background image

29

 

 -  altitude: ≤ 2000 m (see note for table 9.2 - Electrical data, hydronic module)

 

presence of hard solids, class 4S2 (no significant dust present)

 

presence of corrosive and polluting substances, class 4C2 (negligible)

2.  Power supply frequency variation: ± 2 Hz.

3.   The neutral (N) conductor must not be connected directly to the unit (if necessary 

use a transformer).

4.  Overcurrent protection of the power supply conductors is not provided with the 

unit.

5.   The factory-installed disconnect switch 

(option 70)

 is of a type suitable for power 

interruption in accordance with EN 60947.

6.  The units are designed for simplified connection on TN(s) networks (IEC 60364). 

For IT networks provide a local earth and consult competent local organisations to 

complete  the  electrical  installation.  Units  delivered  with  speed  drive 

 

(options 28 and 116V/W) are not compatible with IT network.

7.  Derived currents: If protection by monitoring of derived currents is necessary to 

ensure the safety of the installation, the control of the cut-out value must take the 
presence of leak currents into consideration that result from the use of frequency 

converters  in  the  unit.  A  value  of  at  least  150  mA  is  recommended  to  control 

differential protection devices.

Caution: If particular aspects of an actual installation do not conform to the 

conditions described above, or if there are other conditions which should be 

considered, always contact your local Carrier representative.

The absence of main power disconnect switch on standard machines is an exception 

that must be taken in account at field installation level.

**  The required protection level for this class is IP43BW (according to reference 

document IEC 60529). All 30RQS/RQSY units 

fulfil this protection condition:

 

 - 

Closed electrical box is IP44CW

 

Open electrical box (when accessing to interface) is IPxxB

Electrical data and operating conditions notes:

•  30RQS/RQSY  039-160  units  have  a  single  power  connection  point  located

 

immediately upstream of the field power connections.

•  The control box includes the following standard features:

 

Starter and motor protection devices for each compressor, the fans and the 
pump,

 

The control devices.

 

A main disconnect switch can be installed within the box with the option 70.

• 

Field connections:

 

All  connections  to  the  system  and  the  electrical  installations  must  be  in  full 

accordance  with all applicable local codes.

•  The Carrier 30RQS/RQSY units are designed and built to ensure conformance 

with these codes. The recommendations of European standard EN 60204-1 (machine 

safety - electrical machine components - part 1: general regulations - corresponds 

to IEC 60204-1) are specifically taken into account, when designing the electrical 

equipment*.

• 

An auxiliary contactor is available with the QF breaker allowing a safety channel installation 

to ensure a feedback output about heater and board power supply status and then 

prevent evaporator from frosting when heaters and boards are off.

NOTES: 

•  Generally the recommendations of IEC 60364 are accepted as compliance with 

the requirements of the installation directives. Conformance with EN 60204-1 is 

the best means of ensuring compliance with the Machines Directive § 1.5.1. 

•  Annex  B  of  EN  60204-1  describes  the  electrical  characteristics  used  for  the 

operation of the machines.

•  The operating environment for the 30RQS/RQSY units is specified below:

1.  Environment** - Environment as classified in EN 60721 (corresponds to IEC 

60721):

 

outdoor installation**

 

ambient temperature range: -20°C to +48°C, class 4K4H

10.2 - Operating range, standard units - heating mode

Condenser

Minimum Maximum

Entering water temperature at start-up

°C

8

45

Leaving water temperature during operation

°C

25

55

Entering/leaving water temperature difference

K

3

10

Evaporator

Minimum Maximum

Air temperature

°C

-15

40

Hydronic module*

Entering air temperature

Kit without pump

°C

-20

-

Kit with pump (option 116x)

°C

0

-

Kit with (option 116x) et frost protection option 

to -20°C (option 42)

°C

-20

-

Kit with buffer tank (option 307)

°C

0

-

Kit with buffer tank (option 307) and frost 

protection option to -20°C (option 42B)

°C

-20

-

Note:

 Do not exceed the maximum operating temperature.

*  Defines the frost-free temperature of the hydronic components for use without 

glycol.

20

25

30

35

40

45

50

55

60

-20

-10

0

10

20

30

40

50

Entering air temperature, °C

L

ea

ving w

ater temper

atur

e

, °C

Full load
Minimum load

30RQS/RQSY - heating mode

10 - APPLICATION DATA

10.1 - Operating range, standard units - cooling mode

Evaporator

Minimum

Maximum

Entering water temperature at start-up

°C

7.5*

30

Leaving water temperature during operation

°C

5**

20

Entering/leaving water temperature difference

K

3

10

Condenser

Minimum

Maximum

Entering air temperature 30RQS***

°C

-10

48

Entering air temperature 30RQSY***

°C

-20

48

Hydronic module****

Entering air temperature

Kit without pump

°C

-20

-

Kit with pump (option 116x)

°C

0

-

Kit with (option 116x) et frost protection option 

to -20°C (option 42)

°C

-20

-

Kit with buffer tank (option 307)

°C

0

-

Kit with buffer tank (option 307) and frost 

protection option to -20°C (option 42B)

°C

-20

-

Note:

 Do not exceed the maximum operating temperature.

*  For entering water temperatures below 7.5°C at start-up, contact Carrier.

**  For low-temperature applications, where the leaving water temperature is below 

5°C, a frost protection solution must be used.

***  For transport and storage of the 30RQS/30RQSY units the minimum and maximum 

allowable  temperatures  are  -20°C  and  +48°C.  It  is  recommended  that  these 

temperatures are used for transport by container.

****  Defines the frost-free temperature of the hydronic components for use without 

glycol.

-20

-10

0

10

20

30

40

50

0

5

10

15

20

25

30RQS

30RQSY

Evaporator leaving water temperature, °C

Entering air temper

atur

e

, °C

Full load
Minimum load

30RQS/RQSY - cooling mode

NOTE: This operating range applies up top 130 Pa static 
pressure without suction air duct for sizes 060, 070 and 078 
and 140-160, and up to 240 Pa for all other sizes.

Содержание 30RQS039

Страница 1: ...I O N S Reversible Air to Water Heat Pumps 30RQS 30RQSY 039 160 A Original instructions Nominal cooling capacity 40 160 kW 50 Hz Touch Pilot Junior For the operation of the control please refer to th...

Страница 2: ...without filter frame 16 4 6 30RQSY 050 078 option 23B units with and without hydronic module with filter frame 17 4 7 30RQSY 080 120 units with and without hydronic module 18 4 8 30RQSY 140 160 units...

Страница 3: ...ressors 43 15 2 Lubricant 43 15 3 Air evaporator condenser 43 15 4 Fans 43 15 5 Electronic expansion valve EXV 43 15 6 Moisture indicator 43 15 7 Filter drier 43 15 8 Water evaporator condenser 44 15...

Страница 4: ...are equipped with variable speed fans with a maximum speed of 19 r s to ensure an optimised air flow rate In the cooling mode the full load or part load speed is controlled by a patented algorithm th...

Страница 5: ...nd national usage monitoring regulations in the European Uniontheprotectiondevicesforthesemachinesareclassified as follows Safety accessory Damage limitation accessory in case of an external fire Refr...

Страница 6: ...OPERATING CHECKS Important information regarding the refrigerant used Thisproductcontainsfluorinatedgreenhousegascoveredbythe Kyoto protocol Fluid type R410A GlobalWarming Potential GWP 2088 Relief v...

Страница 7: ...ify and and record the set points of pressure switchesandreliefdevices valvesandpossiblerupture discs Be ready to switch off the main disconnect switch of thepowersupplyifthepressureswitchdoesnottrigg...

Страница 8: ...itionanysafetydeviceswhen corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not install relief valves in seri...

Страница 9: ...tening measures have been taken if the unit has to operate as a heat pump in temperatures below 0 C it must be raised at least 300 mm from the ground Thisisnecessarytoavoidicebuild up on the unit chas...

Страница 10: ...air heat exchanger is on two unit sides It is therefore necessary to install two additional brackets to allow connection of the heat exchanger suction duct These parts are inside the machine and fixe...

Страница 11: ...ducts The fan protection grilles can be removed to increase the available pressure At the beginning of each duct provide an access hatch with minimum dimensions of 700 x 700 mm to allow motor replace...

Страница 12: ...location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side clearan...

Страница 13: ...entre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C The hei...

Страница 14: ...gs B Provide a gutter around the unit to collect the condensate water or install the accessory condensate collection pan 30RQSY 039 to 078 C The unit must be installed level less than 2 mm per metre d...

Страница 15: ...pplied with the unit or available onrequest whendesigninganinstallation Forthelocationoffixingpoints weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B Prov...

Страница 16: ...ith the unit or available on request when designing an installation For the location of fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B Pro...

Страница 17: ...awings B Provide a gutter around the unit to collect the condensate water or install the accessory condensate collection pan 30RQSY 039 to 080 C The unit must be installed level less than 2 mm per met...

Страница 18: ...mended clearances for maintenance Air outlet do not obstruct Power cable entry NOTES A Non certified drawings Refer to the certified dimensional drawings supplied with the unit or available on request...

Страница 19: ...ecommended clearances for maintenance Air outlet do not obstruct Power cable entry NOTES A Non certified drawings Refer to the certified dimensional drawings supplied with the unit or available on req...

Страница 20: ...fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B The unit must be installed level less than 2 mm per metre deviation in both axes Overall d...

Страница 21: ...location of fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B The unit must be installed level less than 2 mm per metre deviation in both axe...

Страница 22: ...lets and outlets 4 13 30RQS RQSY 140 160 units with desuperheater Position of the desuperheater inlets and outlets Unit water inlet and outlet Water inlet and outlet unit with option 49 4 11 30QBS RQS...

Страница 23: ...Maximum total air flow l s 3692 3690 3910 5285 5284 5282 7770 7380 7376 7818 10568 10568 Maximum rotation speed r s 12 12 12 16 16 16 12 12 12 12 16 16 Water heat exchanger Direct expansion plate hea...

Страница 24: ...draw A 26 29 33 36 42 53 53 55 62 77 85 106 Maximum unit current draw Un A 35 45 47 53 67 73 74 81 99 108 134 146 Maximum unit current draw Un 10 A 38 49 51 58 75 80 80 89 110 118 150 159 Customer sid...

Страница 25: ...with rotating shroud Quantity 1 1 1 1 1 1 2 2 2 2 2 2 Maximum total air flow l s 3692 3690 3910 5278 4982 5267 7770 7380 7376 7818 9964 10534 Maximum speed r s 16 16 16 18 18 18 16 16 16 16 18 18 Wat...

Страница 26: ...ximum unit current draw Un A 37 47 49 55 67 73 79 86 104 113 135 147 Maximum unit current draw Un 10 A 41 52 54 61 75 80 85 94 116 123 150 160 Customer side unit power reserve kW Customer reserve at t...

Страница 27: ...ear of manufacture This information varies depending on the manufacturer and model at the time of incorporation Please refer to the motor name plates 4 Manufacturer s name and trademark commercial reg...

Страница 28: ...ecifically designed I Altitudes above sea level m 1000 II Ambient air temperature C 55 IV Maximum air temperature C Please refer to the operating conditions given in this manual or in the specific con...

Страница 29: ...power supply status and then prevent evaporator from frosting when heaters and boards are off NOTES Generally the recommendations of IEC 60364 are accepted as compliance with the requirements of the...

Страница 30: ...en into account 250 litres Bad Good Bad Good 10 6 2 Maximum water loop volume Units with hydronic module incorporate an expansion tank that limits the water loop volume The table below gives the maxim...

Страница 31: ...35 305 PVC Cu 070 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 50 350 PVC Cu 078 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 70 380 PVC Cu 080 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 70 380 PVC Cu 090 1 x 95 1 x 95 1 x...

Страница 32: ...ce dure must be chemically neutral in relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier ATTENTION Use of units in a...

Страница 33: ...your area you must do the following when switching the unit off in winter Addethyleneglycolorpropyleneglycolwithanadequate concentration to protect the installation up to a temperature of 10 K below t...

Страница 34: ...rleavingpressureinformation seeregulationmanual 11 Check valve If dual pump 12 Plate heat exchanger 13 Heater or tracer for frost protection Option 14 Flow sensor for water heat exchange 15 Buffer tan...

Страница 35: ...ic module sizes 039 078 Dual pump shown Hydronic module sizes 080 160 Dual pump shown Hydronic module sizes 039 080 Dual pump and buffer tank shown Hydronic module sizes 090 160 Dual pump and buffer t...

Страница 36: ...for cleaning the hydronic circuit Open the valve completely item 22 Start up the system pump Read the pressure drop of the plate heat exchanger as thedifferencebetweentheunitinletandoutletpressures i...

Страница 37: ...s measured an decreased flow rate if a higher value than the set point is measured This flow rate variation is realised observing the minimum and maximum admissible unit flow rates as well as the mini...

Страница 38: ...t is measured the flow rate is increased If a lower delta T value than the set point is measured the flow rate is decreased This flow rate variation is realised observing the minimum and maximum admis...

Страница 39: ...low rate l s Water flow rate l s Water flow rate l s Water flow rate l s Legend 1 30RQS 30RQSY 039 2 30RQS 30RQSY 045 3 30RQS 30RQSY 050 4 30RQS 30RQSY 060 5 30RQS 30RQSY 070 6 30RQS 30RQSY 078 Legend...

Страница 40: ...0RQSY 039 2 30RQS 30RQSY 045 3 30RQS 30RQSY 050 4 30RQS 30RQSY 060 5 30RQS 30RQSY 070 6 30RQS 30RQSY 078 Legend 1 30RQS 30RQSY 080 2 30RQS 30RQSY 090 3 30RQS 30RQSY 100 4 30RQS 30RQSY 120 5 30RQS 30RQ...

Страница 41: ...3 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard configuration It can also be located...

Страница 42: ...or air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required configuration of the stages consult the 30RB R...

Страница 43: ...s moisture in the circuit The presence of bubbles in the sight glass indicates an insufficient charge or non condensables in the system The presence of moisture changes the colour of the indicator pap...

Страница 44: ...utral in relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier SCS NOTES Monitoring during operation Follow the regulat...

Страница 45: ...Easy and fast installation plug play 30RQS RQSY 039 160 HP variable speed single pump hydronic mod 116V Single high pressure water pump with variable speed drive VSD water filter electronic water flow...

Страница 46: ...l configuration for the desuperheater option is factory assembled 18 1 Physical data 30RQS 30RQSY units with partial heat reclaim using desuperheaters option 49 30RQS RQSY partial heat reclaim mode 03...

Страница 47: ...er 4 Air condenser coils 5 Expansion valve EXV 6 Damage limitation option in case of a fire relief valve 7 Electric heater to protect the desuperheater against frost not supplied 8 Desuperheater insul...

Страница 48: ...temperature and to find the position of the connection block on the board refer to the 30RB RQTouch Pilot Junior control manual Other parameters directly affecting the effective capacity reclaimed at...

Страница 49: ...r the pump every 40 000 hours for applications with water every 15 000 hours for applications with glycol concentrations above 30 To facilitate maintenance operations it is recommended to installshut...

Страница 50: ...s with a low pressure jet and a bio degradable cleaner Checktheunitoperatingparametersandcomparethem with previous values Carry out an oil contamination test Replace the oil if necessary Check and if...

Страница 51: ...et metal plates 4 2 H M6 screw Stauff clamps 10 Earth screw Compressor 2 8 BPHE Brazed plate heat exchanger 20 6 Air heat exchanger We recommend that finned coils are inspected regularly to check the...

Страница 52: ...e pressure Saturat temp Relative pressure 20 297 4 807 28 1687 52 3088 19 312 5 835 29 1734 53 3161 18 328 6 864 30 1781 54 3234 17 345 7 894 31 1830 55 3310 16 361 8 924 32 1880 56 3386 15 379 9 956...

Страница 53: ...inals are tight All cables and thermistors have been inspected for crossed wires All plug assemblies are tight Check air handling systems All air handlers are operating All chilled water valves are op...

Страница 54: ...an the minimum unit flow rate The flow rate in l s corresponds to the specification of l s Carry out the QUICK TEST function see RB 30RQ Touch Pilot Junior control manual Check and register the config...

Страница 55: ......

Страница 56: ...7 Supersedes order No 13465 12 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www ecode...

Отзывы: