background image

LED FUNCTION LIGHTS

System control function LED indicator lights are available at
outdoor unit 2-speed control board. The indoor thermostat may
provide indicator signals for high- and low-speed operation,
system malfunction, and auxiliary heat (if equipped to do so). The
2-speed control board has an LED which provides signals for
several system operations. See Table 8 for LED functions and
definitions. Table 8 also provides the order of signal importance if
more than 1 signal should occur. If equipped and properly wired,
the signal to indoor thermostat is supplied by the low-voltage L
lead.

NOTE:

A signal (code) is not sent through the L lead to

thermostat unless a failure has occurred.

FACTORY DEFAULTS

Factory defaults have been provided in the event of failure of
ambient thermistor, outdoor coil thermistor, and/or furnace inter-
face jumper. Refer to Table 9 for default and function.

THREE-SEC TIME DELAY

Any time the control receives a 24-v input, such as Y1 or Y2, there
is a 3-sec time delay before control function is initiated. This helps
prevent nuisance trips from thermostat jiggling.

ONE-MINUTE SPEED CHANGE TIME DELAY

When compressor changes speeds from high to low or low to high,
there is a 1-minute time delay before compressor restarts. The
outdoor fan motor remains running.

FIVE-MINUTE TIME DELAY

The 2-speed control logic contains a 5-minute time delay that
prevents unit from short cycling after a thermostat off cycle or
power interruption. The unit can be forced to operate immediately

by momentarily touching a jumper between speed-up terminals of
control board. (See Fig. 9.) The speed-up feature does not bypass
any other function or time delay.

TWO-MINUTE LOW-SPEED MINIMUM

If unit has not operated within the past 30 minutes, upon the next
thermostat high- or low-speed demand, unit operates for a mini-
mum of 2 minutes in low speed.

CRANKCASE HEATER OPERATION

The 2-speed control energizes crankcase heater during unit’s off
cycle when outdoor ambient is below 75°F.

OUTDOOR FAN MOTOR OPERATION

The 2-speed control energizes outdoor fan any time compressor is
operating. The outdoor fan remains energized during the 1-minute
speed change time delay and if a pressure switch or positive
temperature coefficient (PTC) overload should trip.

After termination of a defrost cycle, the outdoor fan delays coming
on for 20 sec. This allows refrigerant system to recover outdoor
coil heat and minimize the "steam cloud" effect.

SECOND-STAGE LATCHING

Mechanical thermostats operate with a staging differential of 2°F
(droop). Carrier electronic thermostats are droopless, meaning that
they maintain room temperature at set point without latching
second stage. If system is installed with a mechanical thermostat or
second stage latching is desired, the following information applies.

During normal operation, the compressor operates at low speed to
satisfy first stage of indoor thermostat. If indoor thermostat
temperature increases 2 degrees, the compressor shifts into high-
speed operation. When indoor thermostat temperature is satisfied,
the compressor returns to low-speed, first-stage operation.

The installing technician can select high-speed compressor opera-
tion until first stage of indoor thermostat is satisfied. This
eliminates the temperature droop of indoor thermostat between
first- and second-stage operation and holds room temperature
closer to set point when load requirements are high. To select this
option, rotate the STAGE 2 LATCH potentiometer (pot) to desired
temperature. (See Fig. 10.) The pot is factory set at OFF; however,
a temperature of 85°, 90°, 95°, 100°, or 105°F can be selected. The
selected temperature is the outdoor temperature at which the
structure’s cooling load requires high-speed operation.

Unit high- and low-speed capacities should be plotted versus
cooling load (heat gain) of structure to accurately determine the
STAGE 2 LATCH temperature to be selected. Unit capacities

Table 7—Ambient Temperatures for High- and

Low-Speed Operation

UNIT SIZE

AMBIENT TEMPERATURE (°F)

High Speed

Low Speed

036

30 or less

31 or greater

048

33 or less

34 or greater

060

40 or less

41 or greater

Table 8—LED Control Function Light Code

CODE

DEFINITION

*

Constant flash

No pause

No demand

Stand by

9

1 flash

w/pause

Low-speed operation

8

2 flashes

w/pause

High-speed operation

7

3 flashes

w/pause

Outdoor ambient thermistor failure

6

4 flashes

w/pause

Outdoor coil thermistor failure

5

3 flashes

pause

4 flashes

Thermistor out of range†

4

5 flashes

w/pause

Pressure switch trip (LM1/LM2)

3

6 flashes

w/pause

Compressor PTC’s out of limit

2

Constant light

No pause

No flash

Board failure

1

* Function light signal order of importance in case of multiple signal request; 1
is most important.
† Check both thermistors to determine which is faulty.

Fig. 9—Two-Speed Control Board

A93568

LM1 LM2

DFT1 DFT2 T1

T2

S2

S1

PW2 PW1

P1

1

18

SPEED-UP

STAGE 2

LATCH

DEFROST

TIME

BALANCE

POINT

K7

ZONE

OFF

105

100

95

90

85

FURN INT

OFF

ON

45

40

35

30

25

20

10

15

90

30

50

16

Содержание 38YDA

Страница 1: ...rom improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to...

Страница 2: ...door operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating ambient in heating mode is 66 F Step 5 Elevate Unit Accu...

Страница 3: ...uct Data Sheet for factory approved indoor units Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or facto...

Страница 4: ...for 2 speed units Do not attempt to operate unit below 55 F in cooling mode or modify control system for low ambient operation Compressor dam age may occur Available electrical accessories include lat...

Страница 5: ...ate unit in a vacuum or at negative pressure Do not disable low pressure switch In scroll compressor applications Dome temperatures may be hot To prevent personal injury wear safety glasses protective...

Страница 6: ...LE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED HEAT PUMP See notes 7 8 9 and 11 W2 G W2 O R W3 R L H R1 COOL HEAT STAGE 1 COOL HEAT STAGE 2 24 VAC HOT Y Y2 A D A97498 R C C Y1 W3 O TYPICAL FAN COIL...

Страница 7: ...UMPER J2 JUMPER TWO SPEED HEAT PUMP See notes 7 8 9 11 and 23 DH Y1 Y1 W W1 O W2 Y1 W2 O W1 Y Y2 Y2 W2 W3 Y Y2 O W2 COOL HEAT STAGE 1 COOL HEAT STAGE 2 HEAT STAGE 3 RVS COOLING H A98628 R Y2 R Y2 C C...

Страница 8: ...FURNACE TWO SPEED HEAT PUMP See notes 7 9 11 14 and 24 W R Y1 R O W2 G L W3 Y H R1 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT K A98587 24 VAC HOT 24 VAC COMM HEAT STAGE 3 R C G W W1 Y Y2 R C RVS COOLING...

Страница 9: ...C Y2 W3 W2 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY See notes 7 11 14 15 16 17 18 and 25 N A OUTDOOR SENSOR CONNECTION Y Y2 HUM...

Страница 10: ...W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 FAN HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING 24 VAC HOT P A97497 24 VAC HOT 24 VAC COM HE...

Страница 11: ...CE WITH ICM BLOWER MOTOR TWO SPEED HEAT PUMP See notes 6 7 9 11 12 14 21 and 24 R Y1 R O G L W3 W W1 Y Y2 W2 Y1 COOL HEAT STAGE 2 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT W A97496 R C C W2 TWO STAGE VA...

Страница 12: ...3 W2 O C DHUM HUM B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 HEAT COOL STAGE 1 HEAT COOL STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y...

Страница 13: ...t pump MUST have a high pressure switch for dual fuel applications 15 Outdoor air temperature sensor must be attached in all dual fuel applications 16 Thermidistat Dip Switch 1 should be set in the ON...

Страница 14: ...w Selection for 58MVP Furnaces CFM 38YDA UNIT SIZE HIGH SPEED A C SETUP SWITCH POSITION FURNACE MODEL HEATING SIZE LOW SPEED CF SETUP SWITCH POSITION 060 080 100 A C 1 A C 2 A C 3 High Low High Low Hi...

Страница 15: ...ersects measured liquid service valve pressure 6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line temperature is higher than indicated or rec...

Страница 16: ...door coil heat and minimize the steam cloud effect SECOND STAGE LATCHING Mechanical thermostats operate with a staging differential of 2 F droop Carrier electronic thermostats are droopless meaning th...

Страница 17: ...ature The cycle terminates when coil thermistor reaches 80 F 5 or defrost period reaches a maximum of 10 minutes FURNACE INTERFACE This feature provides a heat pump lockout upon a demand for auxiliary...

Страница 18: ...appears at control board If a PTC trip occurs 3 times the control locks out outdoor unit operation and provides a malfunction signal at control PRESSURE SWITCH PROTECTION The outdoor unit is equipped...

Страница 19: ...s the resistance decreases A thermistor is used to sense outdoor ambient Refer to Fig 14 for resistance values versus temperature If outdoor ambient thermistor should fail a malfunction signal appears...

Страница 20: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalo...

Отзывы: