GB - 10

42PHQ ...P 

Indoor unit wiring

• Lift the front panel up to the top of the unit; in this way  the

front panel will be separated from the unit.

• Remove the plastic cover of the terminal board.
• Make the electrical connections to the terminal board as per

the wiring diagram.

• When the electrical connections are completed, refit the

terminal board cover and fix the cables with the special cable
holders.

• Fix the front panel to the latch of the frame grille.

IMPORTANT:

• Make refrigerant connections before electrical

connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.

• For sizes 007 - 009 - 012 - 014 make ground connection

prior to any other electrical connections.

• The mains supply must be connected as follows:

sizes 007 - 009 - 012 - 014: to the indoor unit.
sizes 018 - 024 : to the outdoor unit.

• Make electrical connections between units prior to proceeding

to mains supply unit connection.

• Before proceeding with the connection to the mains supply

locate live L and neutral N, then make connections as shown
in the wiring diagram.

• Ensure that mains supply connection is made through a switch

that disconnects all poles, with contact gap of a least 3 mm.

• The indoor - outdoor unit connecting wires must be A07 RN-F

type (or higher), with synthetic rubber insulation with Neoprene
coating, according to EN 60335-2-40 and HD277.S1 codes.

• The mains supply connecting cable must be H07 RN-F type (or

higher), with synthetic rubber insulation with neoprene coating,
according to EN 60335-2-40 and HD277.S1 codes.

• Ground connection between indoor and outdoor units is made

via the refrigerant pipes.

Notes:
All field electrical connections are the responsibility of the
installer.

Electrical connection

Содержание 42PHQ Series

Страница 1: ...42PHQ P INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Страница 2: ...ions and weight 2 Nominal data 2 Operating limits 2 Minimum clearances 3 Material supplied 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 Check 9 Electrical connec...

Страница 3: ...nal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit installation instructions Mod 007 009 012 014 018 024 A...

Страница 4: ...ld supplied items are required to complete the installation Name Specification 007 009 Connection pipe 3 8 9 52 mm Gas 1 4 6 35 mm Liquid 012 014 018 024 1 2 12 70 mm Gas 1 4 6 35 mm Liquid Wall sleev...

Страница 5: ...onsisting of two units manufactured by Carrier Consult the factory or a qualified system engineer prior to connecting this unit to any other manufacturer s outdoor unit Coupling units which have diffe...

Страница 6: ...ondensate dripping Flattening or kinking the refrigerant pipes or condensate pipes Excessive height difference between outdoor and indoor units see installation manual of outdoor unit Unnecessary turn...

Страница 7: ...he bracket and the wall Check that the wall hanging bracket does not move This can cause noise during operation If the unit is removed from the wall hanging bracket after installing it onto the wall r...

Страница 8: ...e the unit using a tool such as a screwdriver set between the middle area of the body and bottom right of the wall hanging bracket Connecting the pipe can be done more easily if the unit is inclined F...

Страница 9: ...to ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used Fla...

Страница 10: ...screws After installation if there is a significant gap between the unit and wall it can be adjusted by securing the body to the wall hanging bracket using 2 screws Screw holes can be only seen after...

Страница 11: ...009 012 014 to the indoor unit sizes 018 024 to the outdoor unit Make electrical connections between units prior to proceeding to mains supply unit connection Before proceeding with the connection to...

Страница 12: ...l Cooling only 42PHQ007P 009P 012P 014P 2 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5...

Страница 13: ...2P 014P 2 3 Minimum connection wire size Minimum connection wire size between for power supply mm2 indoor and outdoor unit mm2 Models GND L N N Y O W2 42PHQ007P 009P 1 5 1 5 1 5 1 5 1 5 42PHQ012P 014P...

Страница 14: ...default value of temperatures in Degrees Celsius C to the new value Degrees Fahrenheit o F Press button repeatedly until rc is displayed Press either the or button to change the default value of Heat...

Страница 15: ...ress button to leave the configuration menu Fault code Once a failure occurs with the indoor unit in operation the green LED flashes at intervals of 0 5 seconds The fault code is deduced from the numb...

Страница 16: ...Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2003 Printed in Korea 42KU5A54040...

Отзывы: