APPENDIX A
AIR CONDITIONER AND HEAT PUMP
WITH PURON
®
—
QUICK REFERENCE
GUIDE
S
Puron
®
(R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are
designed to operate with Puron
®
.
S
Puron
®
refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400
psig, DOT 4BA400 or DOT BW400.
S
Puron
®
systems should be charged with liquid
refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with
compressor operating.
S
Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
S
Use hoses with 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC
refrigerant.
S
Puron
®
, as with other HFCs, is only compatible with
POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
S
Do not install a suction-line filter drier in liquid-line.
S
POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
S
POE oils may cause damage to certain plastics and
roofing materials.
S
Wrap all filter driers and service valves with wet cloth
when brazing.
S
A factory approved, liquid-line filter drier is required on
every unit.
S
Do not use an R-22 TXV.
S
If indoor unit is equipped with a TXV, it must be
changed to a Puron
®
TXV.
S
Never open system to atmosphere while it is under a
vacuum.
S
When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
S
Always replace filter drier after opening system for
service.
S
Do not vent Puron
®
into the atmosphere.
S
Do not use capillary tube coils.
S
Observe all
warnings
,
cautions
, and
bold
text.
S
All Puron
®
heat pumps must have indoor TXV.
S
Do not leave Puron
®
suction line driers in place for
more than 72 hours.
APPENDIX B
WIRING DIAGRAM LIST
38AUQ
Size
Electrical Characteristics
Diagram Number
*16
208/230-3-60
Power:
38AU500571
Control: 38AU500890
460-3-60
Power:
38AU500572
Control: 38AU500890
575-3-60
Power:
38AU500573
Control: 38AU500890
*25
208/230-3-60
Power:
38AU500172
Control: 38AU500890
460-3-60
Power:
38AU500173
Control: 38AU500890
575-3-60
Power:
38AU500174
Control: 38AU500890
38A
U
Q
Содержание 38AUQ 16 Series
Страница 4: ...4 C10675 Fig 2 38AUQ 25 Unit Dimensions 38AUQ...
Страница 19: ...19 C10784 Fig 16 38AUQ 16 Charging Chart 38AUQ...
Страница 20: ...20 C10785 Fig 17 38AUQ 25 Charging Chart 38AUQ...
Страница 21: ...21 C10786 Fig 18 38AUQ 16 Power Schematic 208 230 3 60 shown 38AUQ...
Страница 22: ...22 C10787 Fig 19 38AUQ 25 Power Schematic 208 230 3 60 shown 38AUQ...
Страница 23: ...23 C10788 Fig 20 38AUQ 16 25 Control Schematic 38AUQ...
Страница 41: ...41 C10363 Fig 35 Wind Baffles Fabrication 38AUQ...
Страница 42: ...42 C10366 Fig 36 15 Ton Wind Baffle Brackets Fabrication 38AUQ...
Страница 43: ...43 RIGHT BACK LEFT FRONT BOTTOM BRACKET TOP BRACKETS C10367 Fig 37 Wind Baffle Installation 15 Ton Units 38AUQ...
Страница 44: ...44 RIGHT BACK LEFT FRONT C10368 Fig 38 Wind Baffle Installation 20 Ton Units 38AUQ...
Страница 45: ...45 38AUQ...