HANDLING THE UNIT —  To  avoid  overturning  the  unit,

the angle of inclination should not be more than 15 degrees

when carrying the unit

.

LIFTING UNIT WITH CABLES — Make  sure  the  lifting

cables can withstand the weight of the unit. Use 2 cables.

Make  sure  each  cable  is  at  least  26.3  feet  long  to  avoid

excess  tension  and  force  on  the  surfaces  of  the  unit.  To

avoid  damage  while  lifting  the  unit,  do  not  remove  the

original  packaging  or  unscrew  from  its  original  pallet.

Connect lifting cables diagonally as shown in Fig. 5 below.

Note  the  center  of  gravity  in  Fig.  5  below,  which  results

from the weight of the compressor and  other  components

located within the right-end section of the unit.

CONCRETE BASE REQUIREMENTS
• The unit’s base must be made of solid concrete. 
• Ensure that the base is level and that the weight of the

unit is distributed evenly. See Fig. below for reference.

Fig. 6 —Concrete Base

• Create  an  outlet  near  the  base  for  drainage.  Refer  to

Fig. 7 below for main drain connection.

Fig. 7 —Drain Connections

• Ensure the roof can handle the unit weight if mounted on

the roof.

Step  3  —  Connect  Refrigerant  Piping  and

Wiring — 

Refrigerant pipe connections are made on the side 

of the unit. Remove the L-shaped metal plate, and route piping 

through the exposed opening. Route power and control wiring 

through the two separate, adjacent knockouts. See Fig. for 

details.

INSULATION — Liquid  lines  and  suction  lines  must  be

insulated separately. Closed-cell insulation with fire-retardant

properties is recommended.
• For copper pipes less than 

1

/

2

 inch. OD, recommended

insulation thickness is 

1

/

2

 inch.

• For copper pipes equal to or greater than 

5

/

8

 inch. OD,

the recommended insulation thickness is 

3

/

4

 inch.

DANGER

DO NOT stand below unit while it is suspended in the air.

If unit were to fall, it may lead to personal injury or death.

Fig. 3 — Single Unit Installation

NOTE:

 All dimensions shown in inches.

Fig. 4 — Multiple or Parallel Unit Installation

NOTE:

 All dimensions shown in inches.

Fig. 5 — Lifting the Unit

Содержание 38VMA036HDS3-1

Страница 1: ...and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and the current editions of the National Electrical Code NEC ANSI NFPA American National Standards Institute National Fire Protection Association 70 In Canada refer to the current editions of the Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal wor...

Страница 2: ...omponent The system contains oil and refrigerant under pressure To remove a component wear protective gloves and goggles and proceed as follows a Shut off electrical power to unit b Recover refrigerant to relieve all pressure from the system using both high pressure and low pressure ports c Traces of vapor should be displaced with nitrogen and the work area should be well ventilated Refrigerant in...

Страница 3: ...0 Rated kBtu h 36 48 60 HEATING CAPACITY WITH NON DUCTED DUCTED INDOOR UNITS Nominal kBtu h 40 52 5 66 Rated kBtu h 40 52 5 66 ELECTRICAL CHARACTERISTICS WITH NON DUCTED INDOOR UNITS Cooling Power Consumption kW 3 10 4 60 6 10 EER Btu Wh 12 10 11 00 9 50 SEER Btu Wh 19 20 19 20 18 60 Heating Power Consumption kW 3 10 4 30 5 80 COP W W 3 62 3 42 3 19 HSPF Btu Wh 9 20 9 20 10 00 ELECTRICAL CHARACTER...

Страница 4: ...ainst hostile environments theft vandalism and debris on jobsite Do not allow foreign material to fall into unit Failure to do so may have serious adverse effects on unit operation Failure of any unit caused by deposits of foreign material inside unit will not be covered by manufacturer s warranty Some units and or job conditions may require some form of temporary covering during construction PREP...

Страница 5: ... Create an outlet near the base for drainage Refer to Fig 7 below for main drain connection Fig 7 Drain Connections Ensure the roof can handle the unit weight if mounted on the roof Step 3 Connect Refrigerant Piping and Wiring Refrigerant pipe connections are made on the side of the unit Remove the L shaped metal plate and route piping through the exposed opening Route power and control wiring thr...

Страница 6: ...tions Use pipe adapter Components Shipped with Unit Page 2 when main pipe diameter for suction line is 5 8 inch CAUTION During brazing keep nitrogen in pipes to avoid oxidation inside the pipes Use soapy water or refrigerant leak detector to verify every joint in the refrigeration piping Fig 8 Piping and Control Wiring Connections Fig 9 Piping and Control Wiring Locations 38VMH UNIT CAPACITY tons ...

Страница 7: ...or correct positioning of the joint Fig 12 Correct Branch Joint Positioning Install the branch joints properly to avoid oil accumulating in the system DESCRIPTION ALLOWABLE VALUE ft PIPES Piping Length Total Pipe Length 492 L1 L2 L3 L4 L5 L6 A B C D E Maximum Piping Length L Actual Length 296 L1 L3 L4 L5 L6 E Equivalent Length 328 First Branch to Farthest Indoor Unit 131 L3 L4 L5 L6 E Height Diffe...

Страница 8: ...e and carefully re lease liquid refrigerant into the suction service port If the total calculated charge amount is added completely to the system the charging process is finished Step 6 Complete Electrical Connections See Fig 14 for a diagram of the unit s internal power and control wiring PIPE SIZE ON LIQUID SIDE in REFRIGERANT TO BE ADDED PER FOOT lb ft 1 4 0 015 3 8 0 040 1 2 0 080 5 8 0 120 3 ...

Страница 9: ...9 Fig 14 Typical Wiring Diagram ...

Страница 10: ...rce Power entry is on the right side of the unit when facing the fan grille or front of the unit Terminals for field power supply are suitable for copper conductors See Fig 15 and 16 for power wiring Main Power Bring wires from the disconnect switch through the knockout hole at the bottom right corner of the unit to the control box CAUTION Operating the unit on improper supply voltage or with exce...

Страница 11: ...mes from the control board in the outdoor unit and does NOT require a separate source Use of 2 core stranded shielded cable is required Shield is used to protect the signal from interference The control wire between outdoor and indoor units is bus type See Fig 19 for communication wiring COMMUNICATION WIRING Communication wire must be wired as shown in Fig 8 and 19 Do not route communication wire ...

Страница 12: ...9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB HA HB HA HB HA HB HA HB HA HB HA HB NOTE Power from IDU NOTE 24 v AC Power Maximum wiring length L1 L3 3937 ft 18AWG 2 Core Stranded Shield L5 3937 ft 18AWG 2 Core Stranded Shield L6 L7 L8 L9 820 ft 18 AWG 2 Core Stranded Shield L10 L11 820 ft 18 AWG 2 C...

Страница 13: ...of error codes Table 10 List of Error Codes CAUTION NEVER CONNECT the main power source to the control or communication terminal block USE ANAPPROPRIATE SCREWDRIVER for tightening the terminal screws Do not over tighten the terminal screws Failure to follow these procedures may result in personal injury or damage to equipment ERROR CODE EXPLANATION E2 Communication error between indoor unit and ou...

Страница 14: ...utomatic addressing Cooling priority mode Non automatic addressing factory default First running priority mode Clear IDU address Heating mode only Fahrenheit temperature factory default Cooling mode only Celsius temperature ENC1 Function Definition factory use only ENC2 Function Definition For factory use only ODU network address dial up Only 0 7 used ...

Страница 15: ...on outdoor units are fully open If these valves are not fully open equipment damage may occur MAINTENANCE The following are recommended guidelines Jobsite conditions may say that maintenance schedule be performed more often than recommended here EVERY 3 MONTHS Check coil condition Clean the coil if necessary EVERY 6 MONTHS Follow the 3 month maintenance schedule In addition Check for and remove de...

Страница 16: ... to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 38VMH002 01 Printed in U S A Form 38VMH 1P 2SI Pg 16 01 20 Replaces 38VMH 1P 1SI Carrier Corporation 2020 ...

Отзывы: