background image

Table 2 — Electrical Data

OUTDOOR

UNIT 38QR

V-PH-HZ

OPERATIONAL

VOLTAGE*

COMPR

FAN
FLA

MCA

MAX FUSE†

OR HACR TYPE

CKT BKR AMPS

Max

Min

LRA

RLA

018C

208/230-1-60

253

187

49.0

8.9

.70

11.8

20

024C

61.0

10.9

.70

14.3

25

030C

76.0

13.5

.70

17.6

30

036C

90.5

17.9

.70

23.1

40

048C

110.0

22.4

1.45

29.5

50

060C

135.0

27.6

1.50

36.0

60

036C

208/230-3-60

253

187

66.0

11.2

1.45

15.5

20

048C

92.0

14.7

1.45

19.8

40

060C

105.0

17.7

1.50

23.6

45

036C

460-3-60

506

414

35.0

5.8

.80

8.1

15

048C

46.0

6.7

.80

9.2

15

060C

55.0

10.4

.83

13.8

20

LEGEND

FLA

— Full Load Amps

HACR — Heating, Air Conditioning, Refrigeration
LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps per NEC Section 430-24

NEC

— National Electrical Code

RLA

— Rated Load Amps (Compressor)

*Permissible limits of the voltage range at which unit will operate sat-

isfactorily.

†Time-delay fuse.
NOTES:
1. Control circuit is 24 v on all units and requires an external power

source.

2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

4. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.

Use the following formula to determine

the % voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Filter Drier —

Whenever the moisture liquid indicator

shows presence of moisture, replace the filter drier. Refer to
Carrier Standard Service Techniques Manual, Chapter 1, Re-
frigerants, for details on servicing filter driers.

High-Pressure Switch —

This switch, located on dis-

charge line, protects against high discharge pressures caused
by such events as overcharge, outdoor-fan motor failure, sys-
tem restriction, etc. It opens on pressure rise at about
426 psi. If system pressures go above this setting during ab-
normal conditions, the switch opens.

DO NOT attempt to simulate the system abnormalities
— high pressures pose a serious safety hazard.

High-pressure switch is also checked with an ohmmeter

similar to checking low-pressure switch. If system pressure
is below 426 psi, switch shows continuity.

Low-Pressure Switch —

This switch, mounted on

the suction line, has fixed, non-adjustable settings. The switch
is bypassed during defrost, and also for the first 2 minutes of
heating operation after defrost, by means of a time-delay

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

= 457

3

Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine % voltage imbalance.

% Voltage Imbalance = 100 x

7

= 1.53%

457

This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local electric utility com-
pany immediately.

relay. This prevents nuisance tripping of the low-pressure
switch.
To check pressure switch, attach pressure gage to suction
service valve gage port. Slowly close liquid shutoff valve
and allow compressor to pump down. Do not allow com-
pressor to pump down below 2 psig. Compressor should shut
down when suction pressure drops to cutout pressure in
Table 1, and should restart when pressure builds up to cut-in
pressure shown after CLO (compressor lockout switch) has
been reset and accessory Time Guard® device has com-
pleted its timing cycle.

Crankcase Heater —

Heater prevents refrigerant mi-

gration and compressor oil dilution during shutdown when
compressor is not operating. If crankcase heater is deener-
gized for more than 6 hours, both compressor service valves
must be closed.

Crankcase heaters come in 2 basic types: wraparound (bel-

lyband) type that is wrapped externally around compressor
shell, and insertion type that is inserted into compressor oil
well in shell of compressor.

Crankcase heater is powered by high-voltage power of unit.

It is connected across the line side of the contactor and op-
erates continually. Use extreme caution when troubleshoot-
ing this device with power on.

8

Содержание 38QR018C-060C

Страница 1: ...gloves Use quenching cloth for brazing operations Have fire ex tinguisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC for special insta...

Страница 2: ...6C 3 7 sq ft 34 m2 5 Do not use screws longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR018C 154 70 13 329 5 8 15 88 3 8 9 53 38QR024C 167 76 38QR030C 180...

Страница 3: ...longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR036C 249 113 13 11 16 28 97 7 8 22 22 3 8 9 53 38QR048C 252 114 1311 16 28 97 7 8 22 22 3 8 9 53 38QR060C...

Страница 4: ...s should be used and fastened through slots pro vided in unit mounting feet MOUNTING ON ROOF Mount unit on a level platform or frame at least 6 in above roof surface Isolate unit and tubing from struc...

Страница 5: ...through piping while brazing to prevent formation of copper oxide To avoid damage while brazing service valves should be wrapped with a heat sinking material such as a wet cloth When brazing tubing s...

Страница 6: ...unit in system where voltage may fluctuate above or below permissible limits See Table 2 for recommended fuse sizes When making electrical connections provide clearance at unit for refrig erant pipin...

Страница 7: ...meter or continuity tester If necessary refer to Carrier Stand ard System Techniques Manual Chapter 2 for complete information Pumpdown Procedure The system may be pumped down in order to make repairs...

Страница 8: ...opens DO NOT attempt to simulate the system abnormalities high pressures pose a serious safety hazard High pressure switch is also checked with an ohmmeter similar to checking low pressure switch If...

Страница 9: ...pts the nor mal system heating operation to defrost the outdoor coil if the coil saturated suction temperature indicates freezing temperatures Defrost control board can be field set to check need for...

Страница 10: ...wet bulb temperature with a sling psychrometer 6 Refer to Table 3 Find air temperature entering outdoor coil and wet bulb temperature entering indoor coil At this intersection note the superheat temp...

Страница 11: ...of Table 5 Heating Operation Pressure Table Fixed Restrictor High Pressure at Suction Valve Low Pressure at Liquid Valve Suction Pressure at Compressor UNIT 38QR INDOOR DRY BULB TEMP F OUTDOOR TEMPERA...

Страница 12: ...HOOTING CHART HEATING CYCLE LEGEND NC Normally Closed ODT Outdoor Thermostat NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting m...

Страница 13: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND NC Normally Closed NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual 13...

Страница 14: ......

Страница 15: ......

Страница 16: ...acturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 111 Catalog No 563 882 Printed in U S A...

Отзывы: