Thermal sensitivity adj — 

Select

 

“Thermal sensitivity

adj” setting on the “Service” interface.

Thermo-off fan speed — 

Select

 

“Thermo-off fan

speed” setting on the “Service” interface.

Fig. 40 —Thermal Sensitivity Adj.

The thermal sensitivity adj sets a capacity interval. The

 

default is THERMAL ON (1

°

F).

Changeover time — 

Select

 

“Changeover time” setting

 

on the “Service” interface.

Fig. 41 —Changeover Time

This  is  the  changeover  time  for  AUTO  mode  (

NOTE

:

 

AUTO mode is available for Heat Recovery systems only; it is

 

not available for Heat Pump systems.). Changeover time can

 

be set to 15 (default), 30, 60 or 90 minutes.

Anti cold blow — 

Select

 

“Anti cold blow” setting on the

 

“Service” interface.

Fig. 42 —Anti Cold Blow

To prevent the discharge of cold air, the IDU fan is shut off

 

at 

coil temperatures below this setting. Default setting is 68F.

Fig. 43 —Thermo-Off Fan Speed

This  determines  IDU  fan  behavior  when  the  zone  is

 

satisfied ("thermo off") - for both heating and cooling mode.

 

For cooling mode, the default setting is to 

Maintain

 last fan

 

speed before satisfying. For heating mode, the default setting is

 

for the fan to be off.

Static pressure — 

Select

 

“Static pressure” setting on the

 

“Service” interface.

Fig. 44 —Static Pressure

This  selects  the  static  pressure  setting  of  the  IDU  fan.
(

NOTE

: only applicable to IDUs with static pressure settings.)

 

The default setting is 0 in wc.

Occupancy sensor — 

Select

 

“Occupancy sensor” 

setting on the “Service” interface.

Fig. 45 —Occupancy Sensor

These  settings  are  used  when  a  field-provided  occupancy

 

sensor is connected to contact input on IDU control board. 

ON

 

enables occupancy sensor setback; 

Occupancy Delay

 sets the

 

amount of delay before setback; and 

Occupancy Set Temp

 

Offset

 selects the amount of setback after Occupancy Delay has

 

elapsed.

Содержание 40VM Series

Страница 1: ...sult in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices Table 2 Wired Controller Accessory Usage NA...

Страница 2: ...he central controller locks the IDU function and the wired controller cannot use the corresponding functions of the IDU 16 Schedule Turns on when the weekly schedule is available on the wired controll...

Страница 3: ...3 DIMENSIONAL DRAWING 7 1 4 4 7 8 1 1 8 Front View Side View Rear View 2 1 4 3 1 8 Fig 2 Dimensions Note All dimensions are shown in inches...

Страница 4: ...indoor units see Fig 4 2 Connect field provided 24VAC power to R and C terminals 1 Remove back cover from controller as shown in Figure 5 2 Cut a hole in the wall for the 2 wire bundles Run the wires...

Страница 5: ...is turned on as shown in Figure 10 Touch the corresponding fan speed text or the icon to set the fan speed See Figure 12 Fig 8 Snap controller into place Push WALL Fig 9 Turn screen on Fig 10 On Off s...

Страница 6: ...E AND TIME Used to configure date and time settings and corrections DAYLIGHT SAVINGS TIME Used to adjust the clock in observance of daylight savings time ROOM TEMP Used to set display room temperature...

Страница 7: ...Reset to reset all the scheduled tasks Holiday settings 1 Touch the icon from the Setting Schedule screen Figure 20 to access Holiday settings Touch to create a new Holiday Touch Edit to adjust the ex...

Страница 8: ...ose Daylight savings time on the Menu interface 2 Turn the Daylight savings time ON OFF 3 Touch the Edit icon 4 Slide the corresponding items to set the start date and end date respectively 5 Touch th...

Страница 9: ...rds Touch the Delete icon to delete all the error messages It displays the unit address 0 63 for indoor unit and 128 for outdoor unit and the related error code An address is not displayed when the wi...

Страница 10: ...tion setting on the Service interface Fig 35 Query Dry Contact Status Fig 36 Service Menu Password Entry Fig 37 Room temp location The room temperature location can be set to Indoor unit or Wired remo...

Страница 11: ...below this setting Default setting is 68F Fig 43 Thermo Off Fan Speed This determines IDU fan behavior when the zone is satisfied thermo off for both heating and cooling mode For cooling mode the defa...

Страница 12: ...tal Heat Aux Heat Status These settings are used when the IDU is controlling a field provided auxiliary heat source via its ACB interface contact output Turning Aux Heat Status on enables this functio...

Страница 13: ...hedules room temperature display etc Reset setting 1 Choose Reset setting on the Service interface 2 Touch the Reset icon to reset 3 Touch the YES icon to confirm the operation Fig 52 Firmware Update...

Страница 14: ...tic pressure of the DC fan 0 0 in WC default 1 0 04 in WC 2 0 08 in WC 3 0 12 in WC 4 0 16 in WC 5 0 20 in WC 6 0 24 in WC 7 0 28 in WC 8 0 32 in WC 9 0 36 in WC 10 0 40 in WC 11 0 44 in WC 12 0 48 in...

Отзывы: