Carrier 42/38SHDS050 Скачать руководство пользователя страница 19

5. Clamp flare form on the end of the pipe. 

The end of the pipe must extend beyond 
the flare form. 

Flare form

Pipe

Fig. 7.5

6.

 

Place flaring tool onto the form.

7.

 

Turn the handle of the flaring tool clockwise 
until the pipe is fully flared. Flare the pipe in 
accordance with the dimensions shown in 
table 7.5.  

Table 7.5: PIPING EXTENSION BEYOND FLARE FORM

  Pipe 
gauge 

Tightening 

torque

Flare dimension (A) 

(Unit: mm/Inch)

Flare shape

Min.

Max .

Ø 6.4

14.2-17.2 N.m 

(144-176 kgf.cm)

8.3/0.3

8.3/0.3

R0.4~0. 8

45

°±

2

90

°     

±

4

A

Fig. 7.6

Ø 9.5

32.7-39.9 N.m 

(333-407 kgf.cm)

12.4/0.48

12.4/0.48

Ø 12.7

49.5-60.3 N.m 

(504-616 kgf.cm)

15.4/0.6

15.8/0.6

Ø 15.9

61.8-75.4 N.m 

(630-770 kgf.cm)

18.6/0.7

19/0.74

Ø 19.1

97.2-118.6 N.m 

(990-1210 kgf.cm)

22.9/0.9

23.3/0.91

8.

 

Remove the flaring tool and flare form, then 
inspect the end of the pipe for cracks and 
even flaring.  

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 
then connect it to the outdoor unit. You should 
first connect the low-pressure pipe, then the high-
pressure pipe.  

1.

 

When connecting the flare nuts, apply a thin coat 
of refrigeration oil to the flared ends of the pipes.  

2.

 

Align the center of the two pipes that you 
will connect.  

Indoor unit tubing

Flare nut

Pipe

Fig. 7.7

3.

 

Tighten the flare nut as tightly as possible by hand. 

4.

 

Using a spanner, grip the nut on the unit tubing.

5.

 

While firmly gripping the nut, use a torque 
wrench to tighten the flare nut according to 
the torque values in table 7.5.  

NOTE:

 Use both a spanner and a torque wrench 

when connecting or disconnecting pipes to/from 
the unit.

Fig. 7.8

 CAUTION

• 

Ensure to wrap insulation around the piping. 
Direct contact with the bare piping may result 
in burns or frostbite.  

• 

Make sure the pipe is properly connected. 
Over tightening may damage the bell mouth 
and under tightening may lead to leakage.   

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle according 
to the diagram below. 

DO NOT 

bend the tubing 

more than 90° or more than 3 times.  

 

 

 

Bend the pipe with thumb

min-radius 10cm (3.9”)

Fig. 7.9

6.

 

After connecting the copper pipes to the 
indoor unit, wrap the power cable, signal 
cable and the piping together with binding 
tape.  

NOTE:

 

DO NOT

 intertwine signal cable with 

other wires. While bundling these items 
together, do not intertwine or cross the signal 
cable with any other wiring. 

7.

 

Thread this pipeline through the wall and 
connect it to the outdoor unit.  

8.

 

Insulate all the piping, including the valves 
of the outdoor unit.  

9.

 

Open the stop valves of the outdoor unit 
to start the flow of the refrigerant 
between the indoor and outdoor unit.  

 

 C AUTION

Check to make sure there is no refrigerant leak 
after completing the installation work. If there is 
a refrigerant leak, ventilate the area immediately 
and evacuate the system (refer to the Air 
Evacuation section of this manual).    

e

 Page 19 

f

 

Refrigerant Piping 

       Connection 

Ø 22

109.5-133.7 N.m 

(1117-1364 kgf.cm)

27/1.06

27.3/1.07

Содержание 42/38SHDS050

Страница 1: ...ing your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installat...

Страница 2: ...cautions 05 Outdoor Unit Installation 12 a Outdoor Unit Installation Instructions 12 b Outdoor Unit Types and Speci cations 13 c Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Co...

Страница 3: ...ping Connection 17 A Notes on Pipe Length and Elevation 17 B Refrigerant Piping Connection Instructions 18 Wiring 20 a Outdoor Unit Wiring 20 b Indoor Unit Wiring 21 23 Air Evacuation 25 a Evacuation...

Страница 4: ...ement sometimes the pipe connections need the transfer connector to install on the outdoor unit 11 Transfer connector 9 52 12 7 indoor unit used for multi type models only NOTE Pipe size di er from ap...

Страница 5: ...strong winds typhoons and earthquakes that might a ect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks a...

Страница 6: ...1 2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 25 Connect the wires Page 20...

Страница 7: ...meets the following requirements There is enough room for installation and maintenance There is enough room for the connecting pipe and drainpipe The ceiling is horizontal and its structure can sustai...

Страница 8: ...mension and air outlet size Air inlet size Air lter Position of descensional ventilation opening and size of mounted hook Air lter Electric control box Table 4 1 unit mm inch MODEL Btu h Outline dimen...

Страница 9: ...re the same size before moving on 2 Carry out the pipe and line operation in the ceiling after nishing the installation of the main body While choosing where to start the operation determine the direc...

Страница 10: ...all be added to reduce the noise for special requirement 1 Install the lter optional according to air inlet size 5 Please refer to the following static pressure to install Change the fan motor static...

Страница 11: ...slightly di erent from the air conditioner you purchased The actual unit shall prevail Step 5 Fresh air duct installation Dimension Duct joint for fresh air 125mm 4 92 160mm 6 3 MODLE 18 60 Step 6 Mot...

Страница 12: ...or unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is located far away from your neighbo...

Страница 13: ...5 1 Length Speci cations of Split Type Outdoor Unit unit mm inch Refer to Fig 5 4 5 5 and Table 5 1 A B D Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 946x810x41...

Страница 14: ...cing the front of the unit 4 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode NOTE Make sure the water drains to a safe location where...

Страница 15: ...lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause a malfunction of the water level switch In HEAT mode the outdoor unit will discharge water Ensure that...

Страница 16: ...r drainage See Fig 6 5 Place the protective wall cu in the hole This protects the edges of the hole and will help seal it when you nish the installation process Wall Indoor Outdoor 12mm 0 5 inch Fig 6...

Страница 17: ...frigerant circuit Contamination in the system may cause poor operating capacity high pressure in the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leak...

Страница 18: ...1 Make sure that the pipe is cut at a perfect 90 angle Refer to Fig 7 2 for examples of bad cuts Oblique Rough Warped 90 Fig 7 2 Step2 Remove burrs Burrs can a ect the air tight seal of refrigerant pi...

Страница 19: ...a torque wrench to tighten the are nut according to the torque values in table 7 5 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 7 8 CAUTION...

Страница 20: ...sconnects all poles with contact gap of a least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting theindoor wires Make s...

Страница 21: ...or connection a Using wire strippers strip the rubber jacket from both ends of signal cable to reveal about 15cm 5 9 of the wires inside b Strip the insulation from the ends of the wires c Using wire...

Страница 22: ...nditioning unit is o perform the next steps Press the button COPY long Press the button or to select the AF Press the button CONFIRM Then the air conditioning unit will start the fan operation for air...

Страница 23: ...System power supply from outdoor unit Power Speci cations e Page 23 f Wiring NOTE...

Страница 24: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Clos...

Страница 25: ...osions or accidents Ensure that the appropriate refrigerant is used Refrigerant containers must be opened slowly Always use protective gear when charging the system DO NOT mix refrigerants types Some...

Страница 26: ...emperature is being registered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works prope...

Страница 27: ......

Отзывы: