40KMC---N
GB - 3
E N G L I S H
Technical data
Note: For power supply wire size and delay type fuses, refer to the outdoor unit installation instructions.
Table I: Nominal data
POWER INPUT (WATT)
Cooling only
Sizes
standard
Cooling
Heating
12
40KMC012-7N
75
75
18
40KMC018-7N
80
80
24
40KMC024-7N
105
105
28
40KMC028-7N
107
107
36
40KMC036-7N
131
131
48
40KMC048-7N
178
178
60
40KMC060-7N
231
231
Sizes
with electric heaters
Cooling
Heating
12
40KMC112-7EN
75
1575
18
40KMC118-7EN
80
2580
24
40KMC124-7EN
105
2605
28
40KMC328-7EN
107
3107
36
40KMC336-7EN
131
3131
48
40KMC348-7EN
178
3178
60
40KMC360-7EN
231
3231
POWER INPUT (WATT)
Heat pump
Sizes
standard
Cooling
Heating
12
40KMC012-7N
75
75
18
40KMC018-7N
80
80
24
40KMC024-7N
105
105
28
40KMC028-7N
107
107
36
40KMC036-7N
131
131
48
40KMC048-7N
178
178
60
40KMC060-7N
231
231
Sizes
with electric heaters
Cooling
Heating
12
40KMC112-7EN
75
1575
18
40KMC118-7EN
80
1580
24
40KMC124-7EN
105
1605
28
40KMC328-7EN
107
2107
36
40KMC336-7EN
131
2131
48
40KMC348-7EN
178
2178
60
40KMC360-7EN
231
2231
Table II: Technical data of electric heaters (if installed)
Heat pump
Cooling only
Mod.
12
18
24
28
36
48
60
12
18
24
28
36
48
60
Electric heater
kW
1.5
1.5
1.5
2 x 1.0 2 x 1.0 2 x 1.0 2 x 1.0
1.5
1.5
1.5
2 x 1.0 2 x 1.0 2 x 1.0 2 x 1.0
+
+
+
+
+
+
capacity
1.0
1.0
2 x 0.5 2 x 0.5 2 x 0.5 2 x 0.5
Supply voltage
V
230
230
230
230
230
230
230
230
230
230
400
400
400
400
(*)
(*)
(*)
(*)
(*)
(*)
3N
3N
3N
3N
Max. current draw
A
6.5
6.5
6.5
8.8
8.8
8.8
8.8
6,5
10.8
10.8
7.5
7.5
7.5
7.5
Control device
GMC electronic control
Safety thermostat
N
°
1 Manual reset thermostat ST1 60
°
C
N
°
1 Manual reset thermostat ST2 100
°
C
Power supply cables
mm
2
3 G 1.5 3 G 1.5 3 G 1.5 4 G 1.5 4 G 1.5 4 G 1.5 4 G 1.5 3 G 1.5 3 G 2.5 3 G 2.5 5 G 1.5 5 G 1.5 5 G 1.5 5 G 1.5
Recommended fuse (gL type)
A
8
8
8
8
8
8
8
8
12
12
10
10
10
10
*In areas with a 2 kW limit for single-phase electric heaters it is possible to divide the power supply on two phases and neutral of a three phase supply with neutral.
Use cable type H07 RN-F - 4G1,5 mm
2
- 400V 2N ~
Table III:
Material supplied
Description
Quantity
Use
Installation instructions
1
Indoor unit installation
Owner's Manual
1
Correct use
Fresh air intake baffle
1
Air renewal
Table IV: Operating limits
Cooling / Heating
Refer to outdoor unit installation manual.
Nominal single-phase voltage
230V ~ 50Hz
230V-240V ~ 60Hz
Main power supply
Operating voltage limits
min. 198V – max. 264V
Nominal three-phase voltage
400V 3N~ 50Hz
Operating voltage limits
min. 342V – max. 462V
Electric heater
27
°
C
Table V: Components required for a complete installation
Name
Specification
Connection pipe
40KMC 012N Ø (1/2") 12.70 mm (Gas) / Ø (1/4") 6.35 mm (Liquid)
40KMC 018N, 024N, 028N, 036N, 048N and 060N Ø (1/2") 12.70 mm (Gas) / Ø (1/4") 6.35 mm (Liquid)
Wall sleeve
Wall cap
Finishing tape
PVC film
Fastening tape
Tube insulation
Drain hose
I.D. 16 - 17 mm
Sealer putty
- Outdoor power supply cable
H07 RN-F (60245IEC66),
cable with synthetic rubber insulation and polychloroprene sheath.
- Electrical connecting cable
H07 RN-F (60245IEC66),
between indoor and outdoor unit
cable with synthetic rubber insulation and polychloroprenesheath.