PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this caution may result in personal

injury or equipment damage.
Only approved cleaning is recommended.

CAUTION

!

Routine Cleaning of Indoor Coil Surfaces —

Periodic cleaning with Totaline

®

environmentally sound

coil cleaner is essential to extend the life of coils. This

cleaner

is

available

from

Carrier

Replacement

Components Division as part number P902-0301 for one

gallon container, and part number P902-0305 for a 5

gallon container. It is recommended that all coils,

including standard aluminum, pre-coated, copper/copper

or E-coated coils be cleaned with the Totaline

environmentally sound coil cleaner as described below.

Coil cleaning should be part of the unit’s regularly

scheduled maintenance procedures to ensure long life of

the coil. Failure to clean the coils may result in reduced

durability in the environment.

Avoid the use of:

S

coil brighteners

S

acid cleaning prior to painting

S

high pressure washers

S

poor quality water for cleaning

Totaline

environmentally

sound

coil

cleaner

is

nonflammable, hypoallergenic, non bacterial, and a

USDA accepted biodegradable agent that will not harm

the coil or surrounding components such as electrical

wiring, painted metal surfaces, or insulation. Use of

non-recommended coil cleaners is strongly discouraged

since coil and unit durability could be affected.

Totaline Environmentally Sound Coil Cleaner

Application Equipment:

S

2

1

/

2

gallon garden sprayer

S

Water rinse with low velocity spray nozzle

UNIT DAMAGE HAZARD

Failure to follow this caution may result in corrosion

and damage to the unit .
Harsh chemicals, household bleach or acid or basic

cleaners should not be used to clean outdoor or indoor

coils of any kind. These cleaners can be very difficult

to rinse out of the coil and can accelerate corrosion at

the fin/tube interface where dissimilar materials are in

contact. If there is dirt below the surface ot the coil,

use the Totaline environmentally sound coil cleaner as

described above.

CAUTION

!

UNIT RELIABILTY HAZARD

Failure to follow this caution may result in reduced

unit performance .
High velocity water from a pressure washer, garden

hose, or compressed air should never be used to clean

a coil. The force of the water or air jet will bend the

fin edges and increase airside pressure drop.

CAUTION

!

Totaline Environmentally Sound Coil Cleaner

Application Instructions:
NOTE

: Proper eye protection such as safety glasses is

recommended during mixing and application.

1. Turn off unit power.
2. Remove screws holding rear corner post and top cover

in place. Pivot top cover up 12 to 18 inches (305 to 457

mm) and support with a rigid support. See Fig. 32.

C10216

Fig. 32 -- Pivot and Support Top Cover

3. Remove all surface loaded fibers and dirt with a vacu-

um cleaner. If a vacuum cleaner is not available, a

soft non-metallic bristle brush may be used. In either

case, the tool should be applied in the direction of the

fins. Coil surfaces can be easily damaged (fin edges

can be easily bent over and damage to the coating of

a protected coil) if the tool is applied across the fins.

NOTE

: Use of a water stream, such as a garden hose,

against surface loaded coil will drive the fibers and dirt
into the coil, making cleaning efforts more difficult.
Surface loaded fibers must be completely removed prior

to using low velocity clean water rinse.

4. Using a low velocity garden hose thoroughly wet

finned surfaces with clean water. Be careful not to

bend the fins.

38A

U

Q

Содержание 38AUQ 16 Series

Страница 1: ...zer 24 Heating 24 Defrost Cycle 24 Supplemental Heating Emergency Heating 25 Cooling and Heating Shutdown 25 ROUTINE SYSTEM MAINTENANCE 25 Quarterly Inspection and 30 days after initial start 25 SERVI...

Страница 2: ...efrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZAR...

Страница 3: ...structions in this installation manual 7 Operate the system for 10 hr Monitor the pressure drop across the suction line filter drier If pressure drop exceeds 3 psig 21kPa replace suction line and liq...

Страница 4: ...4 C10675 Fig 2 38AUQ 25 Unit Dimensions 38AUQ...

Страница 5: ...psig 27 44 27 44 COMPRESSOR Model ZP83 2 ZP103 2 Oil Charge A B oz 60 110 Speed RPM 3500 3500 OUTDOOR COIL Material Al Cu Coil Type Round Tube Plate Fin RTPF Rows Fins Per Inch FPI 2 17 Total Face Are...

Страница 6: ...PRESSOR Model ZP83 2 ZP103 2 Oil Charge A B L 1 7 3 2 Speed r s 58 58 OUTDOOR COIL Material Al Cu Coil Type Round Tube Plate Fin RTPF Rows Fins Per Meter Fins m 2 17 Total Face Area m2 4 4 4 6 OUTDOOR...

Страница 7: ...a x e T P T E G n o i t a c o l g n i r u t c a f u n a M 5 r e b m u n l a i t n e u q e S 6 10 1 2 3 4 5 6 7 8 9 10 4 8 1 0 G 1 2 3 4 5 POSITION NUMBER TYPICAL Year of manufacture 10 2010 3 4 C10799...

Страница 8: ...and above S The unit may be mounted on a level pad directly on the base channels or mounted on raised pads at support points See Tables 1A and 1B for unit operating weights See Figs 1 and 2 for weight...

Страница 9: ...oor units check to ensure that the separation is within allowable limits Relocate equipment if necessary Provide Safety Relief If local codes dictate an additional safety relief device purchase locall...

Страница 10: ...t low outdoor ambient temperatures Wire the solenoid according to the unit label diagram UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage Failure to use a solenoid valv...

Страница 11: ...exposed to outdoor conditions Closed cell foam insulation with a thermal conductivity of 0 28 Btu S in ft2 S h S F 0 04 W m S C Evacuation Dehydration Evacuate and dehydrate the connected refrigerati...

Страница 12: ...moving the black wire with the 1 4 in female spade connector from the 230 v connection and moving it to the 208 v 1 4 in male terminal on the primary side of the transformer Refer to unit label diagr...

Страница 13: ...a source elsewhere in the building Observe national and local codes when selecting wire size fuse or breaker requirements and disconnect switch size and location Route 125 v power supply conductors in...

Страница 14: ...late as shown in Fig 12 Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover Check for full closing and latching RECEPTACLE NOT INCLUDED COVER WHILE IN USE...

Страница 15: ...for additional features which might require additional conductors in the cable For wire runs up to 50 ft 15 m use no 18 AWG American Wire Gage insulated wire 35 C minimum For 50 to 75 ft 15 to 23 m us...

Страница 16: ...t outlet FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps Protection NEC National Electrical Code PWRD CO Powered convenient outlet RLA Rated Load Amps UNPWR CO Unpowered convenient o...

Страница 17: ...e starting compressor If pressures do not equalize readily charge vapor on low side of system to assure charge in the evaporator Refer to GTAC II Module 5 Charging Recover Recycling and Reclamation fo...

Страница 18: ...o 90 minutes later Advanced Scroll Temperature Protection will reset automatically before the motor protector resets which may take up to 2 hours Start Unit Set the space thermostat to a set point abo...

Страница 19: ...19 C10784 Fig 16 38AUQ 16 Charging Chart 38AUQ...

Страница 20: ...20 C10785 Fig 17 38AUQ 25 Charging Chart 38AUQ...

Страница 21: ...21 C10786 Fig 18 38AUQ 16 Power Schematic 208 230 3 60 shown 38AUQ...

Страница 22: ...22 C10787 Fig 19 38AUQ 25 Power Schematic 208 230 3 60 shown 38AUQ...

Страница 23: ...23 C10788 Fig 20 38AUQ 16 25 Control Schematic 38AUQ...

Страница 24: ...y economizer Heating When the thermostat calls for first stage heating terminal W1 is energized The 38AUQ s Defrost Board DFB receives this input at P2 7 The DFB removes the output at P3 7 RVS1 the re...

Страница 25: ...checked S Fan shaft bearing locking collar tightness checked S Condensate drain checked S Blower motor amperage Outdoor Section S Fan motor mounting bolts tightness S Compressor mounting bolts S Fan b...

Страница 26: ...eader located at the entrance to each evaporator coil circuit path These are non adjustable Service requires replacing the entire liquid header assembly To check the indoor coil disconnect the supply...

Страница 27: ...stalled loss of charge pressure switch LOC has open close settings which do not provide indoor coil freeze protection The control provides a location on terminal board TB2 to add a field supplied indo...

Страница 28: ...mpressor or Stage 1 Heating both compressors run Table 8 38AUQ Defrost Board I O and Jumper Configurations Inputs Point Name Type of I O Connection Pin Number Unit Connection Note G Fan DI 24 vac P2 3...

Страница 29: ...rrupted On restart in Heating the defrost control will resume unit operation at the point in the run period where it was last operating Defrost Thermostats These are temperature switches that monitor...

Страница 30: ...Fans Service Valves C10791 Fig 26 38AUQ 16 Exterior Outdoor Coil Outdoor Coil Defrost Thermostat DFT Defrost Thermostat DFT High Flow Access Ports LOC LOC HPS HPS C10792 Fig 27 38AUQ 16 Interior 38AU...

Страница 31: ...ice Valves C10793 Fig 28 38AUQ 25 Exterior Outdoor Coil Outdoor Coil Defrost Thermostat DFT Defrost Thermostat DFT High Flow Access Port HPS HPS LOC LOC High Flow Access Port C10794 Fig 29 38AUQ 25 In...

Страница 32: ...ions The ALERT LED indicates an abnormal condition exists in the system through a flash code The ALERT LED will blink a number of times consecutively pause and the repeat the process The number of bli...

Страница 33: ...Yellow ALERT Flash Code 3 Short Cycling Compressor is running only briefly LOCKOUT 1 If low pressure switch is open a Low refrigerant charge b Evaporator blower is not running c Evaporator coil is fr...

Страница 34: ...VAC when off Outdoor Fans Each fan is supported by a formed wire mount bolted to the fan deck and covered with a wire guard Fan motors have permanently lubricated bearings 1 Shut off unit power supply...

Страница 35: ...leach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin tu...

Страница 36: ...ilable from the Replacement Components Division s Electronic Parts Information Catalog EPIC EPIC is available at Totaline stores distributor and service office parts departments and on line at HVACPar...

Страница 37: ...ing motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load o...

Страница 38: ...liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with w...

Страница 39: ...the low ambient relay LAR The LAS control temperatures are open 42_F 5_F close 57_F 5_F open 5 5_C 2 8_C close 13 9_C 2 8_C To override the speed control for full fan speed operation during service or...

Страница 40: ...1 2 25 3 4 38 1 2 38SUQ 25 LEFT SIDE 32 7 8 33 5 8 34 3 8 43 1 8 4 1 4 13 1 4 22 1 4 31 1 4 40 1 4 BACK 47 3 4 48 1 2 49 1 4 43 1 8 4 1 4 13 1 4 22 1 4 31 1 4 40 1 4 RIGHT SIDE 61 1 8 61 7 8 62 5 8 43...

Страница 41: ...41 C10363 Fig 35 Wind Baffles Fabrication 38AUQ...

Страница 42: ...42 C10366 Fig 36 15 Ton Wind Baffle Brackets Fabrication 38AUQ...

Страница 43: ...43 RIGHT BACK LEFT FRONT BOTTOM BRACKET TOP BRACKETS C10367 Fig 37 Wind Baffle Installation 15 Ton Units 38AUQ...

Страница 44: ...44 RIGHT BACK LEFT FRONT C10368 Fig 38 Wind Baffle Installation 20 Ton Units 38AUQ...