Do not splash detergent solution in eyes, and avoid prolonged
contact with skin. Keep detergent and solution out of reach of
children.
c. Before placing cells in washing container, pour in deter-
gent. Use approximately 3/4 cup per cell if container is
about size of cell. Add enough very hot water to cover
cell(s).
d. After detergent has completely dissolved, place electronic
cell(s) in container.
e. Soak cells for 15 to 20 minutes, slosh several times, and
remove.
f. Rinse cells with fine water spray.
g. Fill wash container with clean, hot water and soak cell(s)
for 5 to 15 minutes.
h. Remove cell(s) and let water drain. If water draining from
them feels slippery, detergent still remains. Repeat rinsing
until water from them no longer feels slippery. Inspect for
cleanliness.
i. When both cells have been washed and thoroughly rinsed,
check cells from broken wires and bent collector plates. If
none are found, replace electronic cells and pre-filter in
cabinet. Observe proper airflow arrows on cabinet and cells.
j. Dry cells completely before turning on power to air cleaner.
This can be done by turning on system fan continuously for
approximately 30 minutes before turning on power to air
cleaner.
SERVICE GUIDE
Procedures in this section should be performed only be
qualified service personnel.
Electrical shock can cause injury or death.
1. During troubleshooting procedures, dangerous line-voltage
circuits are exposed. Use care to avoid hazard of electrical
shock or damage to equipment.
Fig. 21—EAC Connection to 2-Stage "C" Furnace
Control Board
A94083
1
2
3
4
5
6
7
8
9
PR2
L2
COM
PR1
L1
EAC-2
EAC-1
H
I-
C
O
O
L
HI-GAS
-HEAT
LO-GAS
-HEAT
PARK
3
FU1
SEC-1
SEC-2
1
1
2
3
4
5
6
7
8
9
10
11
12
MASTER SLAVE
TWIN
TEST
LED
G
R
Y/Y2
W/W1
COM
24 V
W2
1
ON
OFF
1
2
3
4
FURNACE AND
BLOWER OFF
DELAY SETUP
SWITCHES
24-VOLT
THERMOSTAT
TERMINALS
EAC - ELECTRONIC AIR CLEANER
(115-VAC 1 AMP MAX)
3-AMP
FUSE
LED -
DIAGNOSTIC
LIGHT
HUM
Fig. 22—Internal Furnace Electrical Connections for
EAC
A91060
W
Y
R
C
G
3
HUM-1
BLOWER OF DELAY SELF TEST
90 100 180 225
3-AMP FUSE
ELECTRONIC
AIR CLEANER
TERMINALS
(115 VAC, 1 AMP MAX)
HUMIDIFIER TERMINAL
(24 VAC, 0.5 AMP MAX)
JW9
SELF-TEST PINS
BLOWER OFF-DELAY
ADJUSTMENT CONTROL
24-VOLT THERMOSTAT
TERMINALS
EAC-2
EAC-1
Fig. 23—EAC Terminals on Control Center
A94084
EAC2
EAC1
Fig. 24—Final Assembly Detail
A89420
AIR FLOW
AIRFLOW
DECAL
JUNCTION
BOX
COVER
PROPER
SPRING
LOCATION
10