Table 9 — Troubleshooting
LEGEND
Replacement Parts —
Quote the unit model number
and unit serial number when ordering replacement parts or
contacting the factory about the unit. This information can be
found on the serial plate attached to the unit. See Fig. 31.
ERROR
DESCRIPTION
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
dd
Heating / Cooling Mode Conflict
System is in cooling or fan only mode and
heating signal is received from a unit on the
system.
All units should be in cooling mode for system to
stay in cooling mode.
System is in heating mode and cooling sig-
nal is received from a unit in the system.
All units should be in heating mode.
E1
Communication Error Between
Indoor and Outdoor Unit
Signal wires are short-circuited or
disconnected.
Check or reconnect signal wire.
Signal wire close to electromagnetic source. Distance signal wires from electromagnetic
source.
PC board fault.
Replace PC board.
E2, E4,
E5
Check Temperature Sensor
Loose connection at port on PC board.
Tighten the connection at port on PC board.
Sensor is short-circuited.
Using multi-meter, measure resistance of the sen-
sor. If the resistance is
100 ohms, change the
sensor.
PC board fault.
Replace PC board.
E6
DC Fan Motor
Operating beyond limits.
Check and correct external static pressure on the
unit.
DC motor fault.
Replace DC motor.
PC board fault.
Replace PC board.
E7
EEPROM Error (Data Storage)
Chip or PC board fault.
Replace PC board.
E9
Communication Error Between
Indoor Unit and Controller
Signal wires are short-circuited or discon-
nected.
Check or reconnect signal wires.
Signal wires close to electromagnetic
source.
Distance signal wires from electromagnetic
source.
PC board fault.
Replace PC board.
Eb
EEV Error
EEV wires are short-circuited or discon-
nected.
Replace EEV wires.
EEV stop.
Replace EEV.
PC board fault.
Replace PC board.
Ed
Outdoor Unit Error
Outdoor unit fault.
Refer to outdoor unit troubleshooting guide.
EE
Condensate Error
Loose connection or disconnected.
Tighten the connection or reconnect at port on PC
board.
Water level float is stuck.
Inspect the slope.
FE
No Address When Powered ON For
First Time
Indoor unit without address.
Run automatic addressing option at the outdoor
unit.
Use remote wireless or wired controller to read-
dress the indoor unit.
UU
MDC In Auto System-Check Mode
MDC fault.
Refer to MDC troubleshooting guide.
EEPROM —
Electronically Erasable Programmable Read-only
Memory
EEV
—
Electronic Expansion Valve
MDC
—
Multiport Distribution Controller
PC
—
Process Controller
Fig. 31 — Unit Serial Plate (Example)
CEILING/FLOOR UNIT
MODEL
R410A
HIGH
LOW
REFRIGERANT
0.44 A
15 A
0.35 A
100W (1/6HP)
40VMU012---3
208/230V-1Ph-60Hz
320 PSIG
580 PSIG
DESIGN
PRESSURE
POWER SUPPLY
MINIMUM CIRCUIT AMPACITY
MAX FUSE OR HACR BREAKER
FAN MOTOR
FLA
OUTPUT
CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236
ELECTRIC CHARACTERISTICS ARE
ONLY FOR INDOOR UNIT.
3124627
SERIAL NO.
Carrier Corporation
1616V00001
Содержание 40VMU012 Series
Страница 19: ......