Table 11 - Troubleshooting chart
Symptoms
Cause
Remedy
Unit does not start
No power supply
Connect power supply
Main switch open
Close switch
Low line voltage
Check voltage and remedy the deficiency
A protection has tripped
Reset
Contactor stuck open
Replace contactor
Seized compressor
Replace compressor
Unit starts and stops frequently
Defective compressor contactor
Replace contactor
Defective compressor
Replace compressor
Refrigerant losses
Check. Remove the charge. Repair leaks.
Evacuate. Recharge with refrigerant
Unit continuously cuts out at
Defective low pressurestat
Replace pressurestat
low pressure
Refrigerant losses
Check and add the necessary quantity
Indoor fan does not operate
Check fan motor
Unit continuously cuts out at
Defective high pressurestat
Replace pressurestat
high pressure
Refrigerant losses
Check and correct
Outdoor fan does not operate
Check fan motor
Abnormal system noise
Piping vibration
Support piping and check drainage
Noisy compressor
Check and change if necessary
Badly fitting panels
Install correctly
Water loss
Defective drainage connections
Check and tighten if necessary
Compressor loses oil
Leak in system
Repair leak
Order No. 13853-20, 12.07. Supersedes order No.: New
Manufactured by: ECO, Guadalajara, Spain.
Manufacturer reserves the right to change any product specifications without notice.
Printed in the Netherlands.
FINAL RECOMMENDATIONS
The unit you have purchased has undergone strict quality
control procedures before leaving the factory.
All components, including the control systems and electrical
equipment, etc., are certified by our Quality Control Depart-
ment, and tested under the harshest possible operating
conditions in our laboratories. However, after leaving the
factory, it is possible that one or more of these elements
may be damaged due to causes beyond our control. In such
an event,
the user should not work on any of the internal
components, or subject the unit to operating conditions
which are not specified in this manual,
since serious damage
may result and the guarantee would be invalidated. Repair
and maintenance work should always be left to the installer.
IMPORTANT: All recommendations concerning unit
installation are intended to be as a guideline. Qualified
technicians or installers must carry out the installation
correctly and in accordance with applicable local, national
and European standards and with the design conditions.
They should also comply with all applicable regulations
for air conditioning and refrigeration installations.
NOTE: The manufacturer does not accept responsibility
for any malfunctions resulting from misuse of the 38UQZ
and 40ALZ units, or from an incorrect installation and
the damage caused by this.