GB - 5
40SMC---N
E N G L I S H
Warnings: avoid...
... inclined installation which could cause dripping.
... flattening or kinking the refrigerant pipes or condensate pipes.
... installation in areas with high frequency waves.
... only partial insulation of the piping.
... exposure to oil vapours.
... connecting condensate piping to sewage system drain without
appropriate trap. Trap height must be calculated according to the
unit discharge head in order to allow sufficient and continuous
water evacuation.
... horizontal sections or curves of condensate drain piping with less
than 5% slope.
... excessive height difference between outdoor and indoor units
(see installation manual of outdoor unit).
... slack on electrical connections.
... disconnecting refrigerant connections after installation: this
will cause refrigerant leaks.
... unnecessary turns and bends in connection pipes (see
installation manual of outdoor unit).
Excessive connection pipe length (see installation manual of
outdoor unit).
5