23
5 - PHYSICAL DATA, 30RQS UNITS
For units with fans with variable available pressure (30RQSY 039-160) please refer to chapter 7.
30RQS
039
045
050
060
070
078
080
090
100
120
140
160
Sound levels
Standard unit
Sound power level
(1)
dB(A)
80
81
81
86
87
87
84
84
84
84
90
90
Sound pressure level at 10 m
(2)
dB(A)
49
49
49
55
55
55
52
52
52
52
58
58
Standard unit + option 15LS
Sound power level
(1)
dB(A)
79
80
80
80
80
80
83
83
83
83
83
83
Sound pressure level at 10 m
(2)
dB(A)
48
48
48
48
48
48
51
51
51
51
51
51
Dimensions
Lenght
mm
1090
1090
1090
1090
1090
1090
2273
2273
2273
2273
2273
2273
Depth
mm
2109
2109
2109
2109
2109
2109
2136
2136
2136
2136
2136
2136
Height without buffer tank module
mm
1330
1330
1330
1330
1330
1330
1330
1330
1330
1330
1330
1330
Height with buffer tank module
mm
1930
1930
1930
1930
1930
1930
1930
1930
1930
1930
1930
1930
Operating weight
(3)
Standard unit without hydronic module
kg
497
504
533
546
547
554
739
886
894
953
1054
1072
Standard unit with hydronic module
Single high-pressure pump
kg
529
537
563
576
576
584
769
918
926
989
1093
1111
Dual high pressure pump
kg
555
563
588
602
602
610
795
963
971
1037
1130
1148
Single high-pressure pump + Buffer tank module option
kg
925
933
959
972
972
980
1202
1351
1359
1422
1526
1544
Dual high pressure pump + Buffer tank module option
kg
951
959
984
998
998
1006
1228
1396
1404
1470
1563
1581
Compressors
Hermetic scroll compressor 48.3 r/s
Circuit A
2
2
2
2
2
2
2
3
3
3
2
2
Circuit B
-
-
-
-
-
-
-
-
-
-
2
2
No. of capacity steps
2
2
2
2
2
2
2
3
3
3
4
4
Refrigerant charge
(3)
R-410A
Circuit A
kg
12.5
13.5
16.5
17.5
18.0
16.5
21.5
27.5
28.5
33.0
19.0
18.5
teqCO
2
26.1
28.2
34.5
36.5
37.6
34.5
44.9
57.4
59.5
68.9
39.7
38.6
Circuit B
kg
-
-
-
-
-
-
-
-
-
-
19.0
18.5
teqCO
2
-
-
-
-
-
-
-
-
-
-
39.7
38.6
Oil charge
POE SZ160 (EMKARATE RL-32-3MAF)
Circuit A
l
5.8
7.2
7.2
7.2
7.0
7.0
7.0
7.2
7.0
7.0
7.0
7.0
Circuit B
l
-
-
-
-
-
-
-
-
-
-
7.0
7.0
Capacity control type
Touch pilot junior
Minimum capacity
%
50
50
50
50
50
50
50
33
33
33
25
25
Air heat exchangers
Grooved copper tubes, aluminium fins
Fans
Axial Flying Bird VI fans with rotating shroud
Quantity
1
1
1
1
1
1
2
2
2
2
2
2
Maximum total air flow
l/s
3692
3690
3910
5285
5284
5282
7770
7380
7376
7818
10568 10568
Maximum rotation speed
r/s
12
12
12
16
16
16
12
12
12
12
16
16
Water heat exchanger
Direct-expansion plate heat exchanger
Water volume
l
2.6
3.0
4.0
4.8
4.8
5.6
8.7
8.7
9.9
11.3
12.4
14.7
Without hydronic module
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
With hydronic module (option)
Single or dual pump (as selected)
Pump, Victaulic screen filter, relief valve, expansion tank, water + air purge valves, pressure sensors
Expansion tank volume
l
12
12
12
12
12
12
35
35
35
35
35
35
Expansion tank pressure
(4)
bar
1
1
1
1
1
1
1
1.5
1.5
1.5
1.5
1.5
Max. water-side operating pressure
kPa
400
400
400
400
400
400
400
400
400
400
400
400
With Buffer tank module (option)
Single or dual pump (as selected)
Pump, Victaulic screen filter, relief valve, expansion tank, purge valves (water + air), pressure sensors
Water volume
l
250
250
250
250
250
250
250
250
250
250
250
250
Expansion tank volume
l
18
18
18
18
18
18
35
35
35
35
35
35
Expansion tank pressure
(4)
bar
1
1
1
1
1
1
1,5
1,5
1,5
1,5
1,5
1,5
Max. water-side operating pressure
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with and without hydronic module
Victaulic
Connections
inch
2
2
2
2
2
2
2
2
2
2
2
2
Outside tube diameter
mm
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
60.3
Chassis paint colour
Colour code RAL 7035
(1)
In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2)
In dB ref 20 μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information,
calculated from the sound power level Lw(A).
(3)
Weight shown is a guideline only. Please refer to the unit nameplate.
(4)
When delivered, the standard pre-inflation of the tank is not necessarily the optimal value for the system. To permit changing the water volume, change the inflation pressure
to a pressure that is close to the static head of the system. Fill the system with water (purging the air) to a pressure value that is 10 to 20 kPa higher than the pressure in
the tank.