24
* Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v /
60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
† Motor Nameplate Amps. Factory programmed per Programmed Set-
tings in Table 6. This value should always be compared to the actual
motor nameplate value before start-up.
** Maximum Output Amps — Factory programmed per Table 6.
Fig. 22 — Field-Supplied Control Wiring for VFD Speed Control
34
3415
Signal Parameter 3
Speed
3416
Signal 3 Minimum
0
3417
Signal 3 Maximum
30000
3418
Output 3 DSP From
0
3419
Output 3 DSP units
rpm
3420
Output 3 Minimum
0
3421
Output 3 Maximum
3000
40
4001
Gain
0.7
4002
Integration Time
30 sec.
4005
Error Value Invert
no
4006
Units
volts
4007
Display Format
x.xxx
4010
Setpoint Select
Internal
4011
Internal Setpoint
Field Program (0.0v~10,0v)
4012
Setpoint Minimum
0 v
4013
Setpoint Maximum
10.0v
4016
ACT 1 Input
AI-2
4027
PID Parameter Set
SET 1
53
5301
EFB Protocol ID
0
5303
EFB Baud Rate
9.6
5304
EFB Parity
8 NONE 1
5305
EFB Control Profile
ABB DRV LIM
5310
EFB PAR 10
0
5311
EFM PAR 11
0
98
9802
Comm Prot SEL
NOT SEL
Table 7 — Air Handler VFD Factory-Set Parameters (cont)
GROUP NUMBER
PARAMETER
NUMBER
DESCRIPTION
VFD DRIVE ONLY PARAMETERS
NOTES:
1. All conductors are no. 22 AWG (American Wire Gage) minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required.