51
8. If solution is too weak, add more antifreeze until desired
strength is reached, then circulate solution through coil for 15
minutes or until concentration is satisfactory.
9. Remove upper line from reservoir to reversible pump. Drain
coil to reservoir and then close service valve.
10. Break union and remove reservoir and its lines.
11. Leave coil flanges or coupling open and auxiliary drain
valves open until spring.
AIR DRYING METHOD OF COIL PROTECTION (UNIT
AND COIL MUST BE LEVEL FOR THIS METHOD.)
1. Close coil water supply and return main valves.
2. Drain coil as described in procedures for Antifreeze Methods
of Coil Protection.
3. Connect air supply or air blower to inlet header connection
and close its drain connection.
4. Circulate air and check for air dryness by holding mirror in
front of open vent in outlet header drain connection. Mirror
will fog if water is still present.
5. Allow coil to stand for a few minutes; repeat Step 4 until coil
is dry.
Field-Installed Coils (39LA,LD Only)
When a 39LA or 39LD unit is ordered without the coil, the fol-
lowing loose parts are shipped (see Fig. 53):
• bottom coil baffle
• side hairpin baffle
• side header baffle
• top coil baffle
These parts should be field-installed onto the coil before placing
the coil into the unit. Once the baffles are installed, install the coil
with the downstream bottom of the coil attached to the upright
mounting flange as shown in Fig. 54. Adjust the coil and then at-
tach the top coil baffle to the top flange provided.
Coil Removal
HORIZONTAL UNIT SLANT COIL REMOVAL (39LA
UNITS)
NOTE: Item numbers are in Fig. 54.
1. Refer to Fig. 10 for service area clearance.
2. Disconnect piping (Item 5).
3. On top panel (Item 3), remove screws located directly above
side panels (Items 2 and 6). Top panels may be removed from
unit to provide more workspace, but it is not required.
4. Remove right side panels (Item 6).
5. If accessory is present, remove accessory side panel (Item 1)
on left side of unit. Detach filter track support bracket if
upstream accessory is a filter.
6. Remove screws from inside baffle (Item 13). Leave baffle
attached to left side panel (Item 2).
7. Remove left side panel (Item 2).
8. Remove condensate baffle (Item 8).
9. Remove coil holddown screws (Items 9 and 11).
10. Remove baffle screws (Item 4) from downstream side of coil.
11. Tilt coil (Item 10) away from coil support panels (Items 7 and
12) and slowly slide coil out of unit.
12. Replace coil by reversing preceding Steps 1-11.