4

d)  If, when the unit is run, symptoms of loss of charge (for 

example, low pressure switch tripping or abnormally 
low cooling capacities) are detected, first conduct a 
leak test. For the latter all refrigerant must be removed 
from the circuit. Transfer the refrigerant to a storage 
tank and then clean the circuit as described earlier.

e)  Before adding the refrigerant charge proceed as follows:
 

Draw a vacuum in the refrigerant circuit until a 
pressure of 667 Pa (-7 mm Hg) has been reached 
for at least two hours. At a greater distance between 
units the period must be longer. 

the period of time 

of the vacuum is important.

 

Check that there are no refrigerant leaks. 

 

Continue to charge refrigerant as described below:

 

Total charge = unit charge plus additional charge per 
metre suction line and per metre liquid line.

 

The refrigerant charge for the 38UQZ and 40ALZ 
units is given in Table 1 - Physical Data.

 

For each metre of refrigerant connection line 
installed, refrigerant has to be added in accor-
dance with the table below for the liquid and gas 
lines:

Table 7 - Refrigerant charge (g/m)

Diameter

  

1/2”   5/8” 

3/4” 

7/8” 

1-1/8”  1-3/8”

Liquid line

 

75 

120 

180 

250 

420 

645

Suction line

 

14 

23 

34 

47 

81 

123

OIL RECHARgE

If any oil needs to be added to fill the siphons and above 
all when the total line length is high, use the same type and 
brand as used in the compressors.

START-UP

Necessary checks/precautions before start-up:
• 

Confirm that the electrical power source agrees with 
the unit nameplate rating.

• 

Ensure that the power connections between speed and 
thermostat have been made and correctly tightened.

• 

Check that there are no refrigerant leaks in the soldered 
refrigerant lines, and that the refrigerant and oil charges 
are correct.

• 

Check the 40ALZ drain connection and that the water 
is drained correctly.

• 

Ensure that the unit is level and well-supported.

• 

Check for proper fan rotation direction

• 

Check the condition of the ductwork in case damage 
has occurred during installation.

• 

The air filter should be clean and in place.

• 

All the panels should be fitted and firmly secured with 
the corresponding screws.

• 

Make sure that compressors float freely on the mount-
ing springs.

WARNING: The compressors are mounted on vibration 
isolators. Do not loosen or remove the support mounting 
bolts.

IMPORTANT: Actual start-up should only be done under 
the supervision of a qualified refrigeration mechanic.

Initial checks

With the unit in operation, ensure that the values shown 
on the high and low pressure gauges are within the normal 
limits. It is advisable to simulate unit shutdown due to high 
and low pressure, in order to make sure that the pressure-
stats work properly. To do so, proceed as follows with the 
unit operating in cooling mode:
• 

High pressure shutdown:

 Completely cover the outdoor 

air inlet, or disconnect the outdoor fan and motor. The 
unit should stop at a pressure of 844 kPa.

• 

Low pressure shutdown:

 Cover the indoor air inlet, or 

disconnect the indoor fan and motor. Observe the low 
pressure gauge. The unit should stop at a pressure of 
6 kPa.

The pressure switches are automatically reset. As this takes 
some time, the unit will stop, the pressures will equalise, and 
then the unit will be reset and will start up again.

Check that the motor and compressor consumptions are 
approximately the same as those shown in the fan perfor-
mance curves and in the cooling capacity tables for the unit 
operating conditions (indoor and outdoor temperatures, 
air flow and static pressures, based on the speed, etc.).

Содержание 38UQZ016

Страница 1: ...he Eurovent Certification Programme Products are as listed in the Eurovent Directory of Certified Products 38UQZ 016 020 024 40ALZ 016 020 024 Split System Air to Air Heat Pumps Installation Operation and Maintenance Instructions ...

Страница 2: ...ATION 14 38UQZ outdoor units 14 40ALZ indoor units 16 ELECTRICAL CONNECTIONS 19 REFRIGERANT LINE CONNECTIONS 20 Connection between units 20 Refrigerant piping design 21 Pipe diameter calculation procedure 21 REFRIGERANT CHARGE 23 OIL RECHARGE 24 START UP 24 Initial checks 24 UNIT COMPONENTS 25 DESCRIPTION OF UNIT PROTECTION DEVICES 25 OPERATING LIMITS 25 GENERAL MAINTENANCE 26 Servicing recommenda...

Страница 3: ...o C Entering air temp o C Leaving air temp o C Leaving air temp o C Pressure drop air kPa Pressure drop air kPa Discharge air pressure Pa Discharge air pressure Pa Fan motor input Ph 1 Volts Fan motor input Ph 1 Volts Ph 2 Volts Ph 2 Volts Ph 3 Volts Ph 3 Volts SAFETY DEVICE SETTING 38UQZ UNIT High pressure switch cut out kPa cut in kPa Low pressure switch cut out kPa cut in kPa Step controller cu...

Страница 4: ...C db Based on an outdoor air temperature of 6 C wb and an indoor air entering temperature of 21 C db The refrigerant charge is for the complete system 38UQZ and 40ALZ but excludes the refrigerant connection lines Table 2 Electrical data 38UQZ 40ALZ 016 020 024 Nominal supply V ph Hz 230 3 50 400 3 50 230 3 50 400 3 50 230 3 50 400 3 50 Voltage range V 207 253 360 440 207 253 360 440 207 253 360 44...

Страница 5: ... 5 8 4 Cable entry 5 Main disconnect switch 6 Control box 7 Front access panel 8 Side acces panel both sides 9 Heat echangers 0 Compressors Fans Fig 1 38UQZ dimensions mm Plan view When designing an installation always use up to date drawings available from your local Carrier office Side view Rear view ...

Страница 6: ...nt and right side view Detail A Electrical connections Refrigerant line connections Access panel Outlet Hot water coil connections accessory option Air inlet Standard drain ø 23 See detail A Rear and left side view Note The air discharge can be changed from horizontal to vertical see page 17 When designing an installation always use up to date drawings available from your local Carrier office Dime...

Страница 7: ...8UQZ 016 024 Required service space for the removal of the air filter and the fans in case of a breakdown Clearance should be the same as the unit width 1000 500 500 600 600 40ALZ all sizes Air filter removal Air filter removal 500 ...

Страница 8: ...oordinates mm approx 38UQZ 016 024 40ALZ all sizes 3 38UQZ 016 020 024 XG 1060 1060 1070 YG 300 340 380 ZG 280 320 400 Measured from point 3 40ALZ 016 020 024 XG 1620 1625 1870 YG 230 230 230 ZG 520 520 520 Measured from point 3 ...

Страница 9: ...ion kg approx 38UQZ 016 024 40ALZ Air filters 3 1 5 4 6 Point 38UQZ 016 020 024 1 180 210 221 2 180 210 221 3 29 33 36 4 29 33 36 5 31 34 38 6 31 34 38 Point 40ALZ 016 020 024 1 43 46 53 2 47 51 53 3 100 104 110 4 100 104 109 ...

Страница 10: ...er input kW 40ALZ 016 high pressure option Available static pressure Pa Air flow l s Power input kW Indoor fan speed Curve Pulley position Standard r s High pressure option r s 0 Closed 17 78 21 42 1 1 17 21 20 74 2 2 16 51 19 89 3 3 15 88 19 14 4 4 15 23 18 35 Factory setting 2 16 51 19 89 ...

Страница 11: ...pressure option r s 0 Closed 20 73 24 11 1 1 20 15 23 43 2 2 19 62 22 82 3 3 19 02 22 12 4 4 18 48 21 49 Factory setting 2 5 19 32 22 47 Available static pressure Pa Available static pressure Pa Air flow l s Air flow l s Power input kW Power input kW 40ALZ 020 high pressure option ...

Страница 12: ... pressure option r s 0 Closed 20 42 23 67 1 1 19 91 23 08 2 2 19 37 22 45 3 3 18 87 21 87 4 4 18 28 21 19 Factory setting 4 18 28 21 19 Available static pressure Pa Available static pressure Pa Power input kW Power input kW Air flow l s Air flow l s 40ALZ 024 high pressure option ...

Страница 13: ...equipment damage make sure disconnects are open before electrical connections are made If this action is not taken personal injury may occur Before performing service or maintenance operations on the unit turn off the main power switch to the outdoor unit 38UQZ Electrical shock could cause personal injury During unit operation some of the refrigerant circuit elements could reach a temperature in e...

Страница 14: ...and return air For minimum clearances between the units and walls or roofs see Figs 8 9 and 10 Fig 8 38UQZ 016 024 Rigging hook FRONT VIEW PLAN VIEW Supply air Return air 38UQZ models Fig 7 FLOOR Return air ROOF Control box Return air Table 3 Minimum clearances mm A C 500 Free There must not be any obstacle ceiling or roof near the unit If several units are installed close to each other in the sam...

Страница 15: ...nimum clearances between units mm 38UQZ A B C 016 024 500 700 500 Installation on the ground 38UQZ units can be positioned on the floor of a patio on the ground or on a lawn If installed on the ground or on the lawn they should be mounted on a 100 mm high concrete base that is 100 mm larger than the base unit on all four sides Return air Return air Return air Return air PLAN VIEW PLAN VIEW Return ...

Страница 16: ...ANT Units must be installed in accordance with applicable local national and European installation and safety standards and regulations 40ALZ indoor units These units have been designed for indoor installation connected to supply and return air ducts When selecting the installation site observe the following points Ensure that the condensate water collected in the drain pan is correctly evacuated ...

Страница 17: ...itioning unit air discharge 40ALZ Supply air Return air Return air Supply air Return air Supply air Return air Return air Supply air Legend 1 Side access panel 6 Drive belt s 2 Rear discharge panel 7 Roof panel 3 Top panel 8 Fan pulley 4 Angle iron to attach fan to base 9 Base 5 U bracket Condensate drainage 40ALZ units are supplied with a condensate drain pan with two drain pipes outside diameter...

Страница 18: ...aft and align with the motor using a ruler making sure that it is parallel to the belt see Fig 21 2 Tighten the fan pulley setscrews To adjust the belt tension loosen the motor mounting plate bolts and slide the motor mounting plate until the belt is tight 3 Belt tension see Fig 22 The minimum belt deflection is 10 mm when the force shown in Fig 22 is applied Fig 22 Legend 1 Fixed flange 2 Setscre...

Страница 19: ...gram Voltage to the unit must be within 10 of the nominal given in the electrical data table with a maximum phase imbalance of 2 Contact your local power company for correction of an incorrect line voltage Take special care when making the earth connection This is the first cable to be connected and it must be longer than the live cables Operation of the unit on improper line voltage consti tutes ...

Страница 20: ...am accom panying the unit and the thermostat installation instruction NOTE Refer to the applicable thermostat installation manuals for each model refrigerant line connections Connection between units The 38UQZ outdoor units must be connected with the 40ALZ indoor units with refrigerant grade copper pipes for correct operation For each compressor in the 38UQZ outdoor unit a pipe for refrigerant gas...

Страница 21: ...d ascen ding in heat pump mode and is calculated as explained later Indoor unit above the outdoor unit Fig 26 For heat pump units this type of installation limits the height difference between the units and the discharge line speed is approximately half of the suction line speed The suction line flow is descending in cooling mode so that the oil flow is not so problematic The most unfavourable con...

Страница 22: ...nd it is checked if the diameter applies to the suction line if this is descending The suction and discharge lines must comply with the following points Maximum admissible pressure loss for the total length 20 kPa 3 psi Minimum velocity in ascending sections 6 m s Horizontal or descending sections the velocity can be between 4 and 6 m s Maximum line velocity 15 m s The horizontal sections must hav...

Страница 23: ...ting the refrigerant lines carefully follow the steps below Remove the nitrogen holding charge from the refrige rant circuits Use silver alloy rod for soldering purposes and ensure that this work is done in a nitrogen atmosphere Check the pipes for leaks before welding the joint to the unit pipes Once these connections have been made carry out another leak test refrigerant charge The 38UQZ and 40A...

Страница 24: ...dered refrigerant lines and that the refrigerant and oil charges are correct Check the 40ALZ drain connection and that the water is drained correctly Ensure that the unit is level and well supported Check for proper fan rotation direction Check the condition of the ductwork in case damage has occurred during installation The air filter should be clean and in place All the panels should be fitted a...

Страница 25: ...n the 38UQZ unit control box High pressurestat This protects the unit against excessive condensing pressure The high pressurestat has factory fixed non adjustable settings To check see section Initial checks Low pressurestat This protects the 40ALZ units against excessive low pressure in the evaporator or in the refri gerant lines It is not operational in heat pump mode The low pressurestat has fa...

Страница 26: ...compressor and the unit Ensure that no faulty contacts exist in the terminal blocks contactor boards etc Make sure that all the electrical connections are properly tightened and that all the electrical components contactors relays etc are firmly secured to the corresponding rails Pay special attention to the condition of the connecting cables between the control elements and the electrical box and...

Страница 27: ...rwise the new compressor will also be damaged In order to remove the acid proceed as follows a Thoroughly clean the refrigerant circuit using dry nitrogen in the opposite direction to the refrigerant flow or another cleaning element Also carefully clean the separate parts of the refrigerant circuit Install anti acid filters in the liquid line Solder the refrigerant lines Evacuate the lines and cha...

Страница 28: ...Spain Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands FINAL RECOMMENDATIONS The unit you have purchased has undergone strict quality control procedures before leaving the factory All components including the control systems and electrical equipment etc are certified by our Quality Control Depart ment and tested under the harshest possi...

Отзывы: