Nitrogen Purge for MDC Brazing —
• Expansion Valves (EXVA~C) in MDC units are shipped from factory and opened to 120 pulses
• Expansion valves for indoor units also have an initial opening from the factory
• During brazing, purge with high-purity nitrogen from ODU high and low pressure service valves. Recommended nitrogen
flow rate is approximately 1.76 ft
3
/h*. This is brazing sequence for
* Note that
the flow capacity through this system is limited, so you cannot “blow” through the lines with a high
flow of nitrogen. The line can only be slowly purged according to the flow rate mentioned above.
2
1
3
Gas/Liquid
separator
Tm3
Tm1
Tm2
SVM
C
EX
VB
EX
VC
SVME
SVP
EXVA
SV1A-1
SV1B-1
SVmA-n
SVmB-n
HEX1
HEX2
Check valves
PS2
PS1
PS3
ODU side
IDU side
1
2
3
N
2
inlet
Fig. 9 —Nitrogen Purge for MDC Brazing