Prior to installation

It is advisable to place the unit as close as possible to the
installation site before removing it from the packaging. The grille
panel and the remote control are separately packed for maximum
protection.

IMPORTANT:
Do not lift the unit by the condensate drain discharge pipe or
by the refrigerant connections; hold it by its four corners
only.

Unit installation will be facilitated using a stacker.

If plaster board ceiling panels are installed the maximum
dimensions of the unit housing must not exceed 660 x 660 mm (for
models 12-18-24) and 900 x 900 mm (for models  28-36-48-60).

In rooms with high humidity, brackets should be insulated using
the  self adhesive insulation supplied.

Installation

Installation




Threaded hangers

"T" bar
(to be removed)

   

 False ceiling

 

 Spirit level

                                 

 

 

Suspension brackets

mm

Carefully lift the unit (without the frame) using the four
suspension brackets (or the four corners), inserting it into the
false ceiling.
If the “T” bar cannot be removed the unit may need to be tilted
(this operation may only be carried out with false ceilings with a
minimum height of 300 mm).

First position the refrigerant lines, as described in the chapter
“Refrigerant connections”.
Remove the “T” bar in order to facilitate installation operations.

Mark the position of the hangers, refrigerant lines and condensate
drain pipe, power supply cables and remote control cable (see
dimensions); the cardboard template (supplied with the kit) may
be of assistance for this operation.
Depending on the type of ceiling the hangers can be fixed as
shown in the drawing.

Once the threaded hangers have been positioned, do not tighten
the nuts, and insert the washers as shown in the drawing.

Washer

Threaded hangers

Washer

Nut

Nut

Nut

Wooden frame

Threaded hangers

Washers

Nut

Align and level the unit by adjusting the nuts and locknuts on
the threaded hangers, maintaining a distance of 25 - 30 mm
between the sheet metal body and the underside of the false
ceiling.
Reposition the “T” bar and align the unit in relation to the bar by
tightening the nuts and locknuts.
After connection of the condensate drain line and the refrigerant
lines, carry out a final check to make sure that the unit is level.

Содержание 40KMC---N

Страница 1: ...AM PM 40KMC N INSTALLATION MANUAL...

Страница 2: ...3 Technical data of electric heaters 3 Material supplied 3 Operating limits 3 Components required for a complete installation 3 General information 4 Accessories 4 Warnings avoid 5 6 Installation 6 8...

Страница 3: ...036 048 060 Unit 17 5 19 19 36 38 38 41 Frame Grille assembly 3 3 3 5 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8...

Страница 4: ...8 8 8 8 8 6 5 10 8 10 8 7 5 7 5 7 5 7 5 Control device GMC electronic control Safety thermostat N 1 Manual reset thermostat ST1 60 C N 1 Manual reset thermostat ST2 100 C Power supply cables mm2 3 G...

Страница 5: ...bility for damage resulting from modifications or errors in the electrical or refrigerant connections Failure to observe the installation instructions or use of the unit under conditions other than th...

Страница 6: ...unit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conde...

Страница 7: ...utlets as indicated in the drawing WARNING To close one or two air outlets use the special kit Install the unit as centrally as possible in the room the air flow direction can be controlled by means o...

Страница 8: ...the unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant c...

Страница 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate w...

Страница 10: ...ns The length of the flared walls must be uniform Lubricate the end of pipe and the thread of the flare connection with anti freeze oil Tighten by hand and then use two wrenches to tighten all connect...

Страница 11: ...VER connector Float connector Pump connector Louvre connector A Electric heater supply connection B Outdoor unit connection CP CG CA CV CLR CONTROL PANEL mod 28 36 48 60 SYSTEM CONFIGURATION IMPORTANT...

Страница 12: ...split unit 4G1 WARNING The ground wire for the indoor unit outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole WARNING The ground wire for the...

Страница 13: ...tin plated eyelet terminal with M4 screw hole 1 2 3 10 80 10 100 4 5 Terminal box legend all models Earth L Live power supply N Neutral power supply N Neutral connection indoor outdoor unit Y Compres...

Страница 14: ...F Interconnection cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Notes See outdoor unit installation manual For correct passage of cables please refer to the drawing sho...

Страница 15: ...MICROSWITCH LOUVRE RELAY BOARD ELECTRIC HEATER SAFETY THERMOSTAT IF PRESENT WIRE COLOURS BROWN BLUE BLACK GREY YELLOW GREEN ORANGE RED WHITE YELLOW IMPORTANT THE WARRANTY WILL BE INVALIDATED IF FACTO...

Страница 16: ...tted grille Air intake grille Fresh air renewal and conditioned air supply to an adjacent room Use locally purchased material suitable for operating temperatures of 60 C continuous Conduits can be of...

Страница 17: ...per during shutdown periods unnecessary Conditioned air supply to an adjacent room Air supply to an adjacent room requires that the outlet corresponding with the duct is closed using the air supply ou...

Страница 18: ...will be cleared the time segments will display the first configuration item rAdr remote address and the tempera ture segments will display the default value of this configuration item Ab control of bo...

Страница 19: ...te When 30 minutes have elapsed and no buttons have been pressed the remote control will automatically exit the test menu and resume its normal operation Address selector If you are installing two ind...

Страница 20: ...code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses with enabled code Guide for the owner When...

Страница 21: ...L010127H26 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Отзывы: