehumidification system requires a field supplied and field installed space relative humidity control de vice This device may be a separate...

Страница 21: ...ilt into the corner post see Fig 35 to the 24 v barrier located on the left side of the control box The raceway provides the UL required clearance between high voltage and low voltage wiring 3 The The...

Страница 22: ...22 Fig 40 Typical Control Wiring Diagram Electro Mechanical with W7212 48FC 04 06 208 230 3 60 Unit Shown...

Страница 23: ...23 Fig 41 Typical Electro Mechanical with W7220 Control Wiring Diagram 48FC 07 208 230 3 60 Unit Shown...

Страница 24: ...24 T Fig 42 Typical 48FC 04 07 Power Wiring Diagram 208 230V Unit Shown...

Страница 25: ...mum position If the over temperature limit opens prior to the start of the indoor fan blower the IGC will shut down the burners and the control will shorten the 45 second delay to 5 seconds less than...

Страница 26: ...the user interface for the system The W7220 economizer module provides the basic inputs and outputs to provide simple economizer control When used with the optional sensors the economizer module provi...

Страница 27: ...Operating Temperature 40 F to 150 F 40 C to 65 C Exception of display operation down to 4 F 20 C with full recovery at 4 F 20 C from exposure to 40 F 40 C Storage Temperature 40 F to 150 F 40 C to 65...

Страница 28: ...d on the front of the economizer controller Keypad Use the four navigation buttons see Fig 50 to scroll through the menus and menu items select menu items and to change parameter and configuration set...

Страница 29: ...ays 2 Press the Enter button to return to the current menu parameter 3 Press the Menu Up Exit button to return to the previ ous menu Menu Structure Table 11 illustrates the complete hierarchy of menus...

Страница 30: ...and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F or _ _ _ C 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP...

Страница 31: ...alpy curves DCV SET 1100ppm 500 to 2000 ppm increment by 100 DEMAND CONTROLLED VENTILATION Displays only if CO2 sensor is connected Set point for Demand Controlled Ventilation of space Above the set p...

Страница 32: ...out for second exhaust fan SYS use output as an alarm signal OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL When using a setback thermostat with occupancy out 24 vac the 24 vac is input I...

Страница 33: ...e fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1 O N A N A Energizes the AUX output If Aux setting is NONE no action...

Страница 34: ...ion with a 2 speed indoor fan with or without DCV see Tables 17 and 18 For enthalpy operation with a 2 speed indoor fan with or without DCV see Tables 19 and 20 ALARMS CONT FREEZE ALARM N A N A Check...

Страница 35: ...NTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On...

Страница 36: ...UPIED UNOCCUPIED Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v On 24 v On VENTMIN Closed Yes Off Off High 0 v Off 0 v Off VENT...

Страница 37: ...Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No OFF OFF LOW 0v Off 0v Off VENTMIN Closed ON OFF LOW 24v On 0v Off VENTMIN Closed ON ON HIGH 24v On 24v On VENTMIN Closed Yes OFF OFF LOW...

Страница 38: ...s to determine the speed of the supply fan and controls the OA damper to the required posi tion see Table 21 The W heating mode is not controlled by the W7220 but it re quires the status to know where...

Страница 39: ...he item RUN appears 3 Press the Enter button to start the test The unit pauses and then displays IN PROGRESS When the test is complete DONE appears 4 When all desired parameters have been tested press...

Страница 40: ...e as factory installed options on 48FC models Smoke detectors may be specified for supply air only for return air without or with economizer or in combina tion of supply air and return air Return air...

Страница 41: ...Unoccupied sequence at terminals marked OCCUPANCY Detach the jumper covering the Occupancy terminals on the UCB and then attach the required connections Step 15 Install Accessories Available accessor...

Страница 42: ...t age cover in the Control Box 3 Connect a multimeter to the Vdc terminals on the UCB 4 Set the Range Switch to either A B or C per the Switch Range table 5 Using a straight blade screwdriver turn the...

Страница 43: ...NDOOR FAN and then press ENTER 8 Refer to the job specifications to set the following deter mining the values per the RPM Calculator label see Fig 59 Use the UP and DOWN arrow keys and the BACK key to...

Страница 44: ...12 1601 1692 1784 1878 1973 2069 2166 1500 1625 1750 1875 2000 2125 2250 2375 65 0 4 1609 1688 1768 1850 1933 2018 2104 2192 2282 65 0 6 1764 1839 1916 1994 2073 2153 2235 2317 0 8 1902 1974 2047 2123...

Страница 45: ......

Страница 46: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480245 01 Printed in U S A Form 48FC 4 7 02SI Pg 46 2 19 Replaces 48FC 4...

Страница 47: ..._ Verify gas pressure to unit gas valve is within specified range Y N _____ Check gas piping for leaks Y N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air i...

Страница 48: ...SIG B Discharge pressure _______________ PSIG C Entering air temperature _______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compresso...