Step 5 — Connect Condensate Drain Line

Observe all local sanitary codes when installing conden-

sate drains. Refer to Fig. 3 and 15 for drain pipe connection
from indoor unit.
1. Use hard polyvinyl chloride (PVC) pipe material with nomi-

nal ID of 3/4 in. to connect at drain line. Use pipe insu-
lation 1/4-in. thick, such as Armaflex insulation, on ex-
posed piping inside the conditioned space.

2. To ensure regular flow of condensate water, the drain pipe

should be pitched toward an open drain or sump at a down-
ward slope of at least 1/4-in. per ft.

3. Attach plate with screws under piping hole.

4. Attach drain pipe with nylon wire tie passing through hole

(Fig. 16).
NOTE: Do not fasten nylon wire ties tight enough to de-
form the insulation, as this affects its performance.

5. Insulate condensate drain line(s) that are located in or above

an occupied area with a condensate-proof material such
as polyurethane or neoprene.

6. Install an external trap at the end of the condensate line.

NOTE: Should your particular installation require one,
a condensate pump may be ordered as a field-installed
accessory.

Table 6 — Required Piston Size for AccuRater

T

Metering Device, Cooling-Only Condensing Units With

Heat Pump Fan Coil Units

INDOOR

UNIT 40QAE

OUTDOOR

UNIT 38HDC

PISTON SIZE

REQUIRED

REQUIRED SYSTEM

CHARGE (lb)*

024†

018

52

3.6

024

024

53

6.2**

036

030

63

5.6

036

65

5.6

048

048

84

7.4

060

060

93

13.6

*Charge is based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coil units.

Check outdoor unit nameplate for required charge.

†Unit is field reconfigured for 18,000 Btuh operation. See Before Installation section on page 3 for reconfiguration details. Check outdoor unit

nameplate for required charge.

**Combination may require charge in addition to what is factory supplied.

NOTES:

1. All pistons are Chattleff

9

B

9

type.

2. All cooling units have a full factory charge for the smallest possible system combination.
3. Service valves are front-seating type.

1 — Air Delivery Louvers
2 — Air Filters
3 — Remote Thermostat
4 — Drain Pipe
5 — Interconnecting Tubing and Wire
6 — Outdoor Unit (38HDC Shown)
7 — Outdoor Unit Disconnect Switch
8 — Indoor Unit Disconnect Switch

Fig. 15 — Component Location (Typical Ceiling-Suspended System)

10

Содержание 40QA

Страница 1: ...ns should be performed by trained service personnel When working on air conditioning equipment observe precautions in lit erature and on tags and labels attached to unit Follow all safety codes Wear s...

Страница 2: ...ure is below 55 F the accessory low ambient or win ter start kit will be required Systems using 38HDS units can operate down to 40 F outdoor air temperature as shipped from the factory If operation at...

Страница 3: ...r ft 150 30 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 LEGEND TXV Thermostatic Expansion Valve Field reconfigured to 18 000 Btuh 11 2 tons See Before Installa tion sectio...

Страница 4: ...ove ft 65 Maximum Lift Fan Coil Below ft 150 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 Field reconfigured to 18 000 Btuh 11 2 tons See Before Installation section on pag...

Страница 5: ...369 on bottom When facing unit discharge UNIT 40QA WEIGHT lb A B E F G QAB QAE ft in mm ft in mm ft in mm ft in mm ft in mm 024 108 110 4 215 16 1294 3 10 1169 4 15 8 1260 1 95 8 549 036 117 119 4 10...

Страница 6: ...t of the unit Wooden Structure Install hanging bolts on a square wooden piece placed over beams Newly Built Concrete Slab Install hanging bolts with in serts embedded bolts etc Metal Structure Install...

Страница 7: ...cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up To connect piping 1 Install insulation Insulate supply and retu...

Страница 8: ...nstall factory supplied piston enclosed in a bag taped inside the out door unit into the AccuRater metering device located in the service valve on the outdoor unit Fig 14 IMPORTANT The factory supplie...

Страница 9: ...ls Check outdoor unit name plate for required charge NOTES 1 All pistons are Chattleff 9B9 type 2 All cooling units have a full factory charge for the smallest possible system combination 3 Service va...

Страница 10: ...ndensate pump may be ordered as a field installed accessory Table 6 Required Piston Size for AccuRaterT Metering Device Cooling Only Condensing Units With Heat Pump Fan Coil Units INDOOR UNIT 40QAE OU...

Страница 11: ...nect to the fan coil unit Place wire through hole on the control box Fig 18 Connect wire to high voltage ter minal board TB1 and ground screw When routing the wire in the unit use care to keep the wir...

Страница 12: ...rminal block Connect the wires Y1 to Y and C to C See Fig 20 HEAT PUMP SYSTEMS The following connections must be made to the 38QRC unit for it to operate as a system with the indoor unit Route 6 wires...

Страница 13: ...ave been installed and that the discharge louvers are positioned correctly After Extended Shutdown If the system has been turned off for more than 12 hours turn on the indoor and outdoor unit disconne...

Страница 14: ...r COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the fan coil relay board is energized The indoor fan s will start in the selected speed if it is not already operating Th...

Страница 15: ...o prevent possible reverse rotation of the compressor Should any of these devices trip after the compressor is energized the Cycle LOC protection device will lock out the outdoor unit turn it off to p...

Страница 16: ...ins to flush out debris To Clean Condensate Drains Clean all drains and drain pans at the start of each cooling season Check the flow by pouring water into the drain TO CLEAN OR REPLACE DRAIN PAN 1 Pl...

Страница 17: ...hermostat Outdoor unit outdoor coil restricted Remove obstruction Fan speed is set too low Adjust fan speed to high or auto using the Fan button on the thermostat System does not heat properly Air fil...

Страница 18: ...S Pump Shutoff Switch RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay SSDR Safety Switch Delay Relay TB Terminal Block TDR Time Delay Relay TRAN Transformer Terminal Marked Terminal Unm...

Страница 19: ...Heat pump fan coil units only Fig 25 Typical System Wiring Cooling Only Systems or Condensing Unit with Heat Pump Fan Coil Unit Systems 19...

Страница 20: ...Fig 26 Typical System Wiring Heat Pump Systems 20...

Страница 21: ......

Страница 22: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Страница 23: ...GLE PHASE POWER HAS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SI...

Страница 24: ...BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG...

Отзывы: