![Carrier 38AUQ 16 Series Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/carrier/38auq-16-series/38auq-16-series_installation-start-up-and-service-instructions-manual_2563136016.webp)
16
Table 7 – Electrical Data — 38AUQ*15--25 60 Hz Units
UNIT
SIZE
38AUQ
NOMINAL
POWER
SUPPLY
VOLTAGE
RANGE
COMPRESSOR
NO C.O. or UNPWRD C.O.
No. 1
No. 2
OFM
POWER SUPPLY
DISCONNECT SIZE
V---Ph---Hz
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
MCA
FUSE or
HACR
BRKR
FLA
LRA
*16
208/230---3---60
187
253
25.0
164
25.0
164
3
1.5
60.8/60.8
80/80
63/63
337/337
460---3---60
414
506
12.2
100
12.2
100
3
0.8
29.9
40
31
206
575---3---60
518
633
9.7
78
9.7
78
3
0.7
23.9
30
2
162
*25
208/230---3---60
187
253
30.1
225
30.1
225
4
1.5
73.7/73.7
100/100
76/76
462/462
460---3---60
414
506
16.7
114
16.7
114
4
0.8
40.8
50
42
236
575---3---60
518
633
12.2
80
12.2
80
4
0.7
30.3
40
31
168
UNIT
SIZE
38AUQ
NOMINAL
POWER
SUPPLY
VOLTAGE
RANGE
COMPRESSOR
w/ PWRD C.O.
No. 1
No. 2
OFM
POWER SUPPLY
DISCONNECT SIZE
V---Ph---Hz
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
MCA
FUSE or
HACR
BRKR
FLA
LRA
*16
208/230---3---60
187
253
25.0
164
25.0
164
3
1.5
65.6/65.6
90/90
68/68
342/342
460---3---60
414
506
12.2
100
12.2
100
3
0.8
32.1
40
33
208
575---3---60
518
633
9.7
78
9.7
78
3
0.7
25.6
30
27
164
*25
208/230---3---60
187
253
30.1
225
30.1
225
4
1.5
78.5/78.5
100/100
82/82
467/467
460---3---60
414
506
16.7
114
16.7
114
4
0.8
43
50
45
238
575---3---60
518
633
12.2
80
12.2
80
4
0.7
32
40
33
170
Legend and Notes for Table 10
LEGEND:
BRKR
--- Circuit breaker
CO
--- Convenient outlet
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
Protection
NEC
--- National Electrical Code
PWRD CO
--- Powered convenient outlet
RLA
--- Rated Load Amps
UNPWR CO
--- Unpowered convenient outlet
NOTES
:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. The MCA values are calculated in accordance with The NEC.
Article 440.
3. Motor RLA and LRA values are established in accordance
with Underwriters’ Laboratories (UL). Standard 1995.
4. The 575---v units are UL, Canada---listed only.
5.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
Example: Supply voltage is 230-3-60
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
3
3
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT
: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
38A
U
Q
Содержание 38AUQ 16 Series
Страница 4: ...4 C10675 Fig 2 38AUQ 25 Unit Dimensions 38AUQ...
Страница 19: ...19 C10784 Fig 16 38AUQ 16 Charging Chart 38AUQ...
Страница 20: ...20 C10785 Fig 17 38AUQ 25 Charging Chart 38AUQ...
Страница 21: ...21 C10786 Fig 18 38AUQ 16 Power Schematic 208 230 3 60 shown 38AUQ...
Страница 22: ...22 C10787 Fig 19 38AUQ 25 Power Schematic 208 230 3 60 shown 38AUQ...
Страница 23: ...23 C10788 Fig 20 38AUQ 16 25 Control Schematic 38AUQ...
Страница 41: ...41 C10363 Fig 35 Wind Baffles Fabrication 38AUQ...
Страница 42: ...42 C10366 Fig 36 15 Ton Wind Baffle Brackets Fabrication 38AUQ...
Страница 43: ...43 RIGHT BACK LEFT FRONT BOTTOM BRACKET TOP BRACKETS C10367 Fig 37 Wind Baffle Installation 15 Ton Units 38AUQ...
Страница 44: ...44 RIGHT BACK LEFT FRONT C10368 Fig 38 Wind Baffle Installation 20 Ton Units 38AUQ...
Страница 45: ...45 38AUQ...