40RUM
Arrangement
Cooling Stage
40RUM Coil
Segment
Connect to 38AUMD
Vertical
Y1
2
Circuit 1
Y2
1
Circuit 2
Horizontal
Y1
1
Circuit 1
Y2
2
Circuit 2
Fig: - Typical Evaporator Coil Connections (40RUM)
Install Filter Drier(s) and Moisture Indicator(s)
Every unit MUST have a filter drier in the liquid line. 38AUMD models require two filter driers (one in each liquid line).
Locate the filter drier(s) at the indoor unit, close to the evaporator coil’s thermal expansion valve (TXV) inlets.
Installation of liquid line moisture indicating sightglass in each circuit is recommended. Locate the sightglass(es)
between the outlet of the filter drier and the TXV inlet. In some applications, depending on space and convenience
requirements, it may be desirable to install 2 filter driers and sight glasses in a single circuit application. One filter drier
and sight glass may be installed at A locations
Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from the
indoor unit to the outdoor unit before opening the liquid and suction lines at the outdoor unit.
Fig: - Location of Sight Glass(es) and Filter Driers Typical 38AUMZ Systems
Page 12
Содержание 38AUM Series
Страница 31: ...TYPICAL WIRING SCHEMATIC 38AUMZ07 08 Page 31...
Страница 32: ...TYPICAL WIRING SCHEMATIC 38AUMD12 14 Page 32...
Страница 33: ...TYPICAL WIRING SCHEMATIC 38AUMD16 Page 33...
Страница 34: ...CHARGING CHARTS Page 34...
Страница 36: ...CHARGING CHARTS cont Page 36...
Страница 37: ...CHARGING CHARTS cont Page 37...
Страница 41: ...NOTES Page 41...
Страница 42: ...NOTES Page 42...
Страница 43: ...NOTES Page 43...