background image

13

Analog Control Troubleshooting —

The following

troubleshooting procedure is directed towards single duct cool-
ing applications. The same concepts can be applied to other
configurations.
CONTROLLER

1. Verify 24 vac at terminals “~” (phase) and “-” (ground).

Tolerance can be –15% to +20% (20.4 to 28.8 vac).

2. Verify 16 vdc at terminals “(16 VDC)” and “(-)”.

a.

Tolerance is 15.0 to 17.0 vdc power supply to
thermostat.

b.

If not correct, disconnect thermostat and recheck.
If still incorrect, replace CSP controller.

3. Check Requested Flow voltage on terminal “IN” and

“-”.

a.

Use chart on page 12 to correlate into cubic feet
per minute (cfm).

b.

If reading is not what is desired, see System Cali-
bration of the Linear Averaging Flow Probe sec-
tion to adjust thermostat.

4. Check Actual Flow voltage on terminal “OUT” and “-”

for 0 to 10 vdc.
Use chart on page 12, Fig. 14 to correlate into cfm.

5. Check box movement, damper rotation, etc.

a.

Review Requested Flow and Actual Flow above
to determine if unit should be satisfied (within
50 fpm) or driving open or closed.

b.

If damper is not moving, verify damper is not
stuck or at end of travel. Check rotation jumpers
for proper position.

c.

Change “Requested Flow” to make unit drive
opposite direction. This can be accomplished by
moving the set point sliders or 1) and 2) below.

1) To manually open the box, remove wiring

from terminal “IN” and jumper terminal “IN”
to terminal “16VDC”. This will tell unit to
control at 3300 fpm/full airflow, and the green
LED should turn on (and the box should drive
open).

2) To manually close the box, remove wiring

from terminal “IN”, jumper and “IN” terminal
to “-” terminal. This will tell unit to control at
zero fpm/no airflow, and the red LED should
be on (and the box should drive closed).

NOTE: When using the same transformer for more than one
control, the phase and ground must be consistent with each
device.

ComfortID™ CONTROLS

Install

Sensors

and

Make

Field

Wiring

Connections

GENERAL — All field wiring must comply with National
Electrical Code and local requirements. Refer to Tables 6-9 for
electrical and wiring specifications.

Wire the control as shown on the control package diagram

for the specific installation. Control wiring diagrams can be
found inside the control box.

If the 35E unit is equipped with electric heat, only power to

the electric heater must be supplied; no additional power
source is required for the control. If the unit does not have an
electric heater or the control transformer option, a field-
supplied dedicated 24-vac/Class II power source must be in-
stalled and wired to the zone controller, to terminals 1 and 2 of
connector J1. Refer to unit wire label diagram for minimum
size (VA) and grounding requirements for each unit.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR INSTAL-
LATION — On terminals with heat, the SAT sensor is provid-
ed. The sensor is factory wired to the controller and shipped in
the control box. The SAT must be field-installed in the duct
downstream from the air terminal. The SAT sensor part num-
ber is 33ZCSENSAT. See Table 6 for resistance information.

To install the sensor, proceed as follows:

1. Remove the plug from one of the

7

/

8

-in. openings in the

control box and pass the sensor probe through the hole.

2. Drill or punch a

1

/

2

-in. hole in the duct downstream of

the unit, at a location meeting the requirements shown in
Fig. 15.

3. Using 2 self-drilling screws (supplied), secure the sensor

probe to the duct.

The SAT sensor probe is 6 inches in length. The tip of the

probe must not touch the inside of the duct. Use field-supplied
bushings as spacers when mounting the probe in a duct that is
6 in. or less in diameter.

If the unit is a cooling only unit, the SAT sensor is not pro-

vided and is not required.

If the unit has a multiple outlet attenuator connected directly

at the discharge, install the sensor in the multiple outlet attenua-
tor. See Fig. 15.

For units equipped with electric reheat, locate the sensor as

far downstream as possible. This ensures the sensor will not be
affected by excessive radiant heat from the heater coil. Install
the sensor a minimum of 2 ft downstream of the coil for units
with hot water heat.

Perform the following steps if state or local code requires

the use of conduit, or if your installation requires a cable length
of more than 8 ft:

1. Disconnect the sensor cable from the ComfortID zone

controller, at the terminals labeled SAT and GND.

2. Mount the sensor to the duct (see steps 2 and 3 above).
3. Mount a field supplied 4 in x 4 in x 20 in. extension box

over the duct sensor.

4. Connect a conduit (

1

/

2

-in. nominal) to the zone controller

enclosure and extension box.

5. Pass the sensor probe through the extension box opening

and into the conduit.

6. Reconnect the sensor leads to the zone controller labeled

SAT and GND.

Never jumper terminal 16 VDC to “-” as this would cause
a short, and possibly damage the power supply.

Disconnect electrical power before wiring inside the con-
troller. Electrical shock, personal injury, or damage to the
zone controller can result.

DO NOT run sensor or relay wires in the same conduit or
raceway with Class 1 service wiring.
DO NOT abrade or nick the outer jacket of cable.
DO NOT pull or draw cable with a force that may harm the
physical or electrical properties.
DO NOT bend a cable through a radius sharper than that
recommended by its manufacturer.
AVOID splices in any control wiring.

Содержание 35E

Страница 1: ... ADJUSTMENT SLIDEBAR WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK PRIMARY AIR TEMPERATURE SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR WIRING HUMIDITY SENSOR Wall Mounted INSTALLATION Connect the CCN Communication Bus 19 COMMUNICATION BUS WIRE SPECIFICATIONS CONNECTION TO THE COMMUNICATION BUS Water Valve Installation 19 ComfortID Start Up 19 GENERAL PR...

Страница 2: ...ls or controls File damage claim immediately with transportation agency and notify Carrier UNIT IDENTIFICATION Each unit is supplied with a shipping label and an identification label Fig 2 INSTALLATION PRECAUTION Check that construction debris does not enter unit or ductwork Do not operate the central station air handling fan without final or construction filters in place Accumulated dust and cons...

Страница 3: ...urn tracking 4149 Proportional floating hot water with supply return tracking 4150 Return air damper CCN Thermostats Ordered Separately Thermostat 33ZCT56SPT RT room temperature sensor with set point adjust and override Thermostat 33ZCT55SPT RT room temperature sensor with override only Thermostat 33ZCT58SPT Communicating room tempera ture sensor with LCD liquid crystal diode set point adjust fan ...

Страница 4: ...ion area Remove unit from ship ping package Do not handle by controls or damper extension rod 2 The unit has factory installed brackets on unit as shown in Fig 3 3 Suspend units from building structure with straps rods or hanger wires Secure the unit and level it in each direc tion Note that reheat coil is in heavy end of unit Step 2 Make Duct Connections 1 Install supply ductwork on unit inlet co...

Страница 5: ...04 0 35 675 13 0 21 0 09 0 27 0 44 0 60 0 76 0 09 925 13 0 39 0 17 0 51 0 82 1 13 1 43 0 17 240 240 or 0 240 4 9 0 02 0 01 0 02 0 03 0 04 0 05 0 01 9 550 11 3 0 08 0 07 0 12 0 17 0 22 0 27 0 07 0 44 875 16 0 21 0 17 0 31 0 44 0 57 0 69 0 17 1200 16 0 40 0 32 0 59 0 83 1 07 1 31 0 32 300 290 or 0 300 6 2 0 02 0 01 0 02 0 04 0 05 0 07 0 01 10 675 13 9 0 08 0 04 0 12 0 20 0 27 0 35 0 04 0 55 1075 21 ...

Страница 6: ...is typical of 480V 3 phase 4 wire heater and control Refer to actual unit wiring diagram AFS Airflow Switch DDC Direct Digital Controls Fig 5 Typical Power Connections for 35E Units with 3 Stage Electric Heat ANALOG OR DDC CONTROLLER 24VAC BLU YEL CLASS II TRANSFORMER OPTIONAL 120VAC 208VAC 240VAC 277VAC L1 GROUND 24 VAC POWER LEGEND NOTE Drawing is typical refer to actual unit wiring diagram for ...

Страница 7: ...s will provide a permanent record of the balanc ing information installation location information box size cooling minimum airflow cfm limit cooling maximum airflow cfm limit reheat cfm limit if applicable heating minimum airflow cfm limit if applicable heating maximum airflow cfm limit if applicable calibration gain after balancing set points PNEUMATIC CONTROLS Preparation for Balancing Control S...

Страница 8: ...______ ENGINEER ______________________________________________ BUILDING LOCATION FLOOR ______________________________ BUS NUMBER ___________________________________________ Fig 7 Air Terminal Performance Sheet CONTROL SET POINTS Tag Number Zone Address Box Size in cfm Cooling cfm Reheat cfm Heating cfm Heat kW Occupied Unoccupied Calibration Gain min max min max Type Btu min max min max mult ...

Страница 9: ...DAMPER Control Sequence 1103 Refer to Fig 9 1 Maximum volume setting a Disconnect the thermostat line from the velocity controller b Adjust the maximum volume control knob marked HI and located in the center of the con troller to achieve the required minimum flow To determine the required pressure differential refer to Tables 2 and 5 and the Linear Averaging Probe Chart provided on the side of the...

Страница 10: ... initial adjustments are made cycle the thermostat pressure a few times to settle the internal reset mechanisms and verify set tings Fine tune the settings if necessary The thermostat pres sure may be left at a high pressure and the G port cap may be removed and replaced to cycle the reset mechanism RESET START setting is factory set at 8 0 psig This is the lowest thermostat pressure that the LO S...

Страница 11: ... heating set point slider all the way to the right for maximum heating 5 Read the DC voltage across the meter taps on the heating left side Adjust the maximum set point MAX INCR potentiometer clockwise to increase or counterclockwise to decrease to the DC voltage equal to the desired air flow cfm as shown on the calibration curve Fig 14 NOTE The maximum set point must be adjusted last Adjust ment ...

Страница 12: ...adjusted first Adjust ment of the MIN INCR potentiometer directly affects the max imum set point and auxiliary set point 2 Adjustment of auxiliary set point if required Read the DC voltage across the meter taps on the heating left side Adjust the MAX AUX INCR potentiometer clockwise to increase or counterclockwise to decrease to the DC voltage equal to the desired airflow cfm 3 Return the cooling ...

Страница 13: ... and 2 of connector J1 Refer to unit wire label diagram for minimum size VA and grounding requirements for each unit SUPPLY AIR TEMPERATURE SAT SENSOR INSTAL LATION On terminals with heat the SAT sensor is provid ed The sensor is factory wired to the controller and shipped in the control box The SAT must be field installed in the duct downstream from the air terminal The SAT sensor part num ber is...

Страница 14: ... connection will be made If connection is desired the CCN communication cable should be available at time of sensor installation for convenient wiring connections The cable selected must meet the requirements for the entire network See Connect the CCN Communication Bus section for CCN communication cable specifications RESISTANCE Ohms TEMP F RESISTANCE Ohms TEMP F RESISTANCE Ohms TEMP F RESISTANCE...

Страница 15: ...inches Fig 18 Space Temperature Sensor and Wall Mounted Humidity Sensor Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING Fig 19 Space Temperature Sensor Wiring 33ZCT55SPT 2 3 4 5 6 1 SW1 SEN SET Cool Warm WHT T56 BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING JUMPER TERMINALS AS SHOWN Fig 20 Space Temperature Sensor Wiring 33ZCT56SPT ...

Страница 16: ...he sensor end of the cable 3 Connect the sensor cable as follows a Connect one wire from the cable RED to the SPT terminal on the controller Connect the other end of the wire to the left terminal on the SEN ter minal block of the sensor b Connect another wire from the cable BLACK to the ground terminal on the controller Connect the other end of the wire to the remaining open termi nal on the SEN t...

Страница 17: ... the sensor where it is influenced by the supply air the sensor gives inaccurate readings if the supply air is blown directly onto the sensor To mount the sensor refer to the installation instructions shipped with the accessory kit INDOOR AIR QUALITY SENSOR WIRING To wire the sensor after it is mounted in the conditioned air space see Fig 23 25 and the instructions shipped with the sensor Use two ...

Страница 18: ...he center of the sensor 2 Connect the RED wire to the sensor screw terminal marked 3 Install one lead from the resistor supplied with the sen sor and the WHITE wire into the sensor screw terminal marked After tightening the screw terminal test the connection by pulling gently on the resistor lead 4 Connect the remaining lead from the resistor to the BLACK wire and secure using a field supplied clo...

Страница 19: ...nal zone controllers in a daisy chain fashion following the color coded wiring scheme in Table 9 NOTE The communication bus drain wires shield must be tied together at each zone controller If the communica tion bus is entirely within one building the resulting contin uous shield must be connected to ground at only one single point If the communication bus cable exits from one build ing and enters ...

Страница 20: ...s a portable device to change system set up and set points from a zone sensor or ter minal control module During start up the Building Supervisor or the Network Service Tool can also be used to verify commu nication with each controller For specific operating instructions refer to the appropriate user manual See Table 11 for troubleshooting information ComfortID TEST AND BALANCE TOOL SOFT WARE The...

Страница 21: ...n electric box mounted horizontally may be used instead of cutting the hole 2 Remove the cover from the thermostat controller Care fully remove the circuit board from the backplate of the thermostat controller Line up the backplate with the hole in the wall Push the protruding part of the backplate into the hole Pull the thermostat controller wires out through the backplate 3 Attach backplate to w...

Страница 22: ... board Slide the cir cuit board under the back plate securing bars DO NOT CREASE RIBBON CABLE 7 Align thermostat board with alignment pin Gently pull down on the thermostat latch and press firmly until the circuit board snaps into place 8 If optional locking thermostat cover is purchased insert locking clip on the inside of the thermostat cover Push firmly into place 9 Insert tabs on thermostat co...

Страница 23: ...k system Variable Volume and Temperature VVT Product Data literature and the configura tion instructions provided with the thermostat Refer to the specific control sequence 35E 82XX for de tailed operational information This information should be used to test and commission the control Control Start Up GENERAL Air volume delivery to the conditioned space is controlled by the modulating of the prim...

Страница 24: ... discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 533 530 Printed in U S A Form 35E 2SI Pg 24 3 06 Replaces 35E 1SI Copyright 2006 Carrier Corporation Book 3 Tab 6a ...

Отзывы: