Carrier 38YDA Скачать руководство пользователя страница 13

WIRING DIAGRAM NOTES:

1. Carrier thermostat wiring diagrams are only accurate for model numbers TSTAT _ _ _ _ _ _ _.

2. Wiring must conform to NEC or local codes.

3. Connect 24-v field wiring to factory-provided stripped leads.

4. Thermostats are factory configured with 5-minute compressor cycle protection and 4 cycles per hour limit. See thermostat Installation

Instructions for details.

5. To stage electric resistance heat, consult outdoor thermostat Installation Instructions.

6. Terminals marked with an * may not be present on equipment.

7. Underlined letter on dual terminal indicates its usage.

For example: O/W2 means O is energized in cooling mode.

8. Refer to fan coil Installation Instructions for features and additional wiring information.

9. Programmable model 2S, when used in heat pump installations (Switch C OFF), uses O/W2 to control reversing valve.

10. Non-programmable model 2S, when used in heat pump installations (Jumper R19 NOT cut), uses O/W2 to control reversing valve.

11. Select the ZONE position on 2-speed heat pump control board. In heating mode, this allows Y1 to control low-speed compressor

operation and Y2 to control high-speed compressor operation.

12. Furnace must control its own second-stage operation via furnace control algorithm. Refer to furnace Installation Instructions for proper

setup.

13. To activate dehumidify function on FK4C or 40FKA, remove J1 jumper at fan coil control board.

14. Heat pump MUST have a high-pressure switch for dual fuel applications.

15. Outdoor air temperature sensor must be attached in all dual fuel applications.

16. Thermidistat Dip Switch 1 should be set in the ON position for heat pump installations.

17. Thermidistat Dip Switch 2 should be set in the ON position for 2-speed compressor operation.

18. Thermidistat Configuration Option No. 10 "Dual Fuel Selection" must be turned on in all dual fuel applications.

19. To activate dehumidify feature on current style 58MVP variable-speed furnaces, a pilot duty, 24-v relay must be used.

20. To activate dehumidify feature on current style 58UHV,58UXV variable-speed 80% non-condensing furnaces, disconnect green

(dehum) wire from G on furnace control board and connect to dehumidify terminal dhu on thermidistat.

21. See Table 3—Airflow Selection for 58UHV,58UXV Furnaces.

22. See Table 4—Airflow Selection for 58MVP Furnaces.

23. See Table 5—Airflow Selection for FK4C or 40FKA Fan Coil.

24. Select Furnace Interface Option, Balance Point, and Defrost Time on 2-speed heat pump control board.

25. Thermidistat controls dual fuel operation; do not select Furnace Interface Option on 2-speed heat pump control board.

26. Dual fuel thermostat Dip Switch D should be set in the ON position for 2-speed compressor operation. This thermostat controls dual

fuel operation; do not select Furnace Interface Option on 2-speed heat pump control board.

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT

HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)

AIRFLOW SELECTOR

R1

H

AFS

A97466

13

Содержание 38YDA

Страница 1: ...rom improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to...

Страница 2: ...door operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating ambient in heating mode is 66 F Step 5 Elevate Unit Accu...

Страница 3: ...uct Data Sheet for factory approved indoor units Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or facto...

Страница 4: ...for 2 speed units Do not attempt to operate unit below 55 F in cooling mode or modify control system for low ambient operation Compressor dam age may occur Available electrical accessories include lat...

Страница 5: ...ate unit in a vacuum or at negative pressure Do not disable low pressure switch In scroll compressor applications Dome temperatures may be hot To prevent personal injury wear safety glasses protective...

Страница 6: ...LE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED HEAT PUMP See notes 7 8 9 and 11 W2 G W2 O R W3 R L H R1 COOL HEAT STAGE 1 COOL HEAT STAGE 2 24 VAC HOT Y Y2 A D A97498 R C C Y1 W3 O TYPICAL FAN COIL...

Страница 7: ...UMPER J2 JUMPER TWO SPEED HEAT PUMP See notes 7 8 9 11 and 23 DH Y1 Y1 W W1 O W2 Y1 W2 O W1 Y Y2 Y2 W2 W3 Y Y2 O W2 COOL HEAT STAGE 1 COOL HEAT STAGE 2 HEAT STAGE 3 RVS COOLING H A98628 R Y2 R Y2 C C...

Страница 8: ...FURNACE TWO SPEED HEAT PUMP See notes 7 9 11 14 and 24 W R Y1 R O W2 G L W3 Y H R1 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT K A98587 24 VAC HOT 24 VAC COMM HEAT STAGE 3 R C G W W1 Y Y2 R C RVS COOLING...

Страница 9: ...C Y2 W3 W2 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY See notes 7 11 14 15 16 17 18 and 25 N A OUTDOOR SENSOR CONNECTION Y Y2 HUM...

Страница 10: ...W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 FAN HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING 24 VAC HOT P A97497 24 VAC HOT 24 VAC COM HE...

Страница 11: ...CE WITH ICM BLOWER MOTOR TWO SPEED HEAT PUMP See notes 6 7 9 11 12 14 21 and 24 R Y1 R O G L W3 W W1 Y Y2 W2 Y1 COOL HEAT STAGE 2 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT W A97496 R C C W2 TWO STAGE VA...

Страница 12: ...3 W2 O C DHUM HUM B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 HEAT COOL STAGE 1 HEAT COOL STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y...

Страница 13: ...t pump MUST have a high pressure switch for dual fuel applications 15 Outdoor air temperature sensor must be attached in all dual fuel applications 16 Thermidistat Dip Switch 1 should be set in the ON...

Страница 14: ...w Selection for 58MVP Furnaces CFM 38YDA UNIT SIZE HIGH SPEED A C SETUP SWITCH POSITION FURNACE MODEL HEATING SIZE LOW SPEED CF SETUP SWITCH POSITION 060 080 100 A C 1 A C 2 A C 3 High Low High Low Hi...

Страница 15: ...ersects measured liquid service valve pressure 6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line temperature is higher than indicated or rec...

Страница 16: ...door coil heat and minimize the steam cloud effect SECOND STAGE LATCHING Mechanical thermostats operate with a staging differential of 2 F droop Carrier electronic thermostats are droopless meaning th...

Страница 17: ...ature The cycle terminates when coil thermistor reaches 80 F 5 or defrost period reaches a maximum of 10 minutes FURNACE INTERFACE This feature provides a heat pump lockout upon a demand for auxiliary...

Страница 18: ...appears at control board If a PTC trip occurs 3 times the control locks out outdoor unit operation and provides a malfunction signal at control PRESSURE SWITCH PROTECTION The outdoor unit is equipped...

Страница 19: ...s the resistance decreases A thermistor is used to sense outdoor ambient Refer to Fig 14 for resistance values versus temperature If outdoor ambient thermistor should fail a malfunction signal appears...

Страница 20: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalo...

Отзывы: