GB - 13

42PHQ ...P 

E N G L I S H

Operating test and address selector

NOTE:

• Indoor fan speed will be "HIGH" in Test operation.

• The swing motor will operate when the indoor fan is operated.

• Operate the unit in accordance with the Owner's Manual and

check the following:

a. Indoor unit.

- Do all switches operate normally?
- Does each light come on normally?
- Do the horizontal louvres operate normally?
- Is the drain correct?

b. Outdoor unit.

- Is there any abnormal noise or vibration during operation?
- Is there any gas leakage?

Address selector

If you are installing two indoor units in the same room, it is
necessary for you to assign each unit its own address so each can
be operated by its own remote controller.
One address selector is in the PCB side and the other is
configured by remote controller.
The address selector is set to A when yoy purchase the unit.

• Indoor unit

- Turn off the unit and pull out the power plug.
- Remove the front panel and terminal block cover.
- Assign the address selector of one indoor unit to B.

Configuration (of the remote controller)

• Press the 

 and 

 buttons of the infrared remote controller and

hold them pressed for more than 5 seconds.

• The display will be cleared, the temperature segments will

display the first configuration item (CH = remote address) and
the time segments will display the default value of this
configuration item (A = control of both indoor units).

• Press either the 

 or 

 button to change the default value (A)

to the new value (b).

• Press 

 button repeatedly until “tU” is displayed.

• Press either the 

 or 

 button to change the default value of

temperatures in Degrees Celsius (C) to the new value Degrees
Fahrenheit (

o

F).

• Press 

 button repeatedly until “rc” is displayed.

• Press either the 

 or 

 button to change the default value of

Heat pump in model type (HP) to new value cooling only Export
(CO1) or cooling only korean (CO2).

• Press 

 button repeatedly until “CL” is displayed.

• Press either the 

 or 

 button to change the default value of

time format as AM/PM (12) to the new value of 24 hours time
format (24).

• LOOK OUT! Whichever configuration value changed must be

confirmed pressing 

 button each time.

• Press 

 button to leave the configuration menu.

Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote controller will automatically exit the
configuration menu and the procedure has to be restarted.

Operating test

This procedure is used to check the operation after unit installation.

• Press the EMER. button continuously for 5~10 seconds.

The unit will now be in Test Mode.

• Press the EMER. button once more after checking, to activate

the remote control. If there is any input signal (remote control
signal or EMER. button press) during test operation, the TEST
mode will change to the input signal mode.

• The setting conditions of the test operation are as follows:

1) Mono type

- Operating mode: COOL
- Fan speed: HIGH
- Timer mode: Disabled
- Discharge air direction: SWING

2) Multi or T-kit type

- Operation LED: ON
- Timer LED : Blink ON for 0.5 seconds and OFF for 0.5 seconds

 four (for T-kit model) and three times(for multi model)

- Operation mode :

 Cool mode for 3 minutes, firstly and then Heat mode for

  2 minutes and Cool mode until test mode is existed
- Fan speed: HIGH
- Timer mode: Disabled
- Discharge air direction: SWING

EMER.

Adress switch

Jumper cap

018, 024

007, 009, 012, 014

AB

A

B

Содержание 42PHQ Series

Страница 1: ...42PHQ P INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Страница 2: ...ions and weight 2 Nominal data 2 Operating limits 2 Minimum clearances 3 Material supplied 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 Check 9 Electrical connec...

Страница 3: ...nal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit installation instructions Mod 007 009 012 014 018 024 A...

Страница 4: ...ld supplied items are required to complete the installation Name Specification 007 009 Connection pipe 3 8 9 52 mm Gas 1 4 6 35 mm Liquid 012 014 018 024 1 2 12 70 mm Gas 1 4 6 35 mm Liquid Wall sleev...

Страница 5: ...onsisting of two units manufactured by Carrier Consult the factory or a qualified system engineer prior to connecting this unit to any other manufacturer s outdoor unit Coupling units which have diffe...

Страница 6: ...ondensate dripping Flattening or kinking the refrigerant pipes or condensate pipes Excessive height difference between outdoor and indoor units see installation manual of outdoor unit Unnecessary turn...

Страница 7: ...he bracket and the wall Check that the wall hanging bracket does not move This can cause noise during operation If the unit is removed from the wall hanging bracket after installing it onto the wall r...

Страница 8: ...e the unit using a tool such as a screwdriver set between the middle area of the body and bottom right of the wall hanging bracket Connecting the pipe can be done more easily if the unit is inclined F...

Страница 9: ...to ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used Fla...

Страница 10: ...screws After installation if there is a significant gap between the unit and wall it can be adjusted by securing the body to the wall hanging bracket using 2 screws Screw holes can be only seen after...

Страница 11: ...009 012 014 to the indoor unit sizes 018 024 to the outdoor unit Make electrical connections between units prior to proceeding to mains supply unit connection Before proceeding with the connection to...

Страница 12: ...l Cooling only 42PHQ007P 009P 012P 014P 2 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5...

Страница 13: ...2P 014P 2 3 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5 1 5 1 5 1 5 1 5 42PHQ012P 014P...

Страница 14: ...default value of temperatures in Degrees Celsius C to the new value Degrees Fahrenheit o F Press button repeatedly until rc is displayed Press either the or button to change the default value of Heat...

Страница 15: ...ress button to leave the configuration menu Fault code Once a failure occurs with the indoor unit in operation the green LED flashes at intervals of 0 5 seconds The fault code is deduced from the numb...

Страница 16: ...Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2003 Printed in Korea 42KU5A54040...

Отзывы: