If a field-supplied control power source is needed when
adding solenoid, wiring must comply with local codes and
NEC requirements.

1. Remove coil liquid connection cap and discard.

2. Mount solenoid valve on liquid tube, making sure valve flow

arrow points toward indoor coil. Mount valve in any position
except valve body at top and electric coil at bottom. (See Fig.
2.) The solenoid valve is to be installed a maximum of 2 ft
from indoor coil.

To avoid valve damage while brazing, valve must be wrapped
with a heat-sinking material such as a wet cloth

3. Braze valve onto end of liquid tube using silver bearing or

non-silver bearing brazing material. Consult local code re-
quirements.

4. Braze flare adapter onto outlet end of solenoid valve.

5. Wire solenoid coil into system control circuit.

Fig. 2—Solenoid Valve Installation

A87044

ELECTRICAL JUNCTION

ELECTRICAL COIL

VALVE

FLOW ARROW

STRAIGHT  

3

/

8

 

 IN. STUD

NOTE: System flow direction

must match arrow on
bottom of body.