Since the interconnection pipes are created on site, it is essential to clean and

evacuate the pipes and the indoor and outdoor units.

NOTE

Cleaning must be performed by circulating
nitrogen through the pipes of the system.
Cleanliness is extremely important because
it prevents dirt resulting from the installation
from getting inside the pipes and causing
problems later.

The access points are the service
valves on the outdoor unit.
The valves leave the factory in the closed position
to keep the refrigerant in the outdoor unit.
To perform the evacuation, keep the valve in
the closed position and connect the manifold
hose to the valve and the other end to the
vacuum pump.
It is recommended to proceed with the
evacuation of the two connections of the
service valves simultaneously.
The range to be reached must be located
between 250 and 500 microns.

ATTENTION !!!

Never load liquid into the suction service
valve. When you want to do this, use a
service valve for the expansion pipe.

IMPORTANT !!!

5.3

Adjusting the Gas Load

To adjust the refrigerant load in the machines, superheat can also be used as a

perimeter. (Consider a range of 5 to 7

o

C)

SUPERHEAT

1.

Definition:
Difference between the suction
temperature (Ts) and the saturated
evaporation temperature (Tes).
SA = Ts - Tes

2.

Measuring equipment required:
• Manifold.
• Bulb thermometer or electronic thermometer

(with temperature sensor).

• Insulation tape or foam.
• Pressure - Temperature conversion

table for R-22.

3.

Measuring steps:

1

o

- Bring the bulb or sensor of the thermometer

into contact with the suction pipe 15cm
from the intake of the condenser. The
surface must be clean and the measurement
is  performed  on the upper part of the
pipe to prevent incorrect readings.
Cover the bulb or sensor with foam to
insulate it from the ambient temperature.

2

o

- Install the manifold on the suction

pipe (low pressure gauge).

3

o

- Once the operating conditions have

become stabilized, read the gauge
pressure of the suction pipe. Obtain
the saturated evaporator temperature
(Tes) by consulting the R-22 table.

NOTE

4

o

- Read the suction temperature (Ts)

shown on the thermometer. Take  several
readings and calculate their average,
which will be the adopted temperature.

5

o

- Subtract the saturated evaporation

temperature (Tes) from the suction
temperature. The difference represents
the superheat.

6

o

- If the superheat is between 5 & 7

o

C, the

refrigerant load is correct. If it is below this
range, too much refrigerant is being injected
into the evaporator, and it is necessary
to remove refrigerant from the system.
If the superheat is high, too little refrigerant
is being injected into the evaporator, and
it is necessary to increase the refrigerant
in the system.

4.

Calculation example:

- Suction pipe pressure (pressure gauge)..75 psig
- Saturated evaporation temperature (table)..7

o

C

- Suction pipe temperature (thermometer)..13

o

C

- Superheat (subtraction)..........................6

o

C

- Superheat OK - correct load

Before starting to operate the equipment,
after adding the additional refrigerant load (if
necessary), open the service valves on the
outdoor unit.

ATTENTION !!!

Do not forget to purge the air from the
hose.

After creating the vacuum, add
positive pressure with R-22 so that
the vacuum is broken.

To proceed with loading the refrigerant, simply
keep the service valve in the factory position
(closed) and connect the manifold hose to
the valve (Schrader valve) of the service valve.

Содержание 42XQ Series

Страница 1: ...AND START UP INSTRUCTIONS UNDERCEILING CONSOLE FAN COIL UNIT 42XQ XQA 50 60Hz Carrier International Sdn Bhd Malaysia 42XQ 42XQA MODEL W mm D mm H mm Weight kg 42XQ XQA 020 004 23 42XQ XQA 025 006 102...

Страница 2: ...2 Electrical Box 42XQ 16 7 3 Changing the Wireless Remote Control to a Wired Remote Control 17 7 4 Electrical Diagram for Indoor Unit 220 240V output signal to compressor 20 7 5 Electrical Diagram for...

Страница 3: ...extinguisher periodically to verify that it is completely full and work perfectly Whenever working on the equipment always pay attention to all safety notices written on the labels attached to the uni...

Страница 4: ...being exposed to possible work accidents and arrange for their immediate transfer to the place of installation or another safe location When unpacking the units and removing the protective expanded p...

Страница 5: ...ded particulate matter which could possibly obstruct the vanes of the outdoor unit It is essential for the indoor unit to posses a hydraulic line to drain off the condensate This hydraulic line must h...

Страница 6: ...sewerage systems etc b Install the unit where it is free of any kind of obstruction of the air circulation both in the air intake and the air discharge c Select a location with sufficient space to per...

Страница 7: ...4 3 2 PLACEMENT AT THE LOCATION NOTE To fix the indoor unit in place it is necessary to remove its side covers as described in subsection 4 3 3 d Fig 8 indicates the position of the supports Install t...

Страница 8: ...s the left side gives access to the electrical box and the electrical connections 4 3 3 REMOVING THE SIDES 1 2 Fig 10 shows the position of the screws to be removed to disassemble the grilles which gi...

Страница 9: ...llations on the wall and ceiling and where these pipes must be routed as well as where it is necessary to break the indentation in the right hand side cover of the indoor unit 4 3 5 DRAINING OF THE CO...

Страница 10: ...l with a slight inclination towards the drainage side approximately 2o Fig 14 b The unit uses gravity drainage However the drainage pipe must have a downward slope Avoid the situation shown in Fig 15...

Страница 11: ...olding charge For more information regarding the additional gas load refer to the table below IMPORTANT Note Model code for Thailand market only Outdoor unit connection for reference only refer to spe...

Страница 12: ...condenser The surfacemustbecleanandthemeasurement is performed on the upper part of the pipe to prevent incorrect readings Cover the bulb or sensor with foam to insulate it from the ambient temperatur...

Страница 13: ...indicated for the pipes giving consideration to the fact that it is the result of adding the equivalent distances of the pipe curves in a straight line 5 5 Interconnection Junctions The equivalent len...

Страница 14: ...st or humidity entering the pipe until it is used Take care to place refrigeration oil on the surfaces in contact between the flanged end and the joint before connecting them together This is done to...

Страница 15: ...to the adjacent illustration 6 EXPANSION SYSTEM This system with a piston according to Fig 22 contains a small part with a fixed calibrated orifice which is easily removed on the inside of a nipple fo...

Страница 16: ...ith local codes For the cable gauge values of the main power supply presented in the tables the use of copper and or aluminium cables was considered with insulation of the PVC 70o C type and conductor...

Страница 17: ...to use the indoor unit from the wireless remote control to the wired remote control the following steps must be followed according to the illustrations on the following pages Disconnect the intermedia...

Страница 18: ...18 Fig 25 Changing the remote control use option external connections...

Страница 19: ...emote control to connect the threeway cable The terminals are located in the rear part of the cover Insert the cables in the terminals according to the correspondence of the colors Reattach the cover...

Страница 20: ...20 Electrical interconnection in the Terminal Plate of the Indoor Unit 42XQ 7 4 Electrical Diagram for Indoor Unit 220 240V output signal to compressor Fig 26 Fig 27...

Страница 21: ...21 Electrical interconnection in the Terminal Plate of the Indoor Unit 42XQ 7 5 Electrical Diagram for Indoor Unit 24V output signal to compressor Fig 28 Fig 29...

Страница 22: ...22 7 6 Electrical Diagram and Cold Cycle Interconnection Diagram 50Hz Cooling only ELECTRICAL INTERCONNECTION 42XQ XQA 020 025 42XQ XQA 030 42XQ XQA 040 050 060...

Страница 23: ...er with respect for the steps described from Section 8 3 onwards 8 CONFIGURING THE SYSTEM 8 1 Changing the Configuration of the Unit from Underceiling to Console The indoor units leave the factory con...

Страница 24: ...ss the button to exit the configuration menu To see other available configuration options consult the table 8 3 Configuring the Unit Remote address of indoor unit A Remote address of indoor unit B Def...

Страница 25: ...A remote unit A Remote address of indoor unit A b remote unit B Remote address of indoor unit B Ab remote units A and B Default address of the two units tU C degree Celsius Temperature F degree Fahre...

Страница 26: ...tem Value Description 20 1 Heatpump Configuration of the unit 0 Only A C Use as default Heat Cool 21 1 199 in increments of 1 CNN address of the unit Use as default 1 22 0 199 in increments of 1 Zone...

Страница 27: ...d temperature setpoint is automatically readjusted to the default startup values of 22o C for C mode and 72o F for F mode whenever this configuration item is modified Item Value Description 10 H Remot...

Страница 28: ...ed the last value displayed is the new deflector setting for the system The only way to abort a deflector change is to change the value back to its original value ATTENTION NOTE Selecting DEFLECTOR mo...

Страница 29: ...tion item CH remote address and the temperature digits show the default value of the respective configuration item Ab control of both indoor units Press the buttons or to change the default value Ab t...

Страница 30: ...ion If the sensor temperature of the indoor unit coil does not fluctuate within the range 2o C during the compressor cycle period of 5 minutes the control triggers this error 10 EEPROM error in circui...

Страница 31: ...the electrical connections are securely connected Check that there are no leaks of refrigerant Confirm that the force discharge is compatible with the electrical specifications of the unit Ensure that...

Страница 32: ...TO OUTDOOR COMPRESSOR Carrier International Sdn Bhd 3385 T Lot 4 Jalan P 6 43650 Bandar Baru Bangi Selangor Malaysia Tel 03 8925 8001 Fax 03 8925 3578 REV 2 42XQ 06 2006 Parent Pt No 42XQ 402 001 IOM...

Отзывы: