background image

DEFROST (40QAE Only) — The DFB energizes the RVS
(reversing valve solenoid), and the reversing valve switches
to the cooling position. The K1 relay on the DFB opens and
the outdoor fan stops. The W2 contact on the DFB is also
energized, which in turn energizes the defrost relay on the
fan coil relay board, turns off the electric heater and stops
the indoor fan.

The DFB logic checks the 10-minute defrost timer and

the DFT. If the DFT opens in less than 10 minutes, the DFB
switches the unit back to normal heating operation. If the
DFT remains closed, the DFB switches the unit back to heat-
ing operation after 10 minutes. When the DFB changes back
to heating mode, the RVR (reversing valve relay) is deen-
ergized and the reversing valve switches back to heating op-
eration. Both the outdoor and indoor fans come back on, and
if necessary, the electric heater also turns on.

SYSTEM SAFETIES — The system is equipped with the
following safety devices to protect system components:

A. Indoor coil freeze protection thermostat (40QAE unit cool-

ing cycle only) — If a coil temperature of 28 F or lower
is sensed, the compressor and outdoor fan will be shut
down until the coil temperature exceeds 28 F. The in-
door fan will continue to run.

B. Condensate float switch (40QA units equipped with ac-

cessory condensate pump, cooling cycle only) — If the
level of condensate in the drain pan rises too high, the
condensate float switch will turn off the compressor and
outdoor fan until the condensate level returns to normal.
The indoor fan will continue to run.

C. Outdoor Unit Safeties — These units are protected by

the following devices:
• high-pressure switch
• low-pressure switch (condensing units only)
• compressor internal overloads
• outdoor-fan motor internal overload
NOTE: Outdoor units with scroll compressors are also
protected by a high discharge gas temperature sensor and
a 2-minute timer to prevent possible reverse rotation of
the compressor.

Should any of these devices trip after the compressor is

energized, the Cycle-LOC™ protection device will lock out
the outdoor unit (turn it off) to prevent cycling on a safety
device.

SPECIAL OPERATION, HEATING — Outdoor cooling units
may be matched with heat pump ceiling-suspended fan coil
units to provide supplemental electric heat. All other opera-
tion is the same as a cooling-only system, except these units
have heating capability as follows:

When the room thermostat initiates a call for heating, the

electric heater is turned on. The indoor unit fan will start at
the same time if it was not already running.

When the heating requirement is satisfied, the room ther-

mostat will open, and the heater will turn off.

CLEANING AND MAINTENANCE

To avoid the possibility of electric shock, before per-
forming any cleaning and maintenance operations, al-
ways turn off power to the system by pressing the mode
button on the remote thermostat until the display shows
‘‘OFF,’’ and turning off the outdoor disconnect switch
located near the outdoor unit. If the indoor unit is on a
separate switch, be sure to turn this disconnect off as
well.

Do not wash filter in water over 120 F (to avoid shrink-
age). Do not expose filter to fire (to avoid fire damage).
Do not expose filter to direct sunlight. Clean filter more
frequently when air is extremely dirty.

Do not attempt to clean or service components in con-
trol box.

For proper system operation, perform the cleaning and main-

tenance operations in Table 8.

Lubrication —

The indoor-fan, automatic air sweep, and

the outdoor-fan motors are factory lubricated and require no
oiling.

To Remove and Clean or Replace Air Filters
(Fig. 23)

Operating your system with dirty air filters may damage
the indoor unit and, in addition, can cause reduced cool-
ing performance, intermittent system operation, frost
build-up on the indoor coil, and blown fuses. Inspect
and clean or replace the air filters monthly.

TO REMOVE AIR FILTERS — Remove filters by pulling
them straight out.

Fig. 23 — Cleaning Filters

15

Содержание 40QA

Страница 1: ...ns should be performed by trained service personnel When working on air conditioning equipment observe precautions in lit erature and on tags and labels attached to unit Follow all safety codes Wear s...

Страница 2: ...ure is below 55 F the accessory low ambient or win ter start kit will be required Systems using 38HDS units can operate down to 40 F outdoor air temperature as shipped from the factory If operation at...

Страница 3: ...r ft 150 30 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 LEGEND TXV Thermostatic Expansion Valve Field reconfigured to 18 000 Btuh 11 2 tons See Before Installa tion sectio...

Страница 4: ...ove ft 65 Maximum Lift Fan Coil Below ft 150 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 Field reconfigured to 18 000 Btuh 11 2 tons See Before Installation section on pag...

Страница 5: ...369 on bottom When facing unit discharge UNIT 40QA WEIGHT lb A B E F G QAB QAE ft in mm ft in mm ft in mm ft in mm ft in mm 024 108 110 4 215 16 1294 3 10 1169 4 15 8 1260 1 95 8 549 036 117 119 4 10...

Страница 6: ...t of the unit Wooden Structure Install hanging bolts on a square wooden piece placed over beams Newly Built Concrete Slab Install hanging bolts with in serts embedded bolts etc Metal Structure Install...

Страница 7: ...cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up To connect piping 1 Install insulation Insulate supply and retu...

Страница 8: ...nstall factory supplied piston enclosed in a bag taped inside the out door unit into the AccuRater metering device located in the service valve on the outdoor unit Fig 14 IMPORTANT The factory supplie...

Страница 9: ...ls Check outdoor unit name plate for required charge NOTES 1 All pistons are Chattleff 9B9 type 2 All cooling units have a full factory charge for the smallest possible system combination 3 Service va...

Страница 10: ...ndensate pump may be ordered as a field installed accessory Table 6 Required Piston Size for AccuRaterT Metering Device Cooling Only Condensing Units With Heat Pump Fan Coil Units INDOOR UNIT 40QAE OU...

Страница 11: ...nect to the fan coil unit Place wire through hole on the control box Fig 18 Connect wire to high voltage ter minal board TB1 and ground screw When routing the wire in the unit use care to keep the wir...

Страница 12: ...rminal block Connect the wires Y1 to Y and C to C See Fig 20 HEAT PUMP SYSTEMS The following connections must be made to the 38QRC unit for it to operate as a system with the indoor unit Route 6 wires...

Страница 13: ...ave been installed and that the discharge louvers are positioned correctly After Extended Shutdown If the system has been turned off for more than 12 hours turn on the indoor and outdoor unit disconne...

Страница 14: ...r COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the fan coil relay board is energized The indoor fan s will start in the selected speed if it is not already operating Th...

Страница 15: ...o prevent possible reverse rotation of the compressor Should any of these devices trip after the compressor is energized the Cycle LOC protection device will lock out the outdoor unit turn it off to p...

Страница 16: ...ins to flush out debris To Clean Condensate Drains Clean all drains and drain pans at the start of each cooling season Check the flow by pouring water into the drain TO CLEAN OR REPLACE DRAIN PAN 1 Pl...

Страница 17: ...hermostat Outdoor unit outdoor coil restricted Remove obstruction Fan speed is set too low Adjust fan speed to high or auto using the Fan button on the thermostat System does not heat properly Air fil...

Страница 18: ...S Pump Shutoff Switch RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay SSDR Safety Switch Delay Relay TB Terminal Block TDR Time Delay Relay TRAN Transformer Terminal Marked Terminal Unm...

Страница 19: ...Heat pump fan coil units only Fig 25 Typical System Wiring Cooling Only Systems or Condensing Unit with Heat Pump Fan Coil Unit Systems 19...

Страница 20: ...Fig 26 Typical System Wiring Heat Pump Systems 20...

Страница 21: ......

Страница 22: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Страница 23: ...GLE PHASE POWER HAS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SI...

Страница 24: ...BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG...

Отзывы: