background image

versus outdoor temperature can be found in the unit Product Data
Sheet. The cooling load must be taken from structure’s heat
gain/loss calculations. The selected temperature is the point at
which high-speed capacity is needed and is just above the
low-speed balance point. (See Fig. 11.)

After temperature is selected, unit operates in high speed during
first-stage demand at any temperature at or above the setting.

ZONING SELECTION

If the STAGE 2 LATCH pot is set to the ZONE position,
compressor operating speed in either heat or cool mode is

determined by Y1 and/or Y2 inputs. The system operates in low
speed with a Y1 input and high speed with a Y2, or Y1 and Y2
input. This allows the multistage zoning system to determine what
heating speed is needed regardless of outdoor temperature or
switchover point.

DEFROST TIME SELECTION

The defrost interval can be field selected, dependent on local or
geographical requirements. It is factory set at 90 minutes but can
be changed to either 30 or 50 minutes by rotating DEFROST
TIME pot. (See Fig. 9.)

DEFROST

The 2-speed control logic for defrost function is the standard time
and temperature initiated, time or temperature terminated. Defrost
only occurs at outdoor temperatures less than 50°F. The control
initiates defrost when outdoor coil thermistor is 30°F (

±

2°) or less,

and selected defrost time (interval) has been accumulated during
unit operation. Termination occurs when coil thermistor reaches
80°F (

±

5°) or defrost period reaches a maximum of 10 minutes.

Defrost is always done in high speed, even if unit operation
requires low speed, unless zoning is selected. During defrost, unit
operates in high speed, energizes reversing valve O and auxiliary
heat W2, and de-energizes outdoor fan. Upon termination, there is
a 20-sec delay in outdoor fan being energized.

FIELD-INITIATED FORCED DEFROST

By placing a jumper across speed-up terminals for a minimum of
5 sec and then removing it, a defrost cycle can be initiated. (See
Fig. 9.) The cycle occurs only if outdoor ambient is less than 50°F,
regardless of outdoor coil temperature. The cycle terminates when
coil thermistor reaches 80°F (

±

5° ) or defrost period reaches a

maximum of 10 minutes.

FURNACE INTERFACE

This feature provides a heat pump lockout upon a demand for
auxiliary heat W2 and must be used when interfacing a heat pump
with a gas/oil furnace. Field selection of furnace interface FURN
INT option is done by connecting factory-supplied jumper to ON
position of terminal 3 connector. (See Fig. 9.)

NOTE:

Do not select the Furnace Interface Option if using a

Carrier Dual Fuel thermostat or the Thermidistat Control.

When this option is selected, heat pump is locked out of operation
any time there is a thermostat call for W2, or outdoor ambient is
below balance point pot setting. (See Fig. 9.) When unit requires
defrost, auxiliary heat W2 energizes the furnace. After defrost is
terminated, heat pump shuts down and furnace continues to
operate until thermostat is satisfied. To utilize this function, the
economic and/or thermal balance point must be determined. See
appropriate heat pump balance point worksheet in unit Product
Data Sheet.

Table 9—Factory Defaults

FAILED COMPONENT

FUNCTION

DEFAULT

Ambient Thermistor

Crankcase Heater

Energized during any off cycle

Second-Stage Latching

Does not function

Furnace Interface

Balance point does not function, but inter-
face still energizes furnace and locks out
heat pump with a call for W2

Heating Switchover Speed Point

Unit only runs in high compressor speed

Defrost Initiation

Defrost is initiated based on coil tempera-
ture only

Outdoor Thermostat for Auxiliary Heat

Anytime there is a call for W2, W3 is also
energized

Outdoor Coil Thermistor

Defrost Initiation and Termination

Defrost occurs at each time interval, but
terminates after 5 minutes

Furnace Interface Jumper

Furnace Interface

Does not function

Fig. 10—LED and Potentiometer Location

A93569

HIGH VOLTAGE

LOW VOLTAGE

L2

LO

HI

CCH

ODF

O

C

LM1 LM2

DFT1 DFT2 T1

T2

S2

S1

PW2 PW1

P1

1

18

SPEED-UP

STAGE 2

LATCH

DEFROST

TIME

BALANCE

POINT

K7

K6

K5

K4

K3

K2

K1

LED 1

FURN INT

OFF

ON

Fig. 11—Typical Cooling Balance Points

A91282

10

20

30

40

50

60

70

50

60

70

80

90

100

110

120

BTU (1000'S)

HIGH SPEED CAPACITY

 

HIGH SPEED
BALANCE POINT

LOW SPEED
BALANCE POINT

LOW SPEED CAPACITY

TEMPERATURE (°F)

STRUCTURE
BALANCE POINT

17

Содержание 38YDA

Страница 1: ...rom improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to...

Страница 2: ...door operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating ambient in heating mode is 66 F Step 5 Elevate Unit Accu...

Страница 3: ...uct Data Sheet for factory approved indoor units Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or facto...

Страница 4: ...for 2 speed units Do not attempt to operate unit below 55 F in cooling mode or modify control system for low ambient operation Compressor dam age may occur Available electrical accessories include lat...

Страница 5: ...ate unit in a vacuum or at negative pressure Do not disable low pressure switch In scroll compressor applications Dome temperatures may be hot To prevent personal injury wear safety glasses protective...

Страница 6: ...LE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED HEAT PUMP See notes 7 8 9 and 11 W2 G W2 O R W3 R L H R1 COOL HEAT STAGE 1 COOL HEAT STAGE 2 24 VAC HOT Y Y2 A D A97498 R C C Y1 W3 O TYPICAL FAN COIL...

Страница 7: ...UMPER J2 JUMPER TWO SPEED HEAT PUMP See notes 7 8 9 11 and 23 DH Y1 Y1 W W1 O W2 Y1 W2 O W1 Y Y2 Y2 W2 W3 Y Y2 O W2 COOL HEAT STAGE 1 COOL HEAT STAGE 2 HEAT STAGE 3 RVS COOLING H A98628 R Y2 R Y2 C C...

Страница 8: ...FURNACE TWO SPEED HEAT PUMP See notes 7 9 11 14 and 24 W R Y1 R O W2 G L W3 Y H R1 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT K A98587 24 VAC HOT 24 VAC COMM HEAT STAGE 3 R C G W W1 Y Y2 R C RVS COOLING...

Страница 9: ...C Y2 W3 W2 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY See notes 7 11 14 15 16 17 18 and 25 N A OUTDOOR SENSOR CONNECTION Y Y2 HUM...

Страница 10: ...W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 FAN HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING 24 VAC HOT P A97497 24 VAC HOT 24 VAC COM HE...

Страница 11: ...CE WITH ICM BLOWER MOTOR TWO SPEED HEAT PUMP See notes 6 7 9 11 12 14 21 and 24 R Y1 R O G L W3 W W1 Y Y2 W2 Y1 COOL HEAT STAGE 2 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT W A97496 R C C W2 TWO STAGE VA...

Страница 12: ...3 W2 O C DHUM HUM B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 HEAT COOL STAGE 1 HEAT COOL STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y...

Страница 13: ...t pump MUST have a high pressure switch for dual fuel applications 15 Outdoor air temperature sensor must be attached in all dual fuel applications 16 Thermidistat Dip Switch 1 should be set in the ON...

Страница 14: ...w Selection for 58MVP Furnaces CFM 38YDA UNIT SIZE HIGH SPEED A C SETUP SWITCH POSITION FURNACE MODEL HEATING SIZE LOW SPEED CF SETUP SWITCH POSITION 060 080 100 A C 1 A C 2 A C 3 High Low High Low Hi...

Страница 15: ...ersects measured liquid service valve pressure 6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line temperature is higher than indicated or rec...

Страница 16: ...door coil heat and minimize the steam cloud effect SECOND STAGE LATCHING Mechanical thermostats operate with a staging differential of 2 F droop Carrier electronic thermostats are droopless meaning th...

Страница 17: ...ature The cycle terminates when coil thermistor reaches 80 F 5 or defrost period reaches a maximum of 10 minutes FURNACE INTERFACE This feature provides a heat pump lockout upon a demand for auxiliary...

Страница 18: ...appears at control board If a PTC trip occurs 3 times the control locks out outdoor unit operation and provides a malfunction signal at control PRESSURE SWITCH PROTECTION The outdoor unit is equipped...

Страница 19: ...s the resistance decreases A thermistor is used to sense outdoor ambient Refer to Fig 14 for resistance values versus temperature If outdoor ambient thermistor should fail a malfunction signal appears...

Страница 20: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalo...

Отзывы: