FILE NO. SVM-07018
– 67 –
White
Black
Red
10-8-5. Outdoor unit
1
Compressor
(Model : DA89X1C-23FZ)
2
Outdoor fan motor
(Model : WLF-240-30A-1)
3
Compressor thermo. Bimetal
type (Model : PW - 2AL)
4
Outdoor temperature sensor
(TO), outdoor heat exchanger
temperature sensor (TE)
No.
Part name
Checking procedure
Measure the resistance value of each winding by using the tester.
Under 20°C
Measure the resistance value of winding by using the tester.
For details, refer to Section 10-9.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the
tester. (Normal temperature)
TGa : Heat pump model only.
TO, TE : Refer to the TA, TC characteristic table in Indoor (Refer to
Table 10-8-3, No.1).
Position
Resistance value
Red - White
White - Black 0.51 to 0.57
Ω
Black - Red
Under 20°C
1
Red
Black
White
4
2
5
3
6
Red
Black White
1 : White 4 :
−
2 :
−
5 :
−
3 : Red 6 : Black
Position
Resistance value
Black - Red ~ 237
Ω
Black - White ~ 380
Ω