Table - LED Status Codes
Status LED
Status LED Description
Status LED Troubleshooting Information
Green “POWER”
Module has power
Supply voltage is present at module terminals
Red “TRIP” LED
On Solid
Thermostat demand signal Y is
present, but the compressor is not
running.
1. Compressor protector is open
2. Condensing unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken supply wires or connector is not making contact
5. Compressor power wires not routed through Comfort Alert
6. Compressor contactor has failed open
Red “TRIP” LED
Flashing
The anti-short cycle timer (3 minutes) in module is preventing compressor restart.
Module locks out compressor when compressor damaging ALERT code appears. Lockout ALERT codes are
noted in the Status LED Description.
During a compressor lock out, 24VAC power must be removed from module to manually reset.
Yellow “ALERT” LED
On Solid
A short circuit or over current
condition exists on PROT terminal.
1. Compressor contactor coil shorted
2. Electrical load too high for PROT circuit (maximum 1 Amp)
3. 24 V AC wired directly to PROT terminal
Yellow “ALERT”
Flash Code 2
System Pressure Trip Discharge
pressure out of limits LOCKOUT
1. High head pressure
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan is not running
4. If low pressure switch is open:
a. Low refrigerant charge
b. Evaporator blower is not running c. Evaporator coil
is frozen
d. Faulty metering device e. Condenser coil
is dirty\
f.
Liquid line restriction (filter drier blocked if present)
Yellow “ALERT”
Flash Code 3
Short Cycling
Compressor is running only briefly
(four consecutive cycles of less
than three minutes each)
LOCKOUT
1. Loose connection between thermostat Y1 and CADM Y terminal.
2. Unit short --- cycling on thermostat
3. System or control board defective
Yellow “ALERT”
Flash Code 4
Locked Rotor
LOCKOUT
1. Low line voltage to compressor
2. Excessive liquid refrigerant in compressor
3. Compressor bearings are seized
Yellow “ALERT”
Flash Code 5
Open Circuit
1. Condensing unit power disconnect is open
2. Compressor circuit breaker or fuses are open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Broken supply wires or connector is not making contact
6. Unusually long compressor protector reset time due to extreme ambient
temperature
7. Compressor windings are damaged
Yellow “ALERT”
Flash Code 6
Missing Phase
LOCKOUT
1. Compressor fuse is open on one phase
2. Broken wire or connector on one phase
3. Compressor motor winding is damaged
4. Utility supply has dropped one phase
Yellow “ALERT”
Flash Code 7
Reverse Phase
LOCKOUT
1. Compressor running backward due to supply phase reversal
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Voltage
Control circuit < 18VAC
1. Control circuit transformer is overloaded
2. Low line voltage to compressor
Page 25
Содержание 38AUM Series
Страница 31: ...TYPICAL WIRING SCHEMATIC 38AUMZ07 08 Page 31...
Страница 32: ...TYPICAL WIRING SCHEMATIC 38AUMD12 14 Page 32...
Страница 33: ...TYPICAL WIRING SCHEMATIC 38AUMD16 Page 33...
Страница 34: ...CHARGING CHARTS Page 34...
Страница 36: ...CHARGING CHARTS cont Page 36...
Страница 37: ...CHARGING CHARTS cont Page 37...
Страница 41: ...NOTES Page 41...
Страница 42: ...NOTES Page 42...
Страница 43: ...NOTES Page 43...