background image

Table 3A — Physical Data, 40QAB Cooling-Only Units

UNIT 40QAB

024*

024

036

048

060

NOMINAL CAPACITY (Tons)

1

1

2

2

3

4

5

NOMINAL SIZE (Btuh)

18,000

24,000

36,000

36,000

60,000

OPERATING WEIGHT (lb)

108

108

117

149

179

MOISTURE REMOVAL RATE (Pints/Hr)

5.8

7.1

9.5

13.4

15.1

FINISH

GM Motorhome White with Black Trim

REFRIGERANT

R-22

Control (Cooling)

AccuRater

T

Piston in Fan Coil Unit/TXV in Condensing Unit

System Charge Required (lb)†

3.7

5.5

5.6/5.4**

7.4

13.6

INDOOR FAN

Direct Drive Centrifugal

Rpm...Cfm High

862...500

862...500

1275...840

1435...1200

1275...1600

Rpm...Cfm Medium

690...400

690...400

972...740

1388...1160

972...1220

Rpm...Cfm Low

552...320

552...320

830...640

1315...1100

830...1040

High Speed Watts

92

92

282

425

564

Quantity...Motor Hp

1...

1

15

1...

1

15

1...

1

6

2...

1

15

2...

1

6

Blowers — No. ...Size (in.)

2...6 x 8

2...6 x 8

2...6 x 8

3...6 x 8

4...6 x 8

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)

2.2

2.2

2.6

3.0

4.0

No. of Rows

4

4

4

4

4

Fins/in.

14.9

14.9

14.9

14.9

14.9

Circuits

4

4

4

8

8

FILTERS

Cleanable

(Quantity) Size (in.)

(4) 12 x 8

3

4

(5) 10

5

8

x 8

3

4

(4) 10

5

8

x 8

3

4

(2) 12 x 8

3

4

(6) 12 x 8

3

4

AIRSWEEP

Horizontal

Vertical

Automatic

CONTROLS

Control Voltage

24-v Provided in Control

Auto. Restart

Yes

Fan Speed

High/Medium/Low

Condensate Pump Safety

Yes (Accessory)

Outdoor Coil High Temperature (Cooling Modes)

Outdoor Coil Temperature greater than 144 F; Resets at 104 F

Filter Change Indication

250 Hours of Indoor Fan Operation (through thermostat)

REFRIGERANT LINES

Connection Type

Flare

Liquid Line OD (in.)

3

8

Vapor Line OD (in.)

5

8

5

8

3

4

7

8

††

7

8

††

Maximum Length (ft)

200/50

\

Maximum Lift Fan Coil (Above Outdoor) (ft)

65/30

\

Maximum Lift Fan Coil (Below Outdoor) (ft)

150/30

\

CONDENSATE DRAIN CONNECTION

Pipe Thread (MPT)

CONDENSATE DRAIN SIZE (in.)¶

3

4

LEGEND

TXV — Thermostatic Expansion Valve

*Field reconfigured to 18,000 Btuh (1

1

2

tons). See Before Installa-

tion section on this page for details.

†Outdoor unit is shipped with a full charge for the smallest system

configuration. Refer to unit nameplate (on the unit) for details on
specific system charge required.

**When matched with a size 030 outdoor unit/when matched with a

size 036 outdoor unit.

††The valve connection size is

3

4

inch. The recommended line size

is

7

8

inch.

\

When matched with a 38HDC cooling only unit/when matched with
a 38HDS multi-split unit.

¶ Flexible tubing (

5

8

in.) is required when accessory condensate pump

is used.

Step 1 — Complete Pre-Installation Checks

UNPACK UNIT — Store fan coil unit in the original pack-
aging until it is moved to the final site for installation. When
removing unit from carton, lift unit by its 4 corners; DO NOT
lift unit by its plastic parts.

INSPECT SHIPMENT — Upon receipt of shipment, check
fan coil unit for damage. Forward claim papers directly to
the transportation company. Manufacturer is not responsible
for damage incurred in transit.

Check all items; if any item is missing, notify your Car-

rier distributor. To prevent loss or damage, leave all parts in
original packages until installation.

BEFORE INSTALLATION — Perform the following steps
before installing indoor fan coil unit. Place the indoor unit
upside down on the floor, then:
1. Remove side panels by sliding forward, then away from

sides of unit (Fig. 2). Reinstall prior to unit start-up.

2. Remove air filters from inlet grilles; then remove and re-

tain screws securing inlet grilles to indoor unit. Reinstall
prior to unit start-up.

NOTE: Dimensions shown in brackets [

] are in mm.

Fig. 2 — Removal of Mounting Brackets

from Indoor Unit

3

Содержание 40QA

Страница 1: ...ns should be performed by trained service personnel When working on air conditioning equipment observe precautions in lit erature and on tags and labels attached to unit Follow all safety codes Wear s...

Страница 2: ...ure is below 55 F the accessory low ambient or win ter start kit will be required Systems using 38HDS units can operate down to 40 F outdoor air temperature as shipped from the factory If operation at...

Страница 3: ...r ft 150 30 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 LEGEND TXV Thermostatic Expansion Valve Field reconfigured to 18 000 Btuh 11 2 tons See Before Installa tion sectio...

Страница 4: ...ove ft 65 Maximum Lift Fan Coil Below ft 150 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 Field reconfigured to 18 000 Btuh 11 2 tons See Before Installation section on pag...

Страница 5: ...369 on bottom When facing unit discharge UNIT 40QA WEIGHT lb A B E F G QAB QAE ft in mm ft in mm ft in mm ft in mm ft in mm 024 108 110 4 215 16 1294 3 10 1169 4 15 8 1260 1 95 8 549 036 117 119 4 10...

Страница 6: ...t of the unit Wooden Structure Install hanging bolts on a square wooden piece placed over beams Newly Built Concrete Slab Install hanging bolts with in serts embedded bolts etc Metal Structure Install...

Страница 7: ...cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up To connect piping 1 Install insulation Insulate supply and retu...

Страница 8: ...nstall factory supplied piston enclosed in a bag taped inside the out door unit into the AccuRater metering device located in the service valve on the outdoor unit Fig 14 IMPORTANT The factory supplie...

Страница 9: ...ls Check outdoor unit name plate for required charge NOTES 1 All pistons are Chattleff 9B9 type 2 All cooling units have a full factory charge for the smallest possible system combination 3 Service va...

Страница 10: ...ndensate pump may be ordered as a field installed accessory Table 6 Required Piston Size for AccuRaterT Metering Device Cooling Only Condensing Units With Heat Pump Fan Coil Units INDOOR UNIT 40QAE OU...

Страница 11: ...nect to the fan coil unit Place wire through hole on the control box Fig 18 Connect wire to high voltage ter minal board TB1 and ground screw When routing the wire in the unit use care to keep the wir...

Страница 12: ...rminal block Connect the wires Y1 to Y and C to C See Fig 20 HEAT PUMP SYSTEMS The following connections must be made to the 38QRC unit for it to operate as a system with the indoor unit Route 6 wires...

Страница 13: ...ave been installed and that the discharge louvers are positioned correctly After Extended Shutdown If the system has been turned off for more than 12 hours turn on the indoor and outdoor unit disconne...

Страница 14: ...r COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the fan coil relay board is energized The indoor fan s will start in the selected speed if it is not already operating Th...

Страница 15: ...o prevent possible reverse rotation of the compressor Should any of these devices trip after the compressor is energized the Cycle LOC protection device will lock out the outdoor unit turn it off to p...

Страница 16: ...ins to flush out debris To Clean Condensate Drains Clean all drains and drain pans at the start of each cooling season Check the flow by pouring water into the drain TO CLEAN OR REPLACE DRAIN PAN 1 Pl...

Страница 17: ...hermostat Outdoor unit outdoor coil restricted Remove obstruction Fan speed is set too low Adjust fan speed to high or auto using the Fan button on the thermostat System does not heat properly Air fil...

Страница 18: ...S Pump Shutoff Switch RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay SSDR Safety Switch Delay Relay TB Terminal Block TDR Time Delay Relay TRAN Transformer Terminal Marked Terminal Unm...

Страница 19: ...Heat pump fan coil units only Fig 25 Typical System Wiring Cooling Only Systems or Condensing Unit with Heat Pump Fan Coil Unit Systems 19...

Страница 20: ...Fig 26 Typical System Wiring Heat Pump Systems 20...

Страница 21: ......

Страница 22: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Страница 23: ...GLE PHASE POWER HAS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SI...

Страница 24: ...BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG...

Отзывы: