Unit installation

Insert 4 M8 threaded rods into the celling. Introduce the other end
of the rods through the slots of unit suspension brackets.
Position the shock absorbers, add washers and screw the nuts
down until the unit is correctly suported.
If there is sufficient space, a rubber or neoprene sheet can be
placed between the ceiling and the unit.

IMPORTANT:
The unit must be perfectly levelled.

Once these operations have been completed, an above-ceiling
installation will be necessary to conceal the unit; do not forget to
install a removable panel to allow for maintenance operations.
Grills of an adequate size should be incorporated in the unit for
return air suction.

Unit

False ceiling

Ceiling

Register cover

Minimum 5% slope

Installation

Condensate drainage

All units are provided with an internal condensate drain pan which
incorporates a drainage tube 20 mm external Ø (009, 012, 018)
and 25 mm (024, 028, 036, 048, 060).
A tube for evacuating condensates must therefore be provided.

The recommendations below must be followed in all cases:
• Use galvanizad steel, copper or plastic piping.

Do not used ordinary garden hose.

• Use a material that guarantees perfect watertightness on the

drainage pipe.

• If rigid material has been used for the drainage, it is necessary to

provide some kind of elastic coupling in the drainage line to
absorb possible vibrations.

• The drainage line should always be below the connextion itself,

and should also slope to facilitate drainage.

WARNING:
No drillholes should be made in the base of the unit, since the
drain pans may be perforated.

Ductwork

The ductwork dimensions should be determined in accordance
with the air flow circulating through it and with the available static
pressure of the unit.
These information are available in the final pages of the manual.

Various suggestions are made herebelow, regarding the layout
and design of the said doctwork:
• Whatever type of duct is used, it should not be made of materials

which are flammable, or which give off toxic gases in the event
of a fire.
The internal surfaces should be smooth, and not conteminate the
air which passes through.

• At the points where the duct joins with the unit, it is advisable to

use a flexible connection which absorbs vibration and prevents
the transmission of noise inside the ductwork.

• Bends should be avoided as much as possible near the unit

outlet.
If unavoidable, they should be as slight as possible, and internal
deflectors should be used when the duct is of large dimensiones.

IMPORTANT:
Duct calculation and design must be effected by a qualified
technician.

Содержание 40SMC009N

Страница 1: ...40SMC N INSTALLATION MANUAL...

Страница 2: ...o the corresponding manuals For the instructions for use of the air conditioner and outdoor installation instructions refer to the corresponding manuals Contents Page Dimensions 2 Technical data 3 Gen...

Страница 3: ...S 009 012 018 725 555 220 743 781 262 222 71 23 607 31 5 59 140 200 35 33 659 45 024 028 036 925 660 285 943 981 241 5 321 97 5 23 712 33 5 118 5 199 5 264 5 35 37 5 850 87 5 048 060 1250 750 310 126...

Страница 4: ...y circuit Connection of the system to the mains power supply is to be carried out in compliance with the wiring diagram shown in the installation instructions of the external section Connect the indoo...

Страница 5: ...life the refrigerant must be taken to special collection points or delivered to the retailer for correct disposal Choosing the installation site The SMC N unit has been conceived for above ceiling in...

Страница 6: ...ted according to the unit discharge head in order to allow sufficient and continuous water evacuation horizontal sections or curves of condensate drain piping with less than 5 slope excessive height d...

Страница 7: ...guarantees perfect watertightness on the drainage pipe If rigid material has been used for the drainage it is necessary to provide some kind of elastic coupling in the drainage line to absorb possible...

Страница 8: ...o ISO1337 degreased and deoxidized suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used Flar...

Страница 9: ...condensate drainage pump follow the wiring diagram instructions in the next pages VERY IMPORTANT The installer should place protection elements in the line according to the legislation in force IMPOR...

Страница 10: ...e placed above cable Power supply cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Indoor and outdoor units CRC interconnections mm2 Model GND L N GND N Y O W2 V1 V2 V3 V4...

Страница 11: ...ND L N Y O W2 V1 V2 V3 V4 40 41 1 2 3 40SMC 009 012 018 024N combined with Multisplit 3G1 3 x 1 Disconnected 3 x 0 75 H03VV F Cooling only 40SMC 018N 024N 028N 036N 048N 060N C G P 3 2 3 C C Y O W2 V1...

Страница 12: ...C Y O W2 S V1 V2 V3 V4 40 41 1 2 3 40SMC018N 024N 028N 3G1 4 x 1 Disconnected 3 x 0 75 40SMC036N 048N 060N H03VV F 3 2 10 80 10 100 10 80 C G P 2 2 3 C C Y O W2 V1 V2 V3 V4 40 41 1 R S C G P 2 1 3 N...

Страница 13: ...necessary Turn on power YES Check Guide for the owner When installation and tests are completed explain the Operation and Maintenance Manual to the owner with particular attention to the main operatin...

Страница 14: ...ow speed Air flow l s 40SMC012N 40SMC018N Pa Pa 100 90 80 70 60 50 40 30 20 10 0 70 90 110 130 150 170 180 190 1 2 3 4 100 90 80 70 60 50 40 30 20 10 0 140 160 180 200 220 120 100 1 2 3 4 100 90 80 70...

Страница 15: ...0 0 220 250 300 400 450 350 1 2 3 4 100 90 80 70 60 50 40 30 20 10 0 300 350 400 450 500 550 1 2 3 4 190 90 40 30 20 10 0 300 400 500 600 700 800 850 900 180 170 160 150 140 130 120 110 100 80 70 60 5...

Страница 16: ...L010127H27 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Отзывы: