GB - 13
42PHQ ...P
E N G L I S H
Operating test and address selector
NOTE:
• Indoor fan speed will be "HIGH" in Test operation.
• The swing motor will operate when the indoor fan is operated.
• Operate the unit in accordance with the Owner's Manual and
check the following:
a. Indoor unit.
- Do all switches operate normally?
- Does each light come on normally?
- Do the horizontal louvres operate normally?
- Is the drain correct?
b. Outdoor unit.
- Is there any abnormal noise or vibration during operation?
- Is there any gas leakage?
Address selector
If you are installing two indoor units in the same room, it is
necessary for you to assign each unit its own address so each can
be operated by its own remote controller.
One address selector is in the PCB side and the other is
configured by remote controller.
The address selector is set to A when yoy purchase the unit.
• Indoor unit
- Turn off the unit and pull out the power plug.
- Remove the front panel and terminal block cover.
- Assign the address selector of one indoor unit to B.
Configuration (of the remote controller)
• Press the
and
buttons of the infrared remote controller and
hold them pressed for more than 5 seconds.
• The display will be cleared, the temperature segments will
display the first configuration item (CH = remote address) and
the time segments will display the default value of this
configuration item (A = control of both indoor units).
• Press either the
or
button to change the default value (A)
to the new value (b).
• Press
button repeatedly until “tU” is displayed.
• Press either the
or
button to change the default value of
temperatures in Degrees Celsius (C) to the new value Degrees
Fahrenheit (
o
F).
• Press
button repeatedly until “rc” is displayed.
• Press either the
or
button to change the default value of
Heat pump in model type (HP) to new value cooling only Export
(CO1) or cooling only korean (CO2).
• Press
button repeatedly until “CL” is displayed.
• Press either the
or
button to change the default value of
time format as AM/PM (12) to the new value of 24 hours time
format (24).
• LOOK OUT! Whichever configuration value changed must be
confirmed pressing
button each time.
• Press
button to leave the configuration menu.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote controller will automatically exit the
configuration menu and the procedure has to be restarted.
Operating test
This procedure is used to check the operation after unit installation.
• Press the EMER. button continuously for 5~10 seconds.
The unit will now be in Test Mode.
• Press the EMER. button once more after checking, to activate
the remote control. If there is any input signal (remote control
signal or EMER. button press) during test operation, the TEST
mode will change to the input signal mode.
• The setting conditions of the test operation are as follows:
1) Mono type
- Operating mode: COOL
- Fan speed: HIGH
- Timer mode: Disabled
- Discharge air direction: SWING
2) Multi or T-kit type
- Operation LED: ON
- Timer LED : Blink ON for 0.5 seconds and OFF for 0.5 seconds
four (for T-kit model) and three times(for multi model)
- Operation mode :
Cool mode for 3 minutes, firstly and then Heat mode for
2 minutes and Cool mode until test mode is existed
- Fan speed: HIGH
- Timer mode: Disabled
- Discharge air direction: SWING
EMER.
Adress switch
Jumper cap
018, 024
007, 009, 012, 014
AB
A
B