BASE UNIT DIMENSIONS – 38AUM Series Size Z07-D14
NOTES:
1. Minimum clearance (Local codes or jurisdiction may prevail):
A. Bottom to combustible surfaces: 0 inches
B. Outdoor coil, for proper airflow: 36 inches one side, 12 inches the other. The side getting the greater clearance is optional.
C. Overhead: 60 inches, to assure proper outdoor fan operation.
D. Between units: Control box side: 42 inches per NEC.
E. Between unit and ungrounded surfaces: Control box side, 36 inches per NEC.
F. Between unit and block or concrete walls and other grounded surfaces: Control box side 42 inches per NEC.
2. With exception of the clearance for the outdoor coil as stated in note 1B, are movable fence or barricade requires no clearance.
3. Units may be installed on combustible floors made from wood or Class A, B or C roof covering material.
Unit
38AUM
Unit
Weight
(kg)
Height (mm)
Center of Gravity
(mm)
Service Valve
Connections
H
X
Y
Z
Suction
Liquid
Z07
176.0
1165.0
457.2 609.6
533.4
1-1/8
3/8
Z08
177.0
1165.0
457.2 609.6
533.4
1-1/8
1/2
D12
234.0
1368.0
482.6 584.2
609.6
1-1/8
3/8
D14
297.0
1368.0
508.0 635.0
609.6
1-3/8
1/2
FRONT VIEW
LEFT SIDE VIEW
RIGHT SIDE VIEW
- Center Of Gravity
- Direction of Air Flow
Page 5
Содержание 38AUM Series
Страница 31: ...TYPICAL WIRING SCHEMATIC 38AUMZ07 08 Page 31...
Страница 32: ...TYPICAL WIRING SCHEMATIC 38AUMD12 14 Page 32...
Страница 33: ...TYPICAL WIRING SCHEMATIC 38AUMD16 Page 33...
Страница 34: ...CHARGING CHARTS Page 34...
Страница 36: ...CHARGING CHARTS cont Page 36...
Страница 37: ...CHARGING CHARTS cont Page 37...
Страница 41: ...NOTES Page 41...
Страница 42: ...NOTES Page 42...
Страница 43: ...NOTES Page 43...