APPENDIX

W

ork instructions

The existing R22 and R410A

 piping can be reused for 

inverter R32 product installations.

 

 

W

ARNING

Con

fi

rming the existence of scratches or dents on

the existing pipes and con

fi

rming the reliability of

the pipe strength are conventionally referred to the

local site.

If the speci

fi

ed conditions can be cleared, it is

possible to update existing R22 and R410A

 pipes

to those for R32 models.

Basic conditions needed to reuse existing

pipes

Check and observe the presence of three conditions in

the refrigerant piping works.

1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

T

ight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should

not be reused as they are. Clean the existing pipes

or exchange them with new pipes.

1. 

When a scratch or dent is heavy

, be sure to use new 

pipes for the refrigerant piping works.

2. 

When the existing pipe thickness is thinner than the 

speci

fi

ed “Pipe diameter and thickness,” be sure to 

use new pipes for the refrigerant piping works.

 

y

The operating pressure of R32 is high (1.6 times 

that of R22). If there is a scratch or dent on the pipe 

or a thinner pipe is used, the pressure strength may 

be inadequate, which may cause the pipe to break 

in the worst case.

Pipe diameter and thickness (mm)

Pipe outer diameter

Ø6.4

Ø9.5

Ø12.7

Thickness

R32, R410A

0.8

0.8

0.8

R22

3. 

When the outdoor unit was left with the pipes 

disconnected, or the gas leaked from the pipes and 

the pipes were not repaired and re

fi

lled.

 

y

There is the possibility of rain water or air

, including 

moisture, entering the pipe.

4. 

When refrigerant cannot be recovered using a 

refrigerant recovery unit.

 

y

There is the possibility that a large quantity of dirty 

oil or moisture remains inside the pipes.

5. 

When a commercially available dryer is attached to the 

existing pipes.

 

y

There is the possibility that copper green rust has 

been generated.

6. 

When the existing air conditioner is removed after 

refrigerant has been recovered.

 

Check if the oil is judged to be clearly dif

ferent from 

normal oil.

 

y

The refrigerator oil is copper rust green in color:

 

There is the possibility that moisture has mixed with 

the oil and rust has been generated inside the pipe.

 

y

There is discolored oil, a large quantity of residue, 

or a bad smell.

 

y

A

 large quantity of shiny metal dust or other wear 

residue can be seen in the refrigerant oil.

7. 

When the air conditioner has a history of the 

compressor failing and being replaced.

 

y

When discolored oil, a large quantity of residue, 

shiny metal dust, or other wear residue or mixture of 

foreign matter is observed, trouble will occur

.

8. 

When temporary installation and removal of the air 

conditioner are repeated such as when leased etc.

9. 

If the type of refrigerator oil of the existing air 

conditioner is other than the following oil (Mineral oil), 

Suniso, Freol-S, MS (Synthetic oil), alkyl benzene 

(HAB, Barrel-freeze), ester series, PVE only of ether 

series.

 

y

The winding-insulation of the compressor may 

deteriorate.

NOTE

The above descriptions are results have been con

fi

rmed 

by our company and represent our views on our air 

conditioners, but do not guarantee the use of the existing 

pipes of air conditioners that have adopted R32 in other 

companies.

Curing of pipes

When removing and opening the indoor or outdoor unit for

 

a long time, cure the pipes as follows:

 

y

Otherwise rust may be generated when moisture or 

foreign matter due to condensation enters the pipes.

 

y

The rust cannot be removed by cleaning, and new 

pipes are necessary

.

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

 

y

After the existing air conditioner is operated in cooling 

mode for approx. 30 minutes or longer

,* recover the 

refrigerant.

 

y

For cleaning the pipes and recovering oil

 

y

Refrigerant recovery: Pump down method

 

y

Remove the existing air conditioner from the piping 

and carry out 

fl

ushing (nitrogen pressure 0.5 MPa) to 

remove any remains inside of the pipe.

Note:

 

In case of twin pipes, also be sure to 

fl

ush the 

branching pipe.

Connect the indoor / outdoor units to the existing pipe.

 

y

Use a 

fl

are nut attached to the main unit for the indoor 

/ outdoor units. (Do not use the 

fl

are nut of the existing 

pipe.)

 

y

Re-machine the 

fl

are machining size to size for R32.

 

y

(Airtight test), V

acuum dry

, Refrigerant charge, Gas 

leak check

Test run

W

as largely discolored oil or a large quantity 

of remains discharged? (When the oil deteriorates, 

the color of the oil changes to a muddy 

or black color

.)

Existing pipes: Cannot be used.

 

y

Use new pipes.

Clean the pipes or use new pipes.

Piping necessary to change the 

fl

are nut / machining 

size due to pipe compression

1) Flare nut width: H

H

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

17

22

26

For R22

Same as above

24

2) Flare machining size: 

A

A

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

9.1

13.2

16.6

For R22

9.0

13.0

16.2

Becomes a little larger for R32

Do not apply refrigerator oil to the 

fl

are surface.

(If there is discharge of remains, it is judged that a 

large quantity of remains are present.)

YES

YES

NO

NO

NO

YES

Nitrogen gas pressure 0.5 MPa

01_1124950113_EN.indd   15

01_1124950113_EN.indd   15

23/11/2563 BE   18:36

23/11/2563 BE   18:36

Содержание 42TVBA018

Страница 1: ...nit 42TVBA018 024 Outdoor unit 38TVBA018 024 1124950113 R32 ENGLISH AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 00_1124950113_Cover indd 1 00_1124950113_Cover indd 1 23 11 2563 BE 17 39 23 11 2563...

Страница 2: ...ct Remote Controller for Wire Operation 7 Piping and Drain Hose Installation 8 Indoor Unit Fixing 9 Drainage 10 OUTDOOR UNIT 10 Installation Place 10 Refrigerant Piping Connection 10 Evacuating 11 ELE...

Страница 3: ...uire admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use sh...

Страница 4: ...WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION T...

Страница 5: ...esult in explosion and injury Thickness of copper pipes used R32 must be more than 0 8 mm Never use copper pipes thinner than 0 8 mm Do not perform flare connection inside a building or dwelling or ro...

Страница 6: ...ld result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakag...

Страница 7: ...commend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use th...

Страница 8: ...e control Saddle Extension drain hose Not available provided by installer The provided Remote Controller is a wireless type which also can be used as a wire Please see How to Connect The Remote Contro...

Страница 9: ...no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installe...

Страница 10: ...wire Notch for wire out Control wire Terminal Display unit Screw Front panel Wire size 28 22AWG or 0 08 0 32 mm2 Outer diameter not over 4 7 mm control wire length 30 m or less Remark 1 Recommend to...

Страница 11: ...cribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tight...

Страница 12: ...ilding secure the normal fan operation using a duct or a windshield 3 In particularly windy areas install the unit such as to avoid admission of wind 4 Installation in the following places may result...

Страница 13: ...y the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 20 meters 15 minutes for 20 met...

Страница 14: ...air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Co...

Страница 15: ...use some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A s...

Страница 16: ...rved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are d...

Страница 17: ...ge quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated...

Страница 18: ...1 1 2 1 2 H07RN F 60245 IEC66 3 R32 02_1124950113_TH indd 1 02_1124950113_TH indd 1 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 19: ...TH 2 2 R32 02_1124950113_TH indd 2 02_1124950113_TH indd 2 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 20: ...3 R32 R32 R22 R32 0 8 0 8 Amin m2 Amin m2 Amin M 2 5 x 0 22759 x h0 2 M kg h0 m 0 6 1 8 1 0 2 2 2 5 02_1124950113_TH indd 3 02_1124950113_TH indd 3 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 21: ...TH 4 R32 GWP 1 675 R32 ref AR4 1 GWP F gas regulation 517 2014 02_1124950113_TH indd 4 02_1124950113_TH indd 4 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 22: ...5 1 1 2 1 3 2 4 1 5 Ultra pure 2 6 6 7 2 8 1 9 1 2 1 1 2 1 2 3 4 3 6 1 2 3 4 3 2 P N RB A623DA 02_1124950113_TH indd 5 02_1124950113_TH indd 5 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 23: ...1 5 3 7 7 4 2 A 6 35 12 70 B 8 1 C 8 10 50 300 170 600 100 100 600 600 SPACER 8 125 108 28 320 340 600 90 86 102 2 5 02_1124950113_TH indd 6 02_1124950113_TH indd 6 24 11 2563 BE 16 46 24 11 2563 BE 1...

Страница 24: ...nter of pipe hole 35 120 180 240 65 23 6 1 50 40 170 132 23 6 5 300 85 2 5 1 5 4 45 0 6 RF 1 2 3 5 6 4 6 6 15 5 4 x 25R 1 2 1 3 2 4 3 0 12 0 01 5 3 6 1 2 02_1124950113_TH indd 7 02_1124950113_TH indd...

Страница 25: ...3 1 25L 9 9 3 1 25L 0 15 0 02 10 A B A B 28 22AWG 0 08 0 32 2 4 7 30 4 5 6 7 30 10 1 2 1 1 3 70 5 1 3 2 28 22AWG 0 08 0 32 2 4 7 30 8 9 0 15 0 02 3 1 16L 3 1 25L A B 02_1124950113_TH indd 8 02_112495...

Страница 26: ...9 1 1 4 2 43 43 30 80 520 420 43 R 30 2 2 1 2 3 4 1 2 02_1124950113_TH indd 9 02_1124950113_TH indd 9 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 27: ...1 060 38TVBA018 38TVBA024 12 12 1 2 A 90 RIDGID R32 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1 0 1 5 12 70 0 0 5 1 0 1 5 0 8 IMPERIAL R32 6 35 1 5 2 0 9 52 1 5 2 0 12 70 2 0 2 5 0 8 A 1 2 3 4 10 02_1124950113_T...

Страница 28: ...6 R32 1 2 3 4 15 20 15 20 27 101 76 5 6 7 8 Hight Low 101 76 6 1 2 3 4 5 6 12 70 A 4 15 88 A 5 H H17 H19 14 18 1 4 1 8 H22 H30 33 42 3 3 4 2 H14 8 12 0 8 1 2 H17 14 18 1 4 1 8 A H 02_1124950113_TH in...

Страница 29: ...2 0 12 7 8 42TVBA018 42TVBA024 50Hz 220 V 1 9 05A 10 20A 11 5A 15A H07RN F 60245 IEC66 1 5 2 H07RN F 60245 IEC66 0 75 2 1 2 3 4 5 6 02_1124950113_TH indd 12 02_1124950113_TH indd 12 24 11 2563 BE 16...

Страница 30: ...13 1 2 3 1 2 3 3 50 10 70 10 1 2 3 4 5 6 7 8 9 3 02_1124950113_TH indd 13 02_1124950113_TH indd 13 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Страница 31: ...CHECK 00 1 4 MODE CHECK B 00 B 2 1 A 2 A A 3 A 1 2 B A A B TEST RUN COOL RESET 10 OPERATION RESET OPERATION 3 3 5 5 OPERATION 3 3 ON 02_1124950113_TH indd 14 02_1124950113_TH indd 14 24 11 2563 BE 16...

Страница 32: ...8 R22 3 4 5 6 7 8 9 Freol S MS HAB Barrel Freeze PVE R32 1 1 30 0 5 MPa R32 1 H H 6 4 9 5 12 7 R32 R410A 17 22 26 R22 24 2 A A 6 4 9 5 12 7 R32 R410A 9 1 13 2 16 6 R22 9 0 13 0 16 2 R32 0 5 MPa 02_11...

Страница 33: ...MEMO 00_1124950113_Cover indd 3 00_1124950113_Cover indd 3 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Страница 34: ...MEMO 00_1124950113_Cover indd 4 00_1124950113_Cover indd 4 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Страница 35: ...00_1124950113_Cover indd 5 00_1124950113_Cover indd 5 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Страница 36: ...1124950113 00_1124950113_Cover indd 6 00_1124950113_Cover indd 6 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Отзывы: