– 9 –
FILE NO. SVM-05003
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No.
Parts name
Type
Specifications
1 Fan motor (for indoor)
SKF
-2
2
0-20-4A-1 AC Motor with 1
50
°
C thermo fuse
2
Thermo sensor (TA-sensor)
———
10k
Ω
at 25
°
C
3
Micro Power Module (M01)
µ
RM1260V
4 Microcontroller unit (IC30) TMP87CM40AN-
5CK9
5
Heat exchanger sensor
———
10k
Ω
at 25
°
C
(TC-sensor)
6
Line filter (L01)
LC*SS11V-06270
27mH, 600mA
7
Bridge rectifier (DB01)
D3SBA60
4A, 600V
8 Capacitor (C
63
) KMH400VSSN47M22S 47
µ
F, 400V
9
Fuse (F01)
TSCR6.3A
T6.3A, 250VAC
10
Varistor (R21, R22)
15G561K
560V
11
Resistor (R01)
RF-2TK5R6
5.6
Ω
, 2W
12 Louver motor
MP24Z
12VDC
13 Relay (Comp., RY01)
DI1D
Rating 25A/AC250V, 3-48VDC
14
15
Relay (Fan, RY03)
Relay (Solenoide, RY04)
G5NB-1A
G5NB-1A
Rating 3A/AC250V, 12VDC
Rating 3A/AC250V, 12VDC
4-2. Outdoor Unit (38HNR012-713)
No.
Parts name
Type
Specifications
Output (Rated) 1100W, 2 poles, 1 phase, 220 – 240V, 50Hz
1 Compressor
PH225X2C-4FT
Winding resistance (
Ω
) C-R C-S
(at 20
°
C)
2.35
3.22
Output (Rated) 30W, 6 poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) HF-240-
42A
Winding resistance (
Ω
) Red-Black White-Black
(at 20 C) 176.2 290.5
Running capacitor
3
DS451155BPQC AC 450V, 1.5
µ
F
(for fan motor)
4
Running capacitor
DS371356CPNB AC 370V, 35
µ
F
(for compressor)
5
Solenoid coil
VHV-01A J503C1 AC 220
−
240V, 50Hz
(for 4Way valve)