
FILE NO. SVM-10036
18
-
-
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-
3-10 and Table 7-3-2.
7-3-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-
3-11. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the
RESET button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-
3-11
* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc
≥
24, A is 24, and when Tsc < 24, A is Tsc
Tsc: Set value
H
Line-approximate
H and SUL with Tc.
SUL
Stop
46
46
Tc
34
45
45
33
33
33
21
32
32
20
*A+0 *A+0 *A+0
*A-8 *A-8 *A-8
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
Fig. 7-3-10 Cold draft preventing control
Table 7-3-2
Fan
*5
*6
speed
Starting period
Stabilized period
AUTO
•
Up until 12 minutes
passed after starting
the unit
•
From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual
•
Room temperature
(L – H)
< Preset temperature
–4°C
•
From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
•
25 minutes or more
passed after starting
the unit
•
Room temperature
Preset temperature
–3.5°C
(Room temp.)
−
(Preset temp.)
0
°C
Cooling operation
Fan only operation
-1
Fig. 7-3-11
Heating operation