GB - 8

40SMC---N

Refrigerant connections

VERY IMPORTANT:
To prevent electrical shock or equipment damage, make
sure the power supply sectioners are open before electrical
connections are made.
If this action is not taken, personal injury may occur.

First make the refrigerant connections and then the
electrical ones. In the case of disassembly, operations must
be carried out in the opposite sequence.

WARNING:

Operation of unit on improper line voltage constitutes
abuse and is not covered by Carrier warranty.

IMPORTANT:

• The mains supply indoor unit – outdoor unit connecting

cable must be H07 RN-F (60245IEC66) type synthetic rubber
insulation with neoprene coating.
Consult the wiring diagram sent with the outdoor unit.

• To effect the unit power supply (wire inlet, conductor

section, protections, etc..), consult the Electrical Data
Table, the wiring diagram sent with the unit and the

standards in force affecting the installation of air
conditioning equipment.

• To connect a condensate drainage pump follow the wiring

diagram instructions in the next pages.

VERY IMPORTANT:

The installer should place protection elements in the line
according to the legislation in force.

IMPORTANT:

• Make ground connection prior to any other electrical

connections.

• Make electrical connections between units prior to proceeding

to mains supply unit connection.

• According to the installation instructions, the disconnecting

switches from the mains power supply should have a contact gap
(4 mm) such that total disconnection can be ensured under the
conditions provided for by overvoltage class III.

NOTE:

• All field electrical connection are the responsibility of the

installer.

Cooling only

40SMC 009N, 012N

Power supply from indoor unit

C
G
P

2 3

N N Y O W2 V1 V2 V3 V4 40 41

1

L

C         G       P

2

1

3

1

1

10

80

10

100

3

10

100

10

80

Indoor and outdoor units

CRC

interconnections  (mm

2

)

Model

GND

L

N

GND

N

Y

O

W2

V1

V2

V3

V4

40

41

1

2

3

40SMC009N

3G1,5

3G1,5

Disconnected

3 x 0,75

40SMC012N

3G2,5

3G2,5

H03VV-F

IMPORTANT:
Cable 

 must always be placed above cable 

.

NOTE:
See the outdoor unit installation manual.

Power supply cable (H07 RN-F)

Interconnection cable (H07 RN-F)

Содержание 40SMC009N

Страница 1: ...40SMC N INSTALLATION MANUAL...

Страница 2: ...o the corresponding manuals For the instructions for use of the air conditioner and outdoor installation instructions refer to the corresponding manuals Contents Page Dimensions 2 Technical data 3 Gen...

Страница 3: ...S 009 012 018 725 555 220 743 781 262 222 71 23 607 31 5 59 140 200 35 33 659 45 024 028 036 925 660 285 943 981 241 5 321 97 5 23 712 33 5 118 5 199 5 264 5 35 37 5 850 87 5 048 060 1250 750 310 126...

Страница 4: ...y circuit Connection of the system to the mains power supply is to be carried out in compliance with the wiring diagram shown in the installation instructions of the external section Connect the indoo...

Страница 5: ...life the refrigerant must be taken to special collection points or delivered to the retailer for correct disposal Choosing the installation site The SMC N unit has been conceived for above ceiling in...

Страница 6: ...ted according to the unit discharge head in order to allow sufficient and continuous water evacuation horizontal sections or curves of condensate drain piping with less than 5 slope excessive height d...

Страница 7: ...guarantees perfect watertightness on the drainage pipe If rigid material has been used for the drainage it is necessary to provide some kind of elastic coupling in the drainage line to absorb possible...

Страница 8: ...o ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used Flar...

Страница 9: ...condensate drainage pump follow the wiring diagram instructions in the next pages VERY IMPORTANT The installer should place protection elements in the line according to the legislation in force IMPOR...

Страница 10: ...e placed above cable Power supply cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Indoor and outdoor units CRC interconnections mm2 Model GND L N GND N Y O W2 V1 V2 V3 V4...

Страница 11: ...ND L N Y O W2 V1 V2 V3 V4 40 41 1 2 3 40SMC 009 012 018 024N combined with Multisplit 3G1 3 x 1 Disconnected 3 x 0 75 H03VV F Cooling only 40SMC 018N 024N 028N 036N 048N 060N C G P 3 2 3 C C Y O W2 V1...

Страница 12: ...C Y O W2 S V1 V2 V3 V4 40 41 1 2 3 40SMC018N 024N 028N 3G1 4 x 1 Disconnected 3 x 0 75 40SMC036N 048N 060N H03VV F 3 2 10 80 10 100 10 80 C G P 2 2 3 C C Y O W2 V1 V2 V3 V4 40 41 1 R S C G P 2 1 3 N...

Страница 13: ...necessary Turn on power YES Check Guide for the owner When installation and tests are completed explain the Operation and Maintenance Manual to the owner with particular attention to the main operatin...

Страница 14: ...ow speed Air flow l s 40SMC012N 40SMC018N Pa Pa 100 90 80 70 60 50 40 30 20 10 0 70 90 110 130 150 170 180 190 1 2 3 4 100 90 80 70 60 50 40 30 20 10 0 140 160 180 200 220 120 100 1 2 3 4 100 90 80 70...

Страница 15: ...0 0 220 250 300 400 450 350 1 2 3 4 100 90 80 70 60 50 40 30 20 10 0 300 350 400 450 500 550 1 2 3 4 190 90 40 30 20 10 0 300 400 500 600 700 800 850 900 180 170 160 150 140 130 120 110 100 80 70 60 5...

Страница 16: ...L010127H27 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Отзывы: